EGS Appleton WSRD Series Скачать руководство пользователя страница 2

EGS Electrical Group • 800-621-1506 • www.appletonelec.com

331114-1    Rev. B  08/12/08  

Page 2 

APPLICATION:

• 

Designed to supply power to portable or 

fi

 xed 

electrical equipment such as welders, infrared 
ovens, batch feeders, conveyors and truck and 
marine docks.

• 

Designed to supply three (3) phase, grounded 

electrical power to the aforementioned electrical 
equipment.

• 

Designed to provide an interlocked receptacle 

for use in ordinary (non-hazardous) locations, as 
de

fi

 ned by the National Electrical Code (NEC). In 

addition, the receptacle is designed such that a 
mating plug can only be engaged and disengaged 
when the switch handle is in the "OFF" position.

• 

Ideal for use on shipping docks, ports, and 

other "ship to shore" applications.

• 

Suitable for use in locations that require a degree 

of protection from the elements (See TABLE 
A). Enclosure cover and receptacle housing are 
sealed with gaskets. The receptacle housing 

fl

 ip 

cover is gasketed to seal against the housing. 
In addition, mating plugs can be engaged to the 
receptacle face to provide weatherproof union,

SHORT CIRCUIT RATING FUSED/

NONFUSED: 

• 

Suitable for use on a circuit capable of delivering 

not more than 10,000 RMS symmetrical Amperes, 
600 VAC maximum .

WARNING

• 

Do not modify these devices in any way. 

Replace missing or broken parts with the proper 
replacement parts from Appleton Electric, LLC.

• 

Modi

fi

 cation of these devices or substitution 

of parts with non-standard parts may result in 
serious or fatal personal injury from electrocution. 

WARNING

• 

If any part(s) of 

"WSRD"

 unit or the mating plug    appear 

to be missing, broken or show signs of damage:

DISCONTINUE USE IMMEDIATELY!

This condition could cause serious or fatal personal injury 
due to electrocution and/or equipment damage. Repair with 
the proper replacement part(s) before continuing service.

WARNING

• 

Turn off power supplying WSRD interlocked receptacle 

before and during installation and maintenance.

• 

Failure to do so may result in serious or fatal  injury 

from electrocution.

 

TABLE  C

TABLE  B

TIGHTENING TORQUE — LINE SIDE

DISCONNECT SWITCH LUG SCREWS

SLOTTED HEAD SCREWS

WIRE SIZE (AWG)

TORQUE (LB.-IN.

)

#14 -#10 AWG

35

#8 AWG

40

#6 - #4 AWG

45

#3 - #2 AWG

70

ACP & CPH PLUGS FOR "WSR" RECEPTACLES

CABLE 

DIAMETER (In.)

CURRENT 

RATING

CATALOG 

NUMBER

.390 - 1.375

30

ACP3034BC

.500 -   .875

30

CPH3034B

.500 - 1.375

60

ACP6034BC

.500 -   .750

60

CPH6034A

.750 - 1.00

60

CPH6034B

1.000 - 1.375

60

CPH6034C

.500 - 1.375

60

CPH6034BC

.875 - 1.906

100

ACP1034C

*CPH Plug is rated for NEMA 3R applications only.

Содержание Appleton WSRD Series

Страница 1: ...rained and experienced in the use and maintenance of this equipment and not for consumers or consumer use Appleton warranties do not extend to and no reseller is authorized to extend Appleton s warran...

Страница 2: ...vering not more than 10 000 RMS symmetrical Amperes 600 VAC maximum WARNING Do not modify these devices in any way Replace missing or broken parts with the proper replacement parts from Appleton Elect...

Страница 3: ...lug screws to the torques given in TABLE C and TABLE E for the listed wire ranges Failure to do so may result in over stressed wire termina tions which could cause the conductors to pull out of the di...

Страница 4: ...COVER OPEN Unit shown is Catalog Number WSRD6352SQ NEMA 12 Version FIGURE C Device Rating Dimension in Inches A B C 30 60 Amp 16 75 16 50 22 25 100 Amp 20 75 20 50 26 25 EGS Electrical Group 800 621...

Страница 5: ...ors for the bolts C Install the two top bolts leaving 3 16 to 5 16 under the heads The bolts must be engaged at least five 5 full threads 2 MOUNTING THE WSRD INTERLOCKED RECEPTACLE Place the interlock...

Страница 6: ...e 10 Make sure the assembly labels located on the inside of the cover remain clean and legible B DISCONNECT SWITCH Disconnect switches occasionallt fail with use and need to be replaced The disconnect...

Страница 7: ...recommendations contained herein are based on information and tests we believe to be reliable The accuracy or completeness thereof are not guaranteed In accordance with Appleton Electric LLC Terms an...

Страница 8: ...EGS Electrical Group 800 621 1506 www appletonelec com 331114 1 Rev B 08 12 08 Page 8...

Отзывы: