3 x 300W Dimmer Module
DM03B01KNX
Product and Applications Description
The 3 channel Dimmer Module is designed to interface varia-
ble lighting with bus KNX/EIB and allow dimming of incandes-
cent and halogen loads of 230V, BT and TBT.
The product can control 1, 2 or 3 (C1, C2, C3) independent
lighting circuits. The outputs number depends on switch
7
7
7
7
po-
sition.
Device is intended to be installed on DIN rail.
The device configuration for commissioning in terms of physi-
cal address, group addresses and parameters is done with
ETS (Engineering Tool Software) through a download of the
Application Program
Application
Application
Application
Application Program
Program
Program
Program
Downloadable from website:
www.eelectron.com
Maximum number of group addresses:
254
254
254
254
This is the maximum number of different group addresses the
device is able to memorize.
Maximum number of associations:
255
255
255
255
This is the maximum number of associations between
communication objects and group addresses the device is able
to memorize.
Technical
Technical
Technical
Technical Specifications
Specifications
Specifications
Specifications
Power Supply
Power Supply
Power Supply
Power Supply
Power supply from EIB/KNX bus
•
Voltage
21..30V DC
•
Currnet consumption from EIB/KNX < 5mA
Power supplì from mains :
•
Voltage
230V ~ 50/60 Hz
•
Consumption without load
5W
Connections
Connections
Connections
Connections
EIB/KNX: 2 bus terminal bus 0,8mmØ
Loads and power supply :
0,75 mm
2
2,5 mm
2
Load type
Load type
Load type
Load type /
/
/
/ rated output
rated output
rated output
rated output
Incandescent or halogen lamps - 230V
C1
C1
C1
C1
C1 / C2
C1 / C2
C1 / C2
C1 / C2
C1 / C2 /
C1 / C2 /
C1 / C2 /
C1 / C2 / C3
C3
C3
C3
20..900 W
-
-
20..600 W
20..300 W
-
20..300 W
20..300 W
20..300 W
Halogen lamps (12/24V) via ferromagnetic transformer suit-
able for dimming
( The transformer shouldn’t be used with less than 75 % of
its nominal load)
C1
C1
C1
C1
C1 / C2
C1 / C2
C1 / C2
C1 / C2
C1 / C2 / C3
C1 / C2 / C3
C1 / C2 / C3
C1 / C2 / C3
20..900 VA
-
-
20..600 VA
20..300 VA
-
20..300 VA
20..300 VA
20..300 VA
Halogen lamps (12/24V) with electronic transformer
C1
C1
C1
C1
C1 / C2
C1 / C2
C1 / C2
C1 / C2
C1 / C2 / C3
C1 / C2 / C3
C1 / C2 / C3
C1 / C2 / C3
20..900 VA
-
-
20..600 VA
20..300 VA
-
20..300 VA
20..300 VA
20..300 VA
The efficiency of the tr
The efficiency of the tr
The efficiency of the tr
The efficiency of the transformer has to be taken into a
ansformer has to be taken into a
ansformer has to be taken into a
ansformer has to be taken into ac-
c-
c-
c-
count to calculate the max. number of controlled lamps
count to calculate the max. number of controlled lamps
count to calculate the max. number of controlled lamps
count to calculate the max. number of controlled lamps ....
Standards
Standards
Standards
Standards
•
Protection class IP 30 (according to EN 60529):
•
Compliant to EN 60950 and ETSI 301 489-1 and ETSI 301
489-3
•
Safety Class II according EN 61140
•
EIB / KNX
Environmental specifications
•
Operative temperature:
0°C ÷
+ 45 °C
•
Storage temperature:
-20°C ÷
+ 60 °C
•
Relative Humidity:
max 90 %
CE Mark
In accordance with the EMC and low voltage guidelines
Physical specifications and Dimensions
•
Dimensions
6 DIN modules
•
Weight:
ca. 300 g.
•
Installation:
DIN rail (EN 60715)
Terminals, connections and command/visualisation elements
1.
1.
1.
1.
Switch
Switch
Switch
Switch auto / min / max / manual ( )
auto / min / max / manual ( )
auto / min / max / manual ( )
auto / min / max / manual ( )
2.
2.
2.
2.
Status led
Status led
Status led
Status led
3.
3.
3.
3.
Local push button
Local push button
Local push button
Local push button
4.
4.
4.
4.
Led
Led
Led
Led in
in
in
indicator of overheating protection
dicator of overheating protection
dicator of overheating protection
dicator of overheating protection
5.
5.
5.
5.
Led
Led
Led
Led indicator of overload protection / short circuit
indicator of overload protection / short circuit
indicator of overload protection / short circuit
indicator of overload protection / short circuit
6.
6.
6.
6.
ETS
ETS
ETS
ETS programmin
programmin
programmin
programming
g
g
g push button and led
push button and led
push button and led
push button and led
7.
7.
7.
7.
Selector for output number configuration
Selector for output number configuration
Selector for output number configuration
Selector for output number configuration
Setting of the minimum and maximum dimming values
Setting of the minimum and maximum dimming values
Setting of the minimum and maximum dimming values
Setting of the minimum and maximum dimming values
1
1
1
1
. Set the minimum or maximum dimming value by acting either
way:
•
setting switch
1
1
1
1
in position “
manual
manual
manual
manual
”
( )
( )
( )
( )
and acting on
push-button
3
3
3
3
(a long pressure allows dimming until the de-
sired lighting level is reached, while a short pressure
switches lighting on/off). Set the switch into position min or
max as desired, or,
•
setting switch
1
1
1
1
in position min or max as desired and set
the desired level using a communication pushbutton con-
nected to the output (need to perform the configuration via
ETS before)
2
2
2
2
. Record the value set by pressing push-button
3
3
3
3
for more than
3 seconds. Led
2
flicker twice to confirm the recording.
Note 1
Note 1
Note 1
Note 1
: If the minimal or maximum values are set out of range,
led
2
2
2
2
will flicker after the recording request.
Note 2
Note 2
Note 2
Note 2
: These limits can also be programmed via ETS.
Tes
Tes
Tes
Test
t
t
t and start up
and start up
and start up
and start up
Switch auto
Switch auto
Switch auto
Switch auto //// min
min
min
min //// max
max
max
max //// manu
manu
manu
manual
al
al
al (1)
(1)
(1)
(1)
and local
control
control
control
control
pushbuttons (3)
pushbuttons (3)
pushbuttons (3)
pushbuttons (3)
When switch
1
1
1
1
is in position “
manual
” ( ), pushbuttons
3
can be used to control output (a long pressure allows
dimming until the desired illumination level is reached, while
a short pressure switches lighting on/off).
Use the position “
auto
” of switch
1
1
1
1
in operation mode or for
configuring the product.
In position “
auto
” of switch
1
1
1
1
pushbutton
3
is inactive and
the output is controlled by telegrams received from bus
KNX/EIB.
Status led
Status led
Status led
Status led
Indicators
2
indicate the state of the corresponding outputs:
indicator on = actuated load,
indicator flashing for 5 s = no load connected.
ETS programmin
ETS programmin
ETS programmin
ETS programming
g
g
g push button and led
push button and led
push button and led
push button and led
Press lighted pushbutton
6
to carry out the physical address-
ing of the product or to check bus presence:
indicator on = the bus is present and the product is in physi-
cal addressing state.
Protection against overheating, overload
Protection against overheating, overload
Protection against overheating, overload
Protection against overheating, overload and short
and short
and short
and short----circuit
circuit
circuit
circuit
Indicator
4444
indicates an overheating condition when switch-
ed on in a fixed position: As the power available is reduced,
it is recommended to reduce the load and/or to improve dis-
sipation conditions.
Indicator
5
5
5
5
signals a short circuit when flashing or an over-
load condition when switched on in a fixed position: in such
cases, the dimmer reduces automatically the power available
and no longer controls its load, as required.
It is then necessary to check wiring and/or to decrease the
load.
Selection of the number of outputs
Selection of the number of outputs
Selection of the number of outputs
Selection of the number of outputs
Selection of the numbers of outputs is configurable
through
switch
7
7
7
7
, as described below:
When the switch is in this posi-
tion the dimmer manage only
one load (C1) with a maximum
rated power of 900W
When the switch is in this posi-
tion the dimmer manage two
loads: the first (C1) with a max-
imum rated power of 600W,
the second (C2) with a maxi-
mum rated power of 300W.
When the switch is in this posi-
tion the dimmer manage three
loads:: C1, C2, C3 everyone
with a maximum rated power of
300W.
Mounting and Wiring hints
Device is intended to be used indoor in dry places.
IMPORTANTE
IMPORTANTE
IMPORTANTE
IMPORTANTE
•
This device must be installed only by a qualified electri-
cian.
•
Install in conformity to SELV installation rules.
•
The applicable safety and accident prevention regula-
tions must be observed.
•
The device must not be opened. Any faulty devices
should be returned to manufacturer.
•
For planning and construction of electric installations, the
relevant guidelines, regulations and standards of the re-
spective country are to be considered.