background image

 

1

AUTOMATIC    VOLTAGE    REGULATOR 

(MODEL : AVR-126) 

WARNING :   

To prevent personal injury or equipment damage, only qualified technicians /operators 

should install, operate or service this device.

 

                                 

 

CAUTION : 

    Megger and high potential test equipment should not be used. 

Incorrect use of such equipment could damage components contained in the regulator. 
 

 

1. APPLICATION

 :

      AVR 125 is voltage regulator to control brushless generator output by regulating                                                                                       

                                  the current into the generator exciter field.

 

 
 

2. FEATURES : 

2.1.  Available for low resistance exciter filed. 
2.2.  Under frequency protection circuit. 

When the generator frequency drops below the set point, generator output voltage is decreased with 
the curve proportional to the frequency. 

2.3.  Over excitation 

When the generator excitation field voltage exceeds 85Vdc, AVR output shut down to protect the 
generator winding coil from burning out. 

2.4.  Starting engine generator set, if the residual voltage remains on the stator winding of generator, 

AC output voltage is built up rapidly. 

2.5.  Durable under dust, damp and vibration. 
2.6.  Response time, below 25ms(1.5cycles) 

 
 

3. SPECIFICATIONS 

3.1.  Input : 190~277Vac, 1

Φ

, 50/60Hz, Burden 650VA (terminal 3-4) 

3.2.  Output :   
         

MODEL 

VOLTAGE 

CURRENT 

REMARKS 

AVR - 125 

125Vdc 

15A 

continuous 

                                                                               

Maximum current (for 1min.) - 20A 

                                                                                                                   

3.3.  Sensing : 1

Φ

,190 ~ 240Vac    (220V sensing – terminal 4-3) 

                          1

Φ

,380 ~ 400Vac    (380V sensing – terminal 4-E1) 

3.4.  Exciter field resistance : 2ohms to 100ohms 
3.5.  External voltage adjust rheostat : 1

, 2W 

(out of supply scope)

 

3.6.  Voltage adjust range   

Coarse adjusting (by internal rheostat) 

±

12.5% 

Fine adjusting    (by external rheostat) 

±

5% 

3.7.  voltage regulating accuracy 

±

1.0% 

3.8.  Voltage build up condition internally and automatically raised by the residual voltage from the   

Generator stator winding (minimum 3Vac) 

Содержание AVR-126

Страница 1: ...tage exceeds 85Vdc AVR output shut down to protect the generator winding coil from burning out 2 4 Starting engine generator set if the residual voltage remains on the stator winding of generator AC o...

Страница 2: ...1 Size W140 x H200 x D60 mm 4 2 Mounting size W90 x H190 mm x 5 4Holes 4 3 Color bottom and cover ivory 4 4 Frequency selection changeover switch 4 5 Weight about 2kg 5 INSTRUCTION AND CONNECTION NOT...

Страница 3: ...nnected to the F F or J K of exciter field respectively 6 ADJUSTING 6 1 Start prime mover and bring up to rated speed 6 2 Voltage would be automatically built up If not confirm until voltage build up...

Страница 4: ...system 43 50 45 48 Hz rated volt residual volt output volt residual volt output volt rated volt 55 53 58 60 Hz V V 60Hz System 50Hz System 7 FLASH EXCITING 7 1 MANUAL FIELD FLASH ESCITING When genera...

Страница 5: ...ED FLASH EXCITING Whenever start generator set to avoid no output voltage It is recommended to take automatic field flash exciting by using the generator control sequence as below drawing 8 PARALLE OP...

Страница 6: ...s F F not connected Power input leads not connected Blown or missing fuse Defective regulator Defective generator Check wiring diagram for proper Connections Flash generator field Refer to 7 FLASH EXC...

Страница 7: ...t is turned too high Rotate voltage adjust CCW until desired voltage is reached Rotate remote voltage adjust CCW until desired voltage is reached Output Voltage High No Adjustment Defective regulator...

Отзывы: