INSTALLATION
All instructions for installing the EFAPOWER EV-QC24S are described in this chapter.
5.1
ENVIRONMENTAL REQUIREMENTS
EFAPOWER EV-QC24S reliability is dependent upon compliance of environmental specifications. The design of
the environmental control system for your EFAPOWER EV-QC24S, in case of extreme environmental conditions,
must ensure that the Unit can operate reliably while remaining within the range of its operating specifications.
5.1.1
LOCAL CONDITIONS
The installation of EFAPOWER EV-QC24S shall not be made closer than 6,1m (20 feet) of an outdoor
motor fuel dispensing device.
EFAPOWER EV-QC24S is in an IP54, IK10 (NEMA 3R) enclosure. This Unit is int
ended to work below 40ᵒC (104ᵒF)
ambient temperature.
Clearance around the unit
The air must circulate freely throughout the ventilation grids in order for the charger’s cooling system to be
effective. The ventilation areas on the sides must not be blocked, assuring that the Quick Charger cooling system
can be effective. Efacec recommends clearance of at least 1meter (40’’) in the front (HMI interface and output
cable) and 500mm (20’’) of clearance in the sides of the unit.
Input Power Cables
AC input cables must be copper with appropriate power rating.
EFAPOWER EV-QC24S was intended to be placed as showed in the Figure 4.
Figure 4 - EFAPOWER EV-QC24S placing orientation