331114-1

INSTRUCTION SHEET     

WSRD NEMA 4 Series:

Interlocked Appleton Powertite™ Compatible 
Receptacle with heavy duty single throw dis-
connect switch.

ELECTRICAL RATINGS:

Maximum Voltage: 600VAC at 50-60 Hz*, 
250 VDC 30, 60,100 Amperes — Continuous 
Line Current not to exceed 80% of fuse rating 
employed in other than motor circuits.

*

 For 400 Hz applications, consult factory.

Compliances:
• 

UL Listed

 UL50 for Enclosures

 UL1682 for Receptacles

 NEC wire bending space, Table 373-6(b)

 Federal Speci

fi

 cation WS865C

 Major automotive speci

fi

 cations

STANDARD FEATURES:
• 

Epoxy coated 

fi

 nish on receptacle and switch 

housing.

• 

Factory installed fuse pullers for fusible 

disconnect switch. 

OPTIONS:
• 

Electrical Interlocks :    

1 N.O. or  1 N.C.  

                                      2 N.O. or  2 N.C.

Read instructions carefully and with full 

understanding for safe installation and 

operation.

Instructions for Installation, Operation and Maintenance of:

"WSRD" Interlocked Receptacles — 30, 60 & 100 Ampere

Except as expressly provided by Appleton 
Electric LLC (Appleton) in writing, Appleton 
products are intended for ultimate purchase 
by industrial users and for operation by per-
sons trained and experienced in the use and 
maintenance of this equipment and not for 
consumers or consumer use. Appleton 
warranties do not extend to, and no reseller 
is authorized to extend Appleton's warranties 
to, any consumer.

TABLE  A

HORSEPOWER RATING:

FIGURE A

Shown Above:
Non-Fused Version Catalog Number 

WSRD63542N4WSD

 

WSRD  SERIES

Catalog Number

DC 

Volts

AC 

Volts Amp

Switch 

Type

HP Rating AC

Stand.

Max

Sheet Metal Enclosure NEMA 12

WSRD3352SQ

250

600

30

Fused

7.5

20

WSRD33542SQ

250

600

30

Non-Fused

--

30

WSRD3352WSQ

250

600

30

Fused

7.5

20

WSRD33542WSQ

250

600

30

Non-Fused

--

30

WSRD6352SQ

250

600

60

Fused

15

50

WSRD63542SQ

250

600

60

Non-Fused

--

60

WSRD6352WSQ

250

600

60

Fused

15

50

WSRD63542WSQ

250

600

60

Non-Fused

--

60

WSRD10352SQ

250

600

100

Fused

30

75

WSRD10342SQ

250

600

100

Non-Fused

--

75

WSRD10352WSQ

250

600

100

Fused

30

75

WSRD103542WSQ

250

600

100

Non-Fused

--

75

Stainless Steel Enclosure NEMA 3, 3R, 4, 4X, 12

WSRD3352N4SD

250

600

30

Fused

7.5

20

WSRD33542N4SD

250

600

30

Non-Fused

--

30

WSRD3352N4WSD

250

600

30

Fused

7.5

20

WSRD33542N4WSD

250

600

30

Non-Fused

--

30

WSRD6352N4SD

250

600

60

Fused

15

50

WSRD63542N4SD

250

600

60

Non-Fused

--

60

WSRD6352N4WSD

250

600

60

Fused

15

50

WSRD63542N4WSD

250

600

60

Non-Fused

--

60

WSRD10352N4SD

250

600

100

Fused

30

75

WSRD10342N4SD

250

600

100

Non-Fused

--

75

WSRD10352N4WSD

250

600

100

Fused

30

75

WSRD103542N4WSD

250

600

100

Non-Fused

--

75

Содержание Appleton WSRD Series

Страница 1: ...rained and experienced in the use and maintenance of this equipment and not for consumers or consumer use Appleton warranties do not extend to and no reseller is authorized to extend Appleton s warran...

Страница 2: ...vering not more than 10 000 RMS symmetrical Amperes 600 VAC maximum WARNING Do not modify these devices in any way Replace missing or broken parts with the proper replacement parts from Appleton Elect...

Страница 3: ...lug screws to the torques given in TABLE C and TABLE E for the listed wire ranges Failure to do so may result in over stressed wire termina tions which could cause the conductors to pull out of the di...

Страница 4: ...COVER OPEN Unit shown is Catalog Number WSRD6352SQ NEMA 12 Version FIGURE C Device Rating Dimension in Inches A B C 30 60 Amp 16 75 16 50 22 25 100 Amp 20 75 20 50 26 25 EGS Electrical Group 800 621...

Страница 5: ...ors for the bolts C Install the two top bolts leaving 3 16 to 5 16 under the heads The bolts must be engaged at least five 5 full threads 2 MOUNTING THE WSRD INTERLOCKED RECEPTACLE Place the interlock...

Страница 6: ...e 10 Make sure the assembly labels located on the inside of the cover remain clean and legible B DISCONNECT SWITCH Disconnect switches occasionallt fail with use and need to be replaced The disconnect...

Страница 7: ...recommendations contained herein are based on information and tests we believe to be reliable The accuracy or completeness thereof are not guaranteed In accordance with Appleton Electric LLC Terms an...

Страница 8: ...EGS Electrical Group 800 621 1506 www appletonelec com 331114 1 Rev B 08 12 08 Page 8...

Отзывы: