EIC Solutions AAC-140 Series Скачать руководство пользователя страница 6

 

1

-800-497-4524                   EIC SOLUTIONS, INC

.

                       215-443-5190 

TOOLS AND MATERIALS NEEDED: 

 

AAC-140 cut out stencil (cut out is the same for all types of this model) 

 

Center Punch 

 

Tape Measure and pencil 

 

Jigsaw or suitable alternative 

 

Electric drill 

 

# 29 drill bit (.136”) (Not used for extension frame option) 

 

# 8-32 tap and tap handle (Not used for extension frame option) 

 

.1875” drill bit (Extension frame option only) 

 

# 8-32 x 3/8” stainless machine screws (supplied) 

 

Nylon washers (supplied) 

 

One neoprene gasket (supplied) 

CUT THE OPENING AND DRILL MOUNTING HOLES IN THE ENCLOSURE 

1.

 

Using the guidelines provided in the installation manual choose an appropriate location for 
the air conditioner on your enclosure. 

2.

 

Tape the cut out stencil to the enclosure in the location you have chosen.   

3.

 

Before marking, cutting or drilling check that the location meets the clearance 
requirements as specified in the installation manual.   

4.

 

Using a pencil, center punch or other method, mark the exact center point of each 
mounting hole on the enclosure.   Also mark the four corners of the section to be cut out. 

5.

 

Remove the stencil and using a pencil or other method, connect the marks you made at the 
corners of the cut out, forming a rectangle. 

6.

 

Using the jigsaw, cut the opening in the enclosure. 

7.

 

Using the appropriate drill bit, drill a hole at each of the mounting hole marks you made 
earlier. 

8.

 

Using the 8-32 tap, tap each of the holes you have drilled (standard frame models only). 

 

2.4  INSTALLING THE AIR CONDITIONER 

INSTALL THE AIR CONDITIONER 

1.

 

Before starting the installation be sure the power and thermostat wires are connected to 

the terminal strip on the side of the unit and that they are long enough to reach both the 
power source and the desired thermostat mounting location.  This will eliminate having to 
access the terminal strip once the unit is installed.  See the “Apply Power” section of this 
manual on page 7. 

2.

 

Lay the air conditioner down with the cold side fan (side with the terminal strip) facing up. 

3.

 

Take the supplied gasket and lay it down on the flange. 

4.

 

Take one of the supplied mounting screws and, from the under side of the flange, push it up 
through the top right mounting hole, and through the hole in the gasket.  The gasket hole is 

undersized and will hold the screw in place.  Repeat this on the top left mounting hole.   

5.

 

Set the AC unit in the hole you’ve cut in the enclosure, and using a screwdriver, carefully 
start the two screws you attached to the gasket to the tapped holes in the enclosure.  Do 
not tighten these at this time. 

6.

 

Install the rest of the screws in the flange placing a nylon washer on each fastener and 
screw them into the tapped holes in the enclosure.  Do not tighten them completely.  If you 
have purchased a vertical drip pan, you will need to install the long screw in the center hole 

in the bottom flange.   

7.

 

Remove the two starter screws and place a nylon washer on each and reinstall. 

8.

 

Tighten all screws. 

Содержание AAC-140 Series

Страница 1: ...NC 215 443 5190 EIC SOLUTIONS INC Thermoelectric Air conditioner installation and operation manual FOR 400 Btu MODEL S AAC 140 T AAC 140 4XT AAC 140 T HC AAC 140 4XT HC AAC 140 XXXX Cooling Solutions for Mission Critical Electronics ...

Страница 2: ...ENCLOSURE 5 2 4 INSTALLING THE AIR CONDITIONER 6 INSTALL THE DRIP PAN 7 APPLY POWER 7 3 OPERATION 3 1 THERMOSTAT SET POINTS AND HEATING COOLING UNITS 8 3 2 MAINTENANCE 8 4 APPENDIX 9 EIC SOLUTIONS INC 700 VETERANS WAY SUITE 200 WARMINSTER PA 18974 PHONE 1 215 443 5190 or 1 800 497 4524 FAX 215 443 9564 EMAIL info eicsolutions com VISIT US ON THE WEB AT www eicsolutions com D 06 Rev F 11 12 2013 ...

Страница 3: ...ods to spacecraft Your EIC Solutions Thermoelectric Air Conditioner operates on this principle so there is no compressor and no expensive ozone depleting CFC s EIC s air conditioners use Thermoelectric modules sandwiched between high performance aluminum heat sinks high CFM axial fans and a patented electronic design to pump the heat from the inside of your enclosure to the outside without exposin...

Страница 4: ...lly on the front rear or side of your enclosure See Figure 2 1 Vertically mounted 400 Btu units are always mounted with the exposed heatsink fins at the top and bottom and the terminal on the side Fig 2 1 Vertical installations often require the use of a Condensate Drip Pan part DP 140V depending on a number of factors including internal enclosure temperature ambient temperature humidity levels qu...

Страница 5: ...ut size and hole locations has been included in this manual see Appendix A B The instructions for installing the air conditioner are printed below VERTICAL INSTALLATION OF AAC 140 400 BTU UNIT WITH DP 140V VERTICAL DRIP PAN AND DRAIN TUBE HOT SIDE OF AC OUTSIDE OF ENCLOSURE COLD SIDE OF AC INSIDE OF ENCLOSURE DRAIN TUBE ENCLOSURE DP 140V DRIP PAN HOT SIDE FAN COLD SIDE FAN HOT SIDE HEAT SINK FINS ...

Страница 6: ...ng the 8 32 tap tap each of the holes you have drilled standard frame models only 2 4 INSTALLING THE AIR CONDITIONER INSTALL THE AIR CONDITIONER 1 Before starting the installation be sure the power and thermostat wires are connected to the terminal strip on the side of the unit and that they are long enough to reach both the power source and the desired thermostat mounting location This will elimi...

Страница 7: ...ur AC unit a separate wiring diagram has been provided which will show the correct method of applying power to your particular air conditioner The unit is supplied with a separate thermostat that should be mounted inside the enclosure and wired to the unit per the supplied schematic The thermostat can be mounted in any orientation The ideal location for mounting the thermostat is near the particul...

Страница 8: ...up of dust or dirt If a build up is present on the heat sink fins it can be easily removed as follows 1 Disconnect the power from the unit 2 Dry dust dirt can be removed using compressed air to blow out the heat sinks Do not direct any high pressure air at the fan 3 NEMA 4X models of our air conditioners are designed to allow for water wash down of the hot side of the unit which is outside of the ...

Страница 9: ...9 1 800 497 4524 EIC SOLUTIONS INC 215 443 5190 APPENDIX A Enclosure cutout for 400 BTU air conditioner NON EXTENSION FRAME Holes to be 8 32 TAP ...

Страница 10: ...10 1 800 497 4524 EIC SOLUTIONS INC 215 443 5190 APPENDIX B Enclosure cutout for 400 BTU air conditioner EXTENSION FRAME OPTION ONLY Holes to be 1875 Clearance TOP ...

Страница 11: ...11 1 800 497 4524 EIC SOLUTIONS INC 215 443 5190 APPENDIX C Wiring for 400 BTU Models without heat option APPENDIX D ...

Страница 12: ...12 1 800 497 4524 EIC SOLUTIONS INC 215 443 5190 Wiring for 400 BTU Models with heat option ...