background image

1

-800-497-4524                                    WWW.EICSOLUTIONS.COM                                    215-443-5190

 

6.

 

Remove the two starter screws and place a nylon washer on each and reinstall. 

7.

 

Tighten all screws. 

 
INSTALL THE DRIP PAN 

1.

 

Two hose fittings were provided with the drip pan, a right angle and a straight fitting.  

Choose one and install it on the drip pan.  Be sure if you use the right angle fitting it is 
facing the desired direction prior to installing the drip pan. 

2.

 

There is one mounting hole in the drip pan, match this hole with the long mounting screw 
protruding into the enclosure at the bottom of the AC unit.  Push the drip pan onto this 

screw. 

3.

 

Using the 8-32 keps nut provided, attach the drip pan to the air conditioner. 

4.

 

Attach the supplied PVC drain tube to the hose fitting on the drip pan.  This tube should be 
routed to the bottom of the enclosure and fed through a 3/8” hole to the outside. 

5.

 

If you mount the unit horizontally, the drip pan is pre-installed and you will only need to 

remove the existing hole plug and install the hose fitting and PVC drain hose. 

 
 
APPLY POWER 

Once the air conditioner is mounted, check the serial label and confirm the voltage required 
and then apply appropriate power as outlined below. 
 

Universal voltage units: 
For 120 VAC power plug the supplied IEC 320-C13 to NEMA 5-15P cord into the unit.  Plug the 
other side into a standard 120 volt, grounded outlet.  Amperage for the unit at 120 VAC is 
1.8 amps. 
 
For 220 – 240 VAC power either remove the NEMA 5-15P plug from the supplied power cord 
for a non-supplied plug or use a non-supplied IEC 320-C13 cord.  Amperage for the unit at 
220 VAC is 0.9 amps. 

 

DC voltage units: 
This unit will have a supplied power cord.  Connect the wires to an appropriate power 
source using standard safe wiring methods.  Wire colors are as follows: 

  

 

Red - Positive 

 

 

 

Black  -  Negative   

 

If you purchased a Digital Temperature Controller with your AC unit, a separate wiring diagram 

has been provided which will show the correct method of applying power to your air conditioner. 
 

Upon applying power to the air conditioner turn the power switch to the ON position.  The fans 

on the cold side (inside the enclosure) will come on.  The hot side fan (outside the enclosure) may 

also run depending on where the thermostat is set.  The cold side fans always run when the unit is 
powered on to circulate air within your enclosure thereby eliminating any “hot spots”.  The hot 
side fan will only run when the air conditioner is cooling. 

Содержание AAC-140C-4XT Series

Страница 1: ...LUTIONS COM 215 443 5190 EIC SOLUTIONS INC Thermoelectric Air conditioner installation and operation manual FOR 400 Btu MODEL S AAC 140C 4XT AAC 140C 4XT HC AAC 140C 4XT XXXXX Cooling Solutions for Mission Critical Electronics ...

Страница 2: ...ENCLOSURE 6 2 4 INSTALLING THE AIR CONDITIONER 7 INSTALL THE DRIP PAN 7 APPLY POWER 7 3 OPERATION 3 1 THERMOSTAT SET POINTS AND HEATING COOLING UNITS 8 3 2 MAINTENANCE 8 4 APPENDIX 10 EIC SOLUTIONS INC 700 VETERANS WAY SUITE 200 WARMINSTER PA 18974 PHONE 1 215 443 5190 or 1 800 497 4524 FAX 215 443 9564 EMAIL info eicsolutions com VISIT US ON THE WEB AT www eicsolutions com D 22 Rev A 02 07 2020 ...

Страница 3: ...devices became practical for real world applications and are now found in everything from consumer goods to spacecraft Your EIC Solutions Thermoelectric Air Conditioner operates on this principle so there is no compressor and no expensive ozone depleting CFC s EIC s air conditioners use Thermoelectric modules sandwiched between high performance aluminum heat sinks and high CFM axial fans to pump t...

Страница 4: ...re or horizontally on the top of your enclosure See Figure 2 1 and 2 2 Vertically mounted 400 Btu units are always mounted with the exposed heatsink fins at the bottom and the fans at the top Fig 2 1 Vertical installations often require the use of a Condensate Drip Pan part DP 140V depending on a number of factors including internal enclosure temperatures and ambient temperatures humidity levels q...

Страница 5: ...5 1 800 497 4524 WWW EICSOLUTIONS COM 215 443 5190 FIGURE 2 1 FIGURE 2 2 ...

Страница 6: ...each mounting hole on the enclosure Also mark the four corners of the section to be cut out 5 Remove the stencil and using a pencil or other method connect the marks you made at the corners of the cut out forming a rectangle 6 Using the jigsaw cut the opening in the enclosure 7 Using the appropriate drill bit drill a hole at each of the mounting hole marks you made earlier 8 Using the 8 32 tap tap...

Страница 7: ...rm the voltage required and then apply appropriate power as outlined below Universal voltage units For 120 VAC power plug the supplied IEC 320 C13 to NEMA 5 15P cord into the unit Plug the other side into a standard 120 volt grounded outlet Amperage for the unit at 120 VAC is 1 8 amps For 220 240 VAC power either remove the NEMA 5 15P plug from the supplied power cord for a non supplied plug or us...

Страница 8: ...eating until the cooling turns back on If the air conditioner is operating in an ambient environment that may drop below 45F it is not recommended that the cooling thermostat be set lower than 50F Setting the thermostat lower than 50F in this environment could result in ice forming on the cold side of the unit 3 2 MAINTENANCE MAINTENANCE EIC Thermoelectric Air Conditioners are virtually maintenanc...

Страница 9: ...nsulating build up of dirt or dust will ensure long trouble free operation of your air conditioner NEVER EXPOSE THE COLD SIDE OF THE AIR CONDITIONER INSIDE THE ENCLOSURE TO WATER If you have any questions about any aspect of your EIC air conditioner don t hesitate to call us at the numbers listed below ...