E F A P O W E R E V - P C - I N S T A L L A T I O N A N D U S E R M A N U A L
10 | 37
5.2
SITE PREPARATION
Once the local conditions have been verified, it is time to prepare the site for the installation of the EFAPOWER
EV- PC Station.
5.2.1
UPSTREAM WIRING INFORMATION
Depending on the configuration of the EFAPOWER EV-PC, the station may have different wiring schemes as
represented in the following three figures.
CE AND GB MARKED UNITS:
•
Three phase
input connection for
CE and GB marked
units:
.
Figure 7 - EFAPOWER EV-PC CE/GB Wiring Information (Three-Phase)
Depending on the configuration of the outputs (of
the units) we can have several scenarios for the
circuit breaker to be installed in the distribution
board for each Unit. The appropriate circuit
breaker is represented in Table 3.
Efacec advises a Residual Current Device (RCD)
2P/4P Type AC or 2P/4P Type A, higher than
300mA, to ensure the upstream selectivity. All
local codes shall be taken into consideration.
NOTES
Even if the same Unit side has two outputs
(2,3kVA + any other power rate) the Table 3 is
valid because only one output will work at a time.
In areas with frequent thunderstorms, we advise
to add transient voltage surge suppression (TVSS)
at the service panel for all circuits.
1
st
Output
2
nd
Ou
tp
u
t
---
16A
3P C
20A
3P C
40A
3P C
80A
3P C
63A
3P C
100A
3P C
20A 3P C
40A 3P C
63A
3P C
80A
3P C
125A
3P C
63A
3P C
40A
3P C
63A
3P C
100A
3P C
63A 3P C
80A
3P C
63A
3P C
80A
3P C
125A
3P C
100A 3P C
125A
3P C
100A
3P C
125A
3P C
160A
3P C
Table 3 - Overcurrent protection upstream
* Only available for CE marked units
*
*
*
*