3.1  THERMOSTAT SET POINTS AND HEATING/COOLING UNITS 

SETTING THE THERMOSTAT 

 

Your  EIC  air  conditioner  is  equipped  with  an  adjustable  thermostat.    The  set  point  you 

choose should be based on the desired internal temperature of the enclosure.  The air conditioner 
will run until the set point temperature is achieved within the enclosure and then the hot side fans 
and the thermoelectric cooling modules will shut down.  The cold side fans will continue to run, 
circulating the air to maintain a uniform temperature within the enclosure. 

HEATING AND COOLING UNITS 
 

If you purchased an HC unit (heating and cooling), the heater operation is controlled by a 

fixed-point thermostat.  This thermostat is set to turn the heaters on when the temperature within 
the enclosure falls to approximately 45

°

 F and turn the heaters off when the temperature rises to 

approximately 55

°

 F.   

 

The  cooling  operation  is  controlled  by  the  adjustable  thermostat.    To  avoid  having  the 

heating and cooling on at the same time, do not set the cooling thermostat below 70

°

 F. 

 

3.2  MAINTENANCE 

MAINTENANCE 

 

EIC  Thermoelectric  Air  Conditioners  are  virtually  maintenance-free.    The  only  time 

maintenance is  required  is  when a unit is  installed in  an  extremely  dirty  environment.    In  these 
cases, the hot side heat sinks (outside the enclosure) should be inspected regularly for a build-up 
of dust or dirt.  If a build-up is present on the heat sink fins, it can be easily removed as follows: 

 

1.

 

Disconnect the power from the unit.   

2.

 

Dry  dust/dirt  can  be  removed  using  compressed  air  to  blow  out  the  heat  sinks.    Do  not 
direct any high-pressure air at the fans.   

3.

 

Your AAC-145-4XT air conditioner is rated NEMA 4X and is designed to allow for water wash 
down  of  the  hot  side  of  the  unit,  which  is  outside  of  the  enclosure 

(never  the  cold  side 

which is inside the enclosure).

 

 A pressure washer can be used to carefully clean the hot 

side heat sink fins.  Never direct high-pressure water at the fans or the joint formed by the 
mounting flange, gasket and enclosure.  Never allow the cold side of your unit to get wet.  
Always check your serial label before proceeding with a water wash down. 

 

Keeping the hot side heat sink fins free from any insulating build-up of dirt or dust will ensure 

long, trouble-free operation of your air conditioner. 

 

NEVER  EXPOSE  THE  COLD  SIDE  OF  ANY  AIR  CONDITIONER  (INSIDE  THE  ENCLOSURE)  TO 

WATER.

 

 

If you have any questions about any aspect of your EIC air conditioner, don’t hesitate to call us at 
the numbers listed below.

 

Содержание AAC-145-4XT-EP

Страница 1: ...nditioner installation and operation manual FOR 1500 Btu MODEL S AAC 145 4XT EP AAC 145 4XT HC EP AAC 145 4XT NF EP AAC 145 4XT HC NF EP Cooling Solutions for Cooling Solutions for Cooling Solutions for Cooling Solutions for Mission Mission Mission Mission Critical Electronics Critical Electronics Critical Electronics Critical Electronics ...

Страница 2: ...abinet The outside of the cabinet may be in outdoor atmosphere There is a barrier in the middle of the unit separating inside and outside sections The unit is intended to be permanently connected The unit meets the following standards ANSI ISA 12 12 01 2012 Nonincendive Electrical Equipment for Use in Class I and II Division 2 and Class III Division 1 and 2 Hazardous Classified Locations Dated 07 ...

Страница 3: ...TALLING THE AIR CONDITIONER 7 INSTALL THE DRIP PAN 9 APPLY POWER 9 3 OPERATION 3 1 thermostat set points and heating cooling units 10 3 2 maintenance 10 EIC SOLUTIONS INC EIC SOLUTIONS INC EIC SOLUTIONS INC EIC SOLUTIONS INC 700 VETERANS WAY SUITE 200 WARMINSTER PA 18974 PHONE 1 215 443 5190 or 1 800 497 4524 FAX 215 443 9564 EMAIL info eicsolutions com VISIT US ON THE WEB AT www eicsolutions com ...

Страница 4: ...ic Air Conditioner operates on this principle so there is no compressor and no expensive ozone depleting CFC s EIC s air conditioners use Thermoelectric modules sandwiched between high performance aluminum heat sinks high CFM axial fans and a patented electronic design to pump the heat from the inside of your enclosure to the outside without exposing your delicate electronics to any outside air or...

Страница 5: ...irty environment 2 2 ORIENTATION Your AC unit can be mounted either vertically on the front rear or sides of your enclosure See Figure 2 1 Vertically mounted 1500 Btu units are always mounted with the exposed heatsink fins facing up and down never left and right Fig 2 1 Vertical installations often require the use of a Condensate Drip Pan part DP V depending on a number of factors including intern...

Страница 6: ...ATION OF 1500 BTU UNIT WITH DP V VERTICAL DRIP PAN AND DRAIN TUBE HOT SIDE OF AC OUTSIDE OF ENCLOSURE COLD SIDE OF AC INSIDE OF ENCLOSURE DRAIN TUBE ENCLOSURE DP V DRIP PAN HOT SIDE FANS COLD SIDE FANS HOT SIDE HEAT SINKS COLD SIDE HEAT SINKS COLD SIDE HEAT SINKS HOT SIDE HEAT SINKS ...

Страница 7: ...ied in the installation manual 4 Using a pencil center punch or other method mark the exact center point of each mounting hole on the enclosure Also mark the four corners of the section to be cut out 5 Using the jigsaw cut the opening in the enclosure 6 Using the 29 drill bit drill a hole at each of the marks you made earlier 7 Using the 8 32 tap tap each of the holes you have drilled 2 4 INSTALLI...

Страница 8: ...8 8 8 8 1 800 497 4524 EIC SOLUTIONS INC 215 443 5190 Figure 2 2B Narrow Flange models only DO NOT use with standard models Figure 2 2A Standard Flange models only DO NOT use with Narrow Flange models ...

Страница 9: ...LY POWER Once the air conditioner is mounted check the serial label and confirm the voltage required and then apply appropriate power as outlined below The unit is intended to be permanently connected Attach the wires to an appropriate power source using standard safe wiring methods Wire colors are as follows Black or Brown line White or Blue line neutral Green or Green Yellow ground A wiring diag...

Страница 10: ...tually maintenance free The only time maintenance is required is when a unit is installed in an extremely dirty environment In these cases the hot side heat sinks outside the enclosure should be inspected regularly for a build up of dust or dirt If a build up is present on the heat sink fins it can be easily removed as follows 1 Disconnect the power from the unit 2 Dry dust dirt can be removed usi...

Отзывы: