Note!
Commissioning:
All
Hi-O technology™
devices must be connected to the bus for
the configuration. Then the operating voltage is switched on. Subsequently con-
nected devices are only recognised after renewed connection of the operating
voltage.
At least one Emergency Open module is always necessary for operation of the
RWT locking module.
1 Configure the system via the
ePED® Service Software
(
D01104xx ePED® Ser-
vice Software
manual).
Authorisation
There are three authorisation levels:
Control
Authorisation for calling up information
Settings
Authorisation for calling up information and
restricted configuration
Installation
Authorisation without restrictions
Each authorisation level is assigned a clear authorisation code in the factory. The-
se authorisation codes must be changed for commissioning. Each authorisation
level must be assigned a clear authorisation code once again.
Lock, unlock, reset
1 Press the symbol
2 Enter an authorisation code.
3 Confirm the entry with the [
] key.
After entering a valid authorisation code, you can unlock the door.
Configuration
Authorisations
Enter an authorisation code – configuration
Some menus (such as the
System
menu) can only be opened with expanded au-
thorisation. An authorisation code for configuration is required for this.
1 Press
the symbol.
2 Press
the symbol.
The symbol is no longer shown.
3 Press one of the symbols according to an authorisation code.
4 Enter an authorisation code.
Delete any numbers entered by mistake with the [
] key.
5 Confirm the entry with the [
] key.
The menu is displayed after entry of a valid authorisation code.
Change authorisation codes for authorisation levels
1 Press the symbols in the following order:
2 Enter your authorisation code.
3 Press
the
System
menu item.
4 Press
the
User Administration
menu item.
The keyboard is displayed.
5 Press one of the symbols according to an authorisation code.
6 Assign a new authorisation code.
Delete any numbers entered by mistake with the [
] key.
7 Confirm the entry with the [
] key.
You have changed an authoisation code.
8 If necessary, repeat from step 5 until all authorization codes have been
changed.
Commissioning
Initial commissioning
All devices are connected to the
Hi-O-Technology™
bus for the initial commissio-
ning, but are not configured yet. If the voltage supply is switched on, the system
is in plug and play mode.
Interfaces for locking systems
cannot work with factory settings, because they
must be logically linked to the corresponding Emergency Open push-buttons.
Once it has been started, the installation wizard dialogue shows a series of con-
firmation messages and user prompts.
I
Note!
Process the entire dialogue sequence:
If a dialogue is closed via the
Cancel
key
or if the displayed action is not carried out, the installation must be started again
from the beginning. The RWT system configuration has not taken place and the
system cannot be locked.
Using the installation wizard
1 Press
the
·
Continue
or
OK
button if the entire dia-
logue message is correct or if you have
taken the necessary action,
·
Cancel
button if any part of the dialogue
message is incorrect or if you have not
taken the necessary action.
The installation is finished if you have been able to exit all messages with the
Continue
or
OK
button.
Once the installation is complete, the e
PED® 1386D10 door terminal
is in
normal operation
status.
Resetting to factory settings
If reset to factory settings, changes to operating data are lost. The device must
then be configured.
Within the first five seconds after switching on the operating voltage, the device
can be reset to the factory settings.
Reset to factor y settings
1 Switch off the voltage supply for at least
10 seconds.
2 Switch the voltage supply on again.
The symbol
is shown.
3 Press the symbol
.
4 Press the center of the display.
5 Answer to the confirmation request.
After confirming the request the device is
ready for use again and must be configu-
red.