REPAIRS 

 

 

1. 

Should  an  electrical  component  fail,  consult  the  Factory  Service 
Center to obtain the proper replacement part. 

 

 

 

2. 

If refrigerant gas is lost from the machine, it will be necessary to use 
a  refrigeration  technician  to  correct  the  fault.    Contact  the  Factory 
Service Center prior to initiating this action.  

 

 

 

Any  competent  refrigeration  technician  will  be  able  to  service  the 
equipment.  The following procedure must be used: 

 
 

 

a.  The source of the leak must be determined and corrected. 

 
 

 

b.  The  machine  should  be  thoroughly  evacuated  before 

recharging. 

 

 

 

 

c.  The  unit  must  be  recharged  with  refrigerant  measured 

accurately by weight. 

 
 

 

d.  For evacuation and recharging of the machine, use the crimped 

and brazed charging stub attached to the side of the refrigerant 
compressor. 

 

 

 

 

The  charging  stub  should  be  crimped  and  rebrazed  after 
servicing.  

N

EVER

 

allow permanent service valves to be fitted to 

any part of the circuit.  Service valves may leak causing further 
loss of refrigerant gas. 

 

 

 

3. 

The  refrigerant  compressor  fitted  to  the  dehumidifier  is  a  durable 
unit that should give many years of service.  Compressor failure can 
result from the machine losing its refrigerant gas.  The compressor 
can be replaced by a competent refrigeration technician.   

 
 

 

Failure  of  the  compressor  can  be  confirmed  by  the  following 
procedure: 

 
 

 

a.  Establish  that  power  is  present  at  the  compressor  terminals 

using a voltmeter. 

 

 

 

b.  With the power disconnected, check the continuity of the internal 

winding  by  using  meter  across  the  compressor  terminals.    An 
open circuit indicates that the compressor should be replaced. 

 

 

 

c.  Check that the compressor is not grounded by establishing that 

a  circuit  does  not  exist  between  the  compressor  terminals  and 
the shell of the compressor.    

Содержание 1018110

Страница 1: ...Page 1 of 16 Drawing TPC252 Issue 6 Date 10 12 13 CD425 1018110 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL www eipl co uk ...

Страница 2: ...Page 2 of 16 Drawing TPC252 Issue 6 Date 10 12 13 CD425 PACKAGE CONTENTS Item Description Quantity 1018110 Dehumidifier 1 3086119 Jubilee clip 2 3014315 Reinforced tubing 16mm I D 2 X 3M TPC252 Manual 1 ...

Страница 3: ...Page 3 of 16 Drawing TPC252 Issue 6 Date 10 12 13 ...

Страница 4: ...in tray for collecting and disposing of condensed moisture f A cabinet to house the above components The fan draws the moist air through the evaporator coils which cools the air below its dew point Moisture forms on the evaporator and is collected in the condensate tray which leads away to a permanent drain The cooled air then passes through the hot condenser where it is reheated using the same en...

Страница 5: ...rigerants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R407c 1610 For type and weight of refrigerant contained in this unit please refer to the product data label MODEL CD425 HEIGHT 1193 mm 47 WIDTH 1092 mm 43 DEPTH 482 mm 19 WEIGHT 160 kg 353 lbs AIRFLOW 1750 CFM 2975M3 Hr TOTAL POWER 3680 MAX MAXIMUM OPERATING TEMPERATURE 35ºC 95ºF POWER SUPPLY 220V 3PH ...

Страница 6: ...rocess a Remove the front cover b Check the actual relative humidity inside the area c Set humidity control to a LOWER value than the actual relative humidity d After approximately 6 minutes check the compressor is running e Leave the machine to run for 15 minutes NOTE ensure that the set humidity see c above is set very low as the compressor will switch off when the actual RH coincides with the s...

Страница 7: ...nd flooding of the chamber WIRING Connect a suitably fused 3 phase mains power supply to the MAINS T B terminal block inside the electrical box located at the control panel end of the machine DRAINAGE Connect the outlet from the drain tray located behind the front grille and under the evaporator coils to a permanent drain Please ensure that the drainage does not rise above the level of the CD425 s...

Страница 8: ...emperatures above 25 C the coil may be covered with droplets of water rather than frost Partial frosting accompanied by frosting of the thin capillary tubes indicates loss of refrigerant gas or low charge 4 Check all wiring connections 5 To check the operation of the defrost system ensure the air temperature is below 20 ºC switch the machine on and leave it running for approximately 1 hour The mac...

Страница 9: ...the refrigerant compressor The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may leak causing further loss of refrigerant gas 3 The refrigerant compressor fitted to the dehumidifier is a durable unit that should give many years of service Compressor failure can result from the machine losing ...

Страница 10: ...ng diagram to find fault and repair Little or no water extraction 1 Insufficient air movement 2 Compressor fault 3 Loss of refrigerant gas 4 Blocked filter dryer 1 Check all of the above 2 Contact the Factory Service Center 3 Contact the Factory Service Center 4 Contact the Factory Service Center Unit vibrates excessively 1 Loose compressor 2 Damaged fan 1 Tighten the nuts on the compressor mounts...

Страница 11: ...r Dryer 3020930 1 Capillary Tube 3014251 12 X 1400mm X 0 047 R407c Freon Refrigerant 3100451 2 5kg Drain Tube 2014315 3 meters 3 8 Copper Tube 3014203 2 meters 1 2 Copper Tube 3014204 2 meters 5 8 Copper Tube 3014205 2 meters Cork Tape 3100223 1 2 Roll Fan Motor 3030140 1 Axial Fan 3010119 1 Solenoid Coil 3030402 1 Humidistat 1132200 1 Momentary Switch 3030634 1 Indicator Lamp Holder 3034513 2 12V...

Страница 12: ... 6 Date 10 12 13 Spare parts available online ww EIPLDIRECT com Humidistat Control Knob 2017707 1 Contactor 037H0021 3030355 1 Contactor 037H0041 3030362 1 Relay 3030270 1 Overload 3032646 1 Transformer 3031129 1 Defrost Timer 1619400 1 ...

Страница 13: ... WRITTEN OR IMPLIED WARRANTY WITH RESPECT TO THE FOREGOING DESCRIBED MERCHANDISE For Your Records Model ____________________ S N ______________________ Date Received ______________ SAVE THIS SECTION FOR YOUR RECORDS CLIP AND RETURN THIS CARD PLEASE NOTE WARRANTY REGISTRATION To ensure that your Ebac Dehumidifier is accorded the full coverage provided by this warranty please complete and mail this ...

Страница 14: ...Page 14 of 16 Drawing TPC252 Issue 6 Date 10 12 13 ...

Страница 15: ...Page 15 of 16 Drawing TPC252 Issue 6 Date 10 12 13 ...

Страница 16: ...www eipl co uk sales eipl co uk American Sales Office Ebac Industrial Products Inc 700 Thimble Shoals Blvd Suite 109 Newport News Virginia 23606 2575 USA Tel 01 757 873 6800 Fax 01 757 873 3632 www ebacusa com sales ebacusa com German Sales Office Ebac Industrial Products Ltd Gartenfelder Str 29 37 Gebäude 35 D 13599 Berlin Germany Tel 49 3043 557241 Fax 49 3043 557240 www eip ltd de sales eip ltd...

Отзывы: