1.  GENERAL INFORMATION 

1.1 PRINCIPLES OF OPERATION 

n 1834 Jean Peltier discovered that by passing a current through two dissimilar conductors the 
junction of those materials will either absorb or release heat depending on the direction of the 
current flow.   Thirteen years earlier Thomas Seebeck had discovered that current would flow 
when you placed a temperature gradient across the junction of two dissimilar metals.  These 

two  discoveries  were  the  basis  of  thermoelectrics.    With  the  advent  of  modern  semiconductors 
thermoelectric  devices  became  practical  for  real  world  applications  and  are  now  found  in 
everything from consumer goods to spacecraft.   

Your EIC Solutions Thermoelectric Air Conditioner operates on this principle so there is no 

compressor  and  no  expensive,  ozone  depleting  CFC’s.    EIC’s  air  conditioners  use  Thermoelectric 
“modules” sandwiched between high performance aluminum heat sinks and high CFM axial fans to 
“pump” the heat from the inside of your enclosure to the outside, without exposing your delicate 
electronics to any outside air or contaminates.  See Figure 1.1.  

EIC  uses  only  the  highest  quality  components  in  our  air  conditioners  and  you  can  expect 

years of trouble free cooling from these solid-state devices.  Every unit we sell is backed by our 
one year parts and labor warranty. 

 

FIGURE 1.1 

Содержание AAC-145A-4XT Series

Страница 1: ...ctric Air conditioner installation and operation manual FOR 1500 Btu MODEL S AAC 145A 4XT AAC 145A 4XT HC AAC 145A 4XT XXXXX Cooling Solutions for Cooling Solutions for Cooling Solutions for Cooling Solutions for Mission Mission Mission Mission Critical Electronics Critical Electronics Critical Electronics Critical Electronics ...

Страница 2: ... 3 OPERATION 3 1 THERMOSTAT SET POINTS AND HEATING COOLING UNITS 8 3 2 MAINTENANCE 8 4 SPECIFICATIONS 4 1 STANDARD SPECIFICATIONS 10 5 APPENDIX A STANDARD CUTOUT 11 B NARROW FLANGE CUTOUT 11 C EXTENSION FRAME CUTOUT 12 EIC SOLUTIONS INC EIC SOLUTIONS INC EIC SOLUTIONS INC EIC SOLUTIONS INC 700 VETERANS WAY SUITE 200 WARMINSTER PA 18974 PHONE 1 215 443 5190 or 1 800 497 4524 FAX 215 443 9564 EMAIL ...

Страница 3: ... devices became practical for real world applications and are now found in everything from consumer goods to spacecraft Your EIC Solutions Thermoelectric Air Conditioner operates on this principle so there is no compressor and no expensive ozone depleting CFC s EIC s air conditioners use Thermoelectric modules sandwiched between high performance aluminum heat sinks and high CFM axial fans to pump ...

Страница 4: ...ur enclosure or horizontally on the top of your enclosure See Figure 2 1 and 2 2 Vertically mounted 1500 Btu units are always mounted with the exposed heatsink fins facing up and down never left and right Fig 2 1 Vertical installations often require the use of a Condensate Drip Pan part DP V depending on a number of factors including internal enclosure temperatures and ambient temperatures humidit...

Страница 5: ...ENCLOSURE DP V DRIP PAN HOT SIDE FANS COLD SIDE FANS HOT SIDE HEAT SINKS COLD SIDE HEAT SINKS COLD SIDE HEAT SINKS HOT SIDE HEAT SINKS HORIZONTAL INSTALLATION OF 1500 BTU UNIT WITH INTERNALLY MOUNTED DP 145H DRIP PAN AND DRAIN TUBE ENCLOSURE HOT SIDE OF AC OUTSIDE OF ENCLOSURE COLD SIDE OF AC INSIDE OF ENCLOSURE DRAIN TUBE COLD SIDE FANS HOT SIDE FANS COLD SIDE HEAT SINK FINS HOT SIDE HEAT SINKS H...

Страница 6: ...f each mounting hole on the enclosure Also mark the four corners of the section to be cut out 5 Remove the stencil and using a pencil or other method connect the marks you made at the corners of the cut out forming a rectangle 6 Using the jigsaw cut the opening in the enclosure 7 Using the appropriate drill bit drill a hole at each of the mounting hole marks you made earlier 8 Using the 8 32 tap t...

Страница 7: ... confirm the voltage required and then apply appropriate power as outlined below Universal voltage units For 120 VAC power plug the supplied IEC 320 C13 to NEMA 5 15P cord into the unit Plug the other side into a standard 120 volt grounded outlet Amperage for the unit at 120 VAC is 6 0 amps For 220 240 VAC power either remove the NEMA 5 15P plug from the supplied power cord for a non supplied plug...

Страница 8: ...s operating in an ambient environment that may drop below 45F it is not recommended that the cooling thermostat be set lower than 50F Setting the thermostat lower than 50F in this environment could result in ice forming on the cold side of the unit 3 2 MAINTENANCE MAINTENANCE EIC Thermoelectric Air Conditioners are virtually maintenance free The only time maintenance is required is when a unit is ...

Страница 9: ...OLUTIONS INC 215 443 5190 NEVER EXPOSE THE COLD SIDE OF THE AIR CONDITIONER INSIDE THE ENCLOSURE TO WATER If you have any questions about any aspect of your EIC air conditioner don t hesitate to call us at the numbers listed below ...

Страница 10: ...220 V Input Voltage Range 100 240 V Current 6 0 A Heating Capability HC Units Only 1360 BTU hr 400 W Weight 25 kg 55 lbs Cold Side Airflow 95 cfm 160 m3 hr Hot Side Airflow 140 cfm 235 m3 hr Sound Level at 1 meter 62 dBA Operating Temperature Range 4 to 140 F 20 to 60 C Storage Temperature Range 4 to 185 F 20 to 85 C Cooling Thermostat Accuracy 1 0 F 0 6 C ...

Страница 11: ...APPENDIX A and B Enclosure cutout for Standard Flange models only DO NOT use with Narrow Flange models or Extension Frame Drawing A Enclosure cutout for Narrow Flange models only DO NOT use with standard models or Extension Frame Drawing B Holes to be 8 32 TAP ...

Страница 12: ...12 12 12 12 1 800 497 4524 EIC SOLUTIONS INC 215 443 5190 APPENDIX C Enclosure cutout for 1500 BTU air conditioner EXTENSION FRAME ONLY Holes to be 203 ...

Отзывы: