RadioLINK Troubleshooting

It  is  imperative  that  all  Alarms  in  your  system  communicate  with  each  other.  The 

number of walls, ceilings and metal objects in the signal path reduces the strength 

of  the  RadioLINK  signals  between  the  Alarms.  Accordingly,  one  or  more  Alarms 

may have difficulties in communicating to all the other Alarms in the system. If, when 

checking the RadioLINK interconnection, some of the Alarms do not respond to the 

button test, then you will need to either:
(i) Position another RadioLINK Alarm to act as a ‘repeater’ (see Interconnection 

with RadioLINK Modules below) between the Alarms which are not communicating 

and so shorten the path and/or by-pass an obstacle which is blocking the signal. 

When the new Alarm is fitted, house code all Alarms again, as described above.
(ii) rotate / re-locate the units (e.g. move them away from metal surfaces or wiring).

After making these changes to the RF signal path, the RadioLINK signals may still

not be reaching all the Alarms in your system, even though they have already been

House Coded successfully. (see Section on “RadioLINK Limitations”).
It  is  important  to  check  that  all  Alarms  are  communicating  in  their  final  installed 

positions. If Alarms are rotated and/or resited, we would recommend that all the 

Alarms are returned to the default settings and then House Coded again in their 

final positions (see above). The RadioLINK interconnection should then be checked 

again by button testing all units.
The RadioLINK module can be returned to the originally default settings by pressing 

and holding the House Code button on until the blue light turns on solidly and then 

flashes slowly. This will take about 10 seconds. This clears any previous House 

Code settings.

7

Содержание RadioLINK Ei200MRF

Страница 1: ...ation and installation of your Module The leaflet should be regarded as part of the product If you are just installing this Module the leaftet must be given to the householder The leaflet is to be giv...

Страница 2: ...uction Installation Interconnection with RadioLINK Modules RadioLINK Troubleshooting Testing Getting your Alarm Serviced Guarantee Technical Specification Contact Us Table of Contents 3 3 6 7 8 9 9 10...

Страница 3: ...on Monoxide Alarms Ei207 Ei208 Series It is advisable that all RadioLINK Carbon Monoxide Alarms should be installed where possible with the antennas see figure 2 in the same orientation i e essentiall...

Страница 4: ...attach to the mounting plate in the same manner in less than 15 minutes They automatically exit house code mode after 30 minutes 6 When in the House Code mode the blue light on the front of the Alarm...

Страница 5: ...om its mounting plate and quickly pressing and holding the House Code button until the blue light comes on solidly again Release the button and the blue light will go out after 4 seconds indicating th...

Страница 6: ...t you House Code your Alarm system Another very important reason for house coding is that after the Alarms are house coded they all act as repeaters i e they repeat the messages from other Alarms and...

Страница 7: ...rms again as described above ii rotate re locate the units e g move them away from metal surfaces or wiring After making these changes to the RF signal path the RadioLINK signals may still not be reac...

Страница 8: ...button is released If they are interconnected using RadioLINK modules hold down the Test button until the blue light on the cover of the Alarm illuminates see figure 3 Check that all other Alarms soun...

Страница 9: ...Alarm was purchased and the date of purchase Five Year Guarantee Ei Electronics guarantees this RF RadioLINK Module for five years from date of purchase against any defects that are due to faulty mate...

Страница 10: ...ng Freq 868 499MHz 20 kHz Output power 10dBm nom Range 250m in free air min Protocol Radiolink Alarm Transmit Interval 10 sec Initial Alarm duration 3 5 sec Short Alarm duration 50 ms Status Message d...

Страница 11: ...ates that this product should not be disposed of via the normal household waste stream Proper disposal will prevent possible harm to the environment or to human health When disposing of this product p...

Страница 12: ...P N B17161 Rev 0 Ei Electronics 2011...

Отзывы: