EemaX ED020480T2T Скачать руководство пользователя страница 5

1) The unit is supplied with NPT fittings., USE THESE; DO NOT USE PIPE DOPE AND DO

NOT SOLDER PIPE TO THE INLET OR OUTLET.

2) Take care to ensure that the pipes are correctly aligned with the inlet and outlet bosses in 

order to avoid excessive stress on the heater manifold.

NOTE: When soldering pipe joints remove heater from the wall. Serious damage can occur
if any soldering is done while pipes are connected to the heater.

Run water through the supply pipe to remove all debris from the pipe before connecting the
heater. Failure to do so could cause damage to the flow  switch.

3) Install isolating valves (full flow  ball valve type) on 

both

inlet and outlet pipes. This allows

unit to be isolated for maintenance purposes. (see Fig. 1)

4) When all plumbing is complete, fully check the system for water leaks at all plumbing 

connections. If leak is present take corrective action.  Fully open both inlet and outlet
ball valves.  Run all hot water outlets fed by this heater one at a time for a minute or two
until the water flow is continuous, free from ”gulping” and from all visible air pockets. 

PLUMBING HOOK-UP

NOTE

ALL MOUNTING AND PLUMBING MUST BE COMPLETE BEFORE YOU PROCEED

WITH ELECTRICAL HOOK-UP.

TEST THE INSTALLATION FOR LEAKS BEFORE CONNECTING THE

ELECTRICAL SUPPLY.

7 “

Hot outlet
1/2” Compression 
fitting
DO NOT
SOLDER

Cold inlet
1/2” Compression
fitting
DO NOT
SOLDER

4

Содержание ED020480T2T

Страница 1: ...LITIES PLEASE TAKE THE TIME TO READ NOT ONLY THIS MANUAL BUT ALSO THE WARRANTY CARD ENCLOSED WARRANTY OF THIS HEATER WILL DEPEND ON PROPER INSTALLATION OPERATION AND REQUIRED MAINTENANCE THE WARRANTY SHALL BE VOID IF THE DESIGN ORSTRUCTURE OF THE WATER HEATER HAS BEEN ALTERED IN ANY WAY WHATSOEVER THE MANUFACTURER OF THIS WATER HEATER WILL NOT BE LIABLE FOR ANY DAMAGES BECAUSE OF FAILURE TO COMPLY...

Страница 2: ...ED032480T2T 480 32kW 35 5 AVAILABLE IN EE Emergency Eye Max temperature 90 degrees S Sanitation Temperature Ambient 180 degrees ML Multi lav 0 3 gpm activation temperature set at 105 degrees FS Factory Set Temperature Ambient 180 degrees ACTIVATION FLOW RATES T2T Minimum 7 GPM Maximum 4 GPM MODEL NUMBERS COVERED ...

Страница 3: ... debris before fitting the heater otherwise the flow switches could jam in the on position The unit must be connected to its own individual electric circuit protected by a suitably rated three pole breaker The maximum voltage which can be applied across any heating module is 480 volts WARNING Improper installation adjustment alteration service or maintenance can cause DEATH SERIOUS BODILY INJURY O...

Страница 4: ...e draw off of cold water just before the unit Also do not fit an unrestricted hot water draw off point below the heater as this will tend to empty the heater by siphoning 3 NOTE ALL MOUNTING AND PLUMBING MUST BE COMPLETE BEFORE YOU PROCEED WITH ELECTRICAL HOOK UP TEST THE INSTALLATION FOR LEAKS BEFORE CONNECTING THE ELECTRICAL SUPPLY Hazardous Locations Nonincendive Type Installation 1 The unit is...

Страница 5: ...tall isolating valves full flow ball valve type on both inlet and outlet pipes This allows unit to be isolated for maintenance purposes see Fig 1 4 When all plumbing is complete fully check the system for water leaks at all plumbing connections If leak is present take corrective action Fully open both inlet and outlet ball valves Run all hot water outlets fed by this heater one at a time for a min...

Страница 6: ...es three live and one ground of the appropriate rating protected by the correctly rated three pole breaker WARNING FAILURE TO GROUND THE SYSTEM MAY RESULT IN DEATH OR SERIOUS INJURY IMPORTANT BEFORE SWITCHING ON THE POWER AT THE MAIN CIRCUIT BREAKER PANEL MAKE SURE THAT THE HOT WATER CIRCUIT IS FREE OF AIR POCKETS OR PREMATURE FAILURE OF THE ELEMENT WILL OCCUR TO DO THIS OPEN ALL HOT WATER OUTLETS...

Страница 7: ...s 1 With inlet and outlet BALL VALVES fully open turn on a hot water outlet 2 Run for 3 minute 3 Switch on electric supply at circuit breaker panel 4 The power indicator lights should now come on NOTE At this point water temperature may not be hot 5 Using the OUTLET BALL VALVE slowly reduce water flow until desired temperature is achieved at hot water outlet NOTE The water temperature is regulated...

Страница 8: ...front cover of this manual for the correct value If the resistance is much greater than the correct value call your supplier for a replacement element SYMPTOM NO HEAT OR LOW TEMPERATURE WITH INDICATOR LIGHT ON 1 WATER FLOW TOO HIGH Reduce the water flow by using an outlet ball valve See page 5 for temperature rise at various flow rates 2 INCORRECT POWER SUPPLY Make sure that the unit is connected ...

Страница 9: ...LEASE SPECIFY 480 VOLTS ON ANY ORDERS FOR ED020 PART EX3454 35 54 Ohms FOR ED024 PART EX2880 28 8 Ohms FOR ED032 PART EX2194 21 6 Ohms 10 THERMOSTATIC PCB PART EX100CV 480V SLAVE PART EX100S 480V TRIAC PART EX18 Contactor part EX08002 01 480 volts L1 ...

Отзывы: