UNPACKING

 

 

Carefully  remove  the  CD30SE  dehumidifier  unit  from  its  transit  box  and 
visually check for signs of transit damage. If there is evidence of damage DO 
NOT attempt to operate the unit, call your supplier for advice. Do not discard 
the  packing;  it  will  be  useful  when  transporting  the  dehumidifier  unit  in  the 
future. 

 

INTRODUCTION 
 

The  Ebac  CD30SE  industrial  dehumidifier  removes  moisture  from  the  air 
through the refrigeration process. 
 
The Ebac CD30SE is basically comprised of: 
 

A)

  A compressor 

B)

  A refrigerant evaporator coil 

C)

  A refrigerant condenser coil 

D)

  One circulation fan 

E)

  A drain tray for collecting and disposing of condensed moisture 

F)

  A solid state timer for hot gas defrost cycle 

G)

  An adjustable membrane-type humidistat 

H)

  A cabinet to house the above components 

 
The fan draws the moist air through the cold evaporator coil which cools the 
air below its dew point. Moisture forms on the evaporator coil and is collected 
in the condensate tray which is equipped with a permanent drain. The cooled 
air then passes through the hot condenser coil where it is reheated using the 
same  energy  removed  during  the  cooling  phase  plus  the  additional  heat 
generated  by  the  compressor.  The  air  is,  therefore  discharged  from  the 
dehumidifier  at  a  slightly  higher  temperature  with  a  lower  absolute  humidity, 
than that which entered. Continuous circulation of air through the dehumidifier 
gradually reduces the relative humidity within the area. 
The CD30SE dehumidifier is a rugged reliable drying unit designed to operate 
effectively  over  a  broad  range  of  temperature  and  humidity  conditions.  A 
powerful  and  reliable  active  hot  gas  defrost  system,  controlled  by  an 
electronic timer, guarantees positive de-icing, thereby optimizing operation at 
low temperatures. 
The  unit  incorporates  a  welded  steel  chassis  and  is  finished  in  an  epoxy 
coating for resilience to damage caused by rough handling. 
The CD30SE dehumidifier is fitted with an adjustable humidistat to enable you 
to select the level of dryness. 

Содержание CD30SE

Страница 1: ...Page 1 of 12 Drawing TPC500 Issue 1 Date 29 01 20 CD30SE INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL www eipl co uk...

Страница 2: ...1 Date 29 01 20 CD30SE PACKAGE CONTENTS Item Description Quantity 1142050 Dehumidifier 1 1139504 Wall mount bracket 1 3082214 Brass wood screw 3 3088525 Rawl plug 3 3014338 PVC tube 12mm I D 3 M 30861...

Страница 3: ...point Moisture forms on the evaporator coil and is collected in the condensate tray which is equipped with a permanent drain The cooled air then passes through the hot condenser coil where it is rehe...

Страница 4: ...he Global Warming Potential GWP of refrigerants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R407c 1610 For type and weight of refrigerant contained in this u...

Страница 5: ...the maximum setting c Check the compressor is running d Leave the machine running for 15 minutes e Observe the evaporator coils to confirm frost formation i If the air temperature is below 70 F an eve...

Страница 6: ...distat which has been factory pre set at 70 RH allows for connection to an external warning system This warning indicating system will be monitored by the customer and will warn and indicate when the...

Страница 7: ...e 25 C the coil may be covered with droplets of water rather than frost Partial frosting accompanied by frosting of the thin capillary tubes indicates loss of refrigerant gas or low charge 4 Check all...

Страница 8: ...he refrigerant compressor The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may leak causing...

Страница 9: ...oss of refrigerant gas 4 Blocked filter dryer 1 Check all of the above 2 Contact the Factory Service Center 3 Contact the Factory Service Center 4 Contact the Factory Service Center Little or no defro...

Страница 10: ...MBER Compressor 1 3944958 Refrigeration Coil Set 1 3020740 Evaporator Coil 1 2139528 Fan Motor 1 3035773 Fan Blade 1 3040129 Timer Board 1 1619519 Humidistat 1 3035145 Humidistat Knob 1 3030421 Soleno...

Страница 11: ...oto Protocol The refrigeration system is hermetically sealed The Global Warming Potential GWP of refrigerants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R40...

Страница 12: ...ww eipl co uk sales eipl co uk American Sales Office Ebac Industrial Products Inc 700 Thimble Shoals Blvd Suite 109 Newport News Virginia 23606 2575 USA Tel 01 757 873 6800 Fax 01 757 873 3632 www eba...