Ei Electronics Ei144 Heat Скачать руководство пользователя страница 2

 

Shannon Free Zone, Shannon, Co. Clare, Ireland. 

Ph.

+353 61 471277   

Fx.

+353 61 471053   

 

Email.

 [email protected]

 

 

Web:

 www.eielectronics.com 

E & OE  As our policy is one of continuous product development, we reserve the right to alter product details without prior notice

.           

Ei144 DataSht RevA

 

 
 

Model 

Ei144 Heat 

Installation & Placement 

 

Wiring for Interconnected Alarms 

 

         

       

 

 

Be very careful about correctly wiring the alarms as mixing Live and Neutral 
will blow/damage interconnected alarms. 
 
Locate heat alarms in rooms adjoining or on escape routes 

– kitchens, 

garages, boiler houses etc. where smoke alarms are unsuitable.  Install within 
5.3m of potential sources of fire.  
 
Please consult instruction booklet for specific installation details 

Important Precaution: 

Do not install the actual smoke/heat 
alarm itself in new or renovated 
buildings until all work is completed 
(including floor coverings) and the 
building has been fully cleaned. 
The wiring can be installed when 
appropriate. (Excessive dust and 
debris from building work can 
contaminate the smoke chamber 
and cause problems, and it will also 
invalidate the guarantee). If it must 
be installed, cover it completely, 
particularly around the edges, with 
a dust cover (eg. a plastic bag), 
until all cleaning is finished.. 
Connect wires to the unit as in 
wiring diagram. All wiring must 
comply with local codes. 
 
 

 

Technical Specification 

 

Sensor  

Thermistor 

 
Sensitivity:

 

Complies with BS 5446 Part 2: 
2003 

 
Source: 

Contains no radioactive material 

 
Airspeed:

 

Essentially immune to the effect 

 

of airspeed. 

 
Button Test:

 

Simulates the effect of heat and 
checks electronics and horn. 

 
Supply Voltage: 

230V AC 

 
Battery back up: 

9V Alkaline Battery 

 
Power-On Indicator:

   Continuous green LED 

 
Alarm:  

Electronic Piezoelectric horn 
in unit  

 
Alarm Sound Output:

  85dB (minimum) at 3m 

 
Alarm Status:

 

Red LED flashes every second on 

 

unit sensing heat

 

 

 

 

 

 
 

 

  

 

Temperature Range:

  0° to 40°C 

 
Humidity Range:

 

15% to 95% Relative Humidity 

 
Interconnect:

 

Up to 12 interconnected mains 
powered easi-fit smoke or heat 
alarms, along with an EI128 relay 
base 

 
Fixing:

 

Easi-Fit mounting base 

 
Plastic material:

 

UL94VO flame retardant 

 
Dimensions: 

145mm diameter x 52mm depth

 

 
Weight: 

281g

 

 
Warranty:

 

5 year (limited) warranty 

 
Approvals:

 

Kitemarked to BS5446-2:2003, CE 
Approved

 

 
Specifications are subject to change

 

 