2.10 Voltage measurement
ATTENTION: High voltage!
The nominal voltage is obtained by multiplying the number of modules by 50V. Nominal system voltage should
therefore be in the range 200V-450V.
If the measured voltage deviates significantly from the nominal value, please check the electrical voltage at the
individual modules, as shown below:
Positive
Negative
Measurement:
7