Thermoelectric Air conditioner installation and 

operation manual  

 

FOR 5500 Btu MODEL #’S 

 

 

AAC-170-4XT 

AAC-170-4XT-HC 

AAC-170-XXXXX

  

    
    

Cooling Solutions for 

Cooling Solutions for 

Cooling Solutions for 

Cooling Solutions for     

Mission

Mission

Mission

Mission----Critical Electronics

Critical Electronics

Critical Electronics

Critical Electronics    

Содержание AAC-170 Series

Страница 1: ...oelectric Air conditioner installation and operation manual FOR 5500 Btu MODEL S AAC 170 4XT AAC 170 4XT HC AAC 170 XXXXX Cooling Solutions for Cooling Solutions for Cooling Solutions for Cooling Solutions for Mission Mission Mission Mission Critical Electronics Critical Electronics Critical Electronics Critical Electronics ...

Страница 2: ...ALLING THE AIR CONDITIONER 6 2 5 INSTALL THE DRAIN LINES 8 2 6 APPLY POWER 9 3 OPERATION 3 1 THERMOSTAT SET POINTS AND HEATING COOLING UNITS 10 3 2 MAINTENANCE 10 EIC SOLUTIONS INC EIC SOLUTIONS INC EIC SOLUTIONS INC EIC SOLUTIONS INC 700 VETERANS WAY SUITE 200 WARMINSTER PA 18974 PHONE 1 215 443 5190 or 1 800 497 4524 FAX 215 443 9564 EMAIL info eicsolutions com VISIT US ON THE WEB AT www eicsolu...

Страница 3: ...e practical for real world applications and are now found in everything from consumer goods to spacecraft Your EIC Solutions Thermoelectric Air Conditioner operates on this principle so there is no compressor and no expensive ozone depleting CFC s EIC s air conditioners use Thermoelectric modules sandwiched between high performance aluminum heat sinks high CFM axial fans and a patented electronic ...

Страница 4: ...closure See Figure 2 1 and 2 2 Vertically mounted mounted on the side of an enclosure 5500 BTU units are always mounted with the exposed heatsink fins facing left and right Fig 2 1 The unit cannot be mounted vertically and turned 90 degrees with the exposed heatsink fins at the top and bottom The AAC 170 4XT is equipped with a built in vertical condensate drip pan Once installed the drain hoses mu...

Страница 5: ...5 5 5 5 1 800 497 4524 EIC SOLUTIONS INC 215 443 5190 FIGURE 2 1 FIGURE 2 2 ...

Страница 6: ... 4 Using a pencil center punch or other method mark the exact center point of each mounting hole on the enclosure 5 Using the jigsaw cut the opening in the enclosure 6 Using the 17 64 drill bit drill a hole at each of the marks you made earlier 2 4 INSTALLING THE AIR CONDITIONER INSTALL THE AIR CONDITIONER 1 Lay the air conditioner down with the cold side side with the thermostat facing up 2 Take ...

Страница 7: ...7 7 7 7 1 800 497 4524 EIC SOLUTIONS INC 215 443 5190 FIG 2 3 ...

Страница 8: ...ded with the AC unit Review the Fig 2 4 below for suggested drain line configurations FIG 2 4 YOU MUST USE THE FACTORY INSTALLED HORIZONTAL DRIP PAN IF YOU INSTALL THE AIR CONDITIONER HORIZONTALLY FIG 2 2 ON THE TOP OF YOUR ENCLOSURE FAILURE TO DO SO MAY ALLOW CONDENSATE TO DRIP IN AN UNCONTROLLED MANNER CAUSING DAMAGE TO YOUR EQUIPMENT ...

Страница 9: ...rs are as follows Black or Brown line White or Blue line neutral Green or Green Yellow ground Amperage for 220 VAC unit is 10 3 amps Upon applying power to the air conditioner the fans on the cold side inside the enclosure will come on The hot side fans outside the enclosure may also run depending on where the thermostat is set The cold side fans always run to circulate air within your enclosure t...

Страница 10: ...C Thermoelectric Air Conditioners are virtually maintenance free The only time maintenance is required is when a unit is installed in an extremely dirty environment In these cases the hot side heat sinks outside the enclosure should be inspected regularly for a build up of dust or dirt If a build up is present on the heat sink fins it can be easily removed as follows 1 Disconnect the power from th...