1.
Set
Drop value
to the number of units, that the measured
value may drop within a defined period of time.
2.
Set
Drop time
to the number of minutes, over which the
change in humidity should not exceed the
Drop value
. You
can deactivate this alert by entering
0
.
1.
Set
Rise value
to the number of units, that the measured
value may rise within a defined period of time.
2.
Set
Rise time
to the number of minutes, over which the
change in humidity should not exceed the
Rise value
. You
can deactivate this alert by entering
0
.
After having configured the alerts, don't forget to save your
changes.
1.
Click on
Save
to apply your changes.
4.4.4 Dew point alerts
Querx TH supports two types of dew point alerts:
Dew point too high
Dew point too low
How Querx TH reacts upon occurring alerts, will be
discussed in chapter 5 'Data access and configuration of
interfaces'.
1.
In the configuration interface, open the page
Sensors
/
Dew point.
2.
Optionally, enter a
Sensor name
, through which it can be
identified in alert notifications.
1.
Set
Upper limit
to the value at which the maximum dew
point is exceeded.
2.
Set
Lower limit
to the value at which the minimum dew
point is under-run.
Configuration
20
Save your alert settings
Alert for humidity
dropping too fast
Alert for exceeded
thresholds
Alert for humidity rising
too fast