E F A P O W E R   E V - Q C 4 5   -   I N S T A L L A T I O N   A N D   U S E R   M A N U A L  

12 | 32                           

5.3.3

 

HANDLING 

Due to its heavy weight, 4 (four) lifting hooks are provided on the top of the Power Cabinet as indicated on Figure 
8.
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Never  try  to  move  the  power  cabinets  by  using  tools  under  panels;  this  will  create  a  risk  of 
deformation. 
 

 

Figure 8 - EFAPOWER EV-QC45 

lifting hooks

 

 

After

 the 

power

 

cabinet

 is 

placed

, the 

lifting

 

hooks

 must  be 

removed

, and the M12 

sealing

 

screws

 must be 

inserted

 in their holes in order 

to

 

guarantee

 the 

IP54

IK10

 (

NEMA 3R

) protection degree. 

5.3.4

 

ASSEMBLY/ PLACING INSTRUCTIONS 

 

5.3.4.1

 

ANCHORING TO THE CONCRETE PAD 

 
The Quick Charging Station must  be anchored on the surface compliant  with the specifications  mentioned in 
chapter 5.2.2. 
 
The pow

er cabinet must be installed on a concrete pad using 4 (four) chemical anchors, M8 (5/16’’), 

10mm thread 

diameter 

 

length must comply with local codes, but must have at least 120mm (5”).

 

 
In the following figure, some details are shown regarding the drilling layout for the Power Cabinet. 

Only

 

4

 (four) 

points

 are 

needed

 

to

 

anchor

 the 

Unit

 on the concrete pad (marked with a red circle).  

 
For the power cabinet, the conduits 

must extend 160mm (6.3”) above the concrete, or according to local codes.

 

The 

cable entrance shall only be located as shown in the image below

 (marked in green). 

Содержание EFAPOWER EV-QC45

Страница 1: ...loser than 6 1m 20 feet of an outdoor motor fuel dispensing device EFAPOWER EV QC45 is in an IP54 IK10 NEMA 3R enclosure This Unit is intended to work below 50ᵒC 122ᵒF ambient temperature Clearance around the cabinet The air must circulate freely throughout the ventilation grids in order for the charger s cooling system to be effective The ventilation areas on the sides and back must not be blocke...

Страница 2: ... temperatures heavy dust snow and or very low temperatures it s recommended to provide additional protection either inside a building or a shelter or providing a protection roof for the Unit See example in Figure 6 Figure 6 EFAPOWEREV QC45 with shelter 5 1 2 SITE VERIFICATION AND INSPECTION Check if the installation of the Quick Charger is not planned to be made in a commercial garage repair facil...

Страница 3: ... outputs connections not available for USA market Requires a dedicated 160A circuit breaker 3P C curve Figure 7 EFAPOWEREV QC45Wiring Information NOTES In areas with frequent thunder storms Efacec recommends adding transient voltage surge suppression TVSS at the service panel for all circuits Unless required by local codes it is not necessary to install a residual current device RCD for the circui...

Страница 4: ... 2 above the concrete and 89 5mm 3 52 into the concrete 4 four sealing screws Socket head button cap screws M12x25 metric with matching flat rubber washers supplied with the Quick Charging Station End terminals for input wiring Depending on the EFAPOWER EV QC45 configuration Only DC outputs 5 five end terminals up to 35mm2 3phases neutral protective ground or DC and AC outputs not available for US...

Страница 5: ... WxDxH 1150x850x2150mm 45 3x33 5x84 6 inches 5 3 2 VISUAL INSPECTION Check if the exterior packaging has been damaged by mechanical impacts or any accidents during transportation If applicable check if the exterior panels of the EFAPOWER EV QC45 are in perfect condition Check if the interior of the Quick Charger Station is clean Check if the door of the Quick Charger Station is working properly Ch...

Страница 6: ...4 ASSEMBLY PLACING INSTRUCTIONS 5 3 4 1 ANCHORING TO THE CONCRETE PAD The Quick Charging Station must be anchored on the surface compliant with the specifications mentioned in chapter 5 2 2 The power cabinet must be installed on a concrete pad using 4 four chemical anchors M8 5 16 10mm thread diameter length must comply with local codes but must have at least 120mm 5 In the following figure some d...

Страница 7: ...instructions For the Power Cabinet it s advised to have a concrete block of at least 1000mm 34 9 square by 254mm 10 deep Check local codes to ensure compliance The bolts must extend at least 30 5mm 1 2 above the concrete and 89 5mm 3 52 into the concrete ALL SERVICING MUST BE PERFORMED ONLY BY QUALIFIED PERSONNEL DO NOT ATTEMPT TO SERVICE THE EFAPOWER EV QC45 QUICK CHARGING STATION YOURSELF DO NOT...

Отзывы: