8 Installing and connecting the UPS
All requirements in the technical data regarding environmental and operating
conditions must be observed to ensure trouble-free functioning of the UPS.
The following must be observed when setting up / installing the UPS
equipment:
o
Avoid extremes of temperature and atmospheric humidity. A maximum
service life, particularly in relation to the batteries, is achieved at an
ambient temperature of 15-25°C.
o
Always ensure sufficient space behind the UPS to be able to perform
the necessary connections there. The load-bearing capacity of the
support must be sufficient.
o
Observe the specified installation position. The specified installation
position is upright vertical only.
o
Make sure that ventilation of the equipment is possible at all times.
Therefore a minimum clearance of at least 50mm must be observed on
the right, left and at the rear of the UPS. Ensure an appropriate flow
channel.
o
Make sure the equipment is arranged correctly. When installed in
parent systems (e.g. machine, control cabinet), it must be ensured that
the UPS operates within the specified temperature range. A sufficient
level of forced ventilation must exist to remove excess heat that builds
up in the space where the UPS is installed.
8.1 Connecting the equipment
8.2 Connecting the UPS
The model is equipped with plug-type connections. The connection diagram
(Fig. 5) and the following information must be observed: