INSTALLATION MANUAL

ENGLISH

Thank you for buying this product. Our company is sure that you will be
more than satisfied with the product’s performance.
Carefully read the “

WARNINGS

” pamphlet and the “

INSTRUCTION

BOOKLET

” which are supplied together with this product, since they

provide important information regarding the safety, installation, use and
maintenance of the product. This product complies with recognised technical
standards and safety regulations. We declare that this product is in
conformity with the following European Directives: 73/23/ EEC, 89/336/
EEC, 98/37/EEC and subsequent amendments.

1) GENERAL SAFETY

WARNING! An incorrect installation or improper use of the product
can cause damage to persons, animals or things.

The  “

Warnings

” leaflet and “

Instruction booklet

” supplied with this

product should be read carefully as they provide important information
about safety, installation, use and maintenance.

Scrap packing materials (plastic, cardboard, polystyrene etc) according
to the provisions set out by current standards. Keep nylon or polystyrene
bags out of children’s reach.

Keep the instructions together with the technical brochure for future
reference.

This product was exclusively designed and manufactured for the use
specified in the present documentation. Any other use not specified in
this documentation could damage the product and be dangerous.

The Company declines all responsibility for any consequences resulting
from improper use of the product, or use which is different from that
expected and specified in the present documentation.

Do not install the product in explosive atmosphere.

The construction components of this product must comply with the
following European Directives: 89/336/CEE, 73/23/EEC, 98/37/EEC and
subsequent amendments. As for all non-EEC countries, the above-
mentioned standards as well as the current national standards should
be respected in order to achieve a good safety level.

The Company declines all responsibility for any consequences resulting
from failure to observe Good Technical Practice when constructing closing
structures (door, gates etc.), as well as from any deformation which might
occur during use.

The installation must comply with the provisions set out by the following
European Directives: 89/336/CEE, 73/23/EEC, 98/37/EEC and
subsequent amendments.

Disconnect the electrical power supply before carrying out any work on
the installation. Also disconnect any buffer batteries, if fitted.

Fit an omnipolar or magnetothermal switch on the mains power supply,
having a contact opening distance equal to or greater than 3mm.

Check that a differential switch with a 0.03A threshold is fitted just before
the power supply mains.

Check that earthing is carried out correctly: connect all metal parts for
closure (doors, gates etc.) and all system components provided with an
earth terminal.

Fit all the safety devices (photocells, electric edges etc.) which are needed
to protect the area from any danger caused by squashing, conveying
and shearing, according to and in compliance with the applicable
directives and technical standards.

Position at least one luminous signal indication device (blinker) where it
can be easily seen, and fix a Warning sign to the structure.

The Company declines all responsibility with respect to the automation
safety and correct operation when other manufacturers’ components are
used.

Only use original parts for any maintenance or repair operation.

Do not modify the automation components, unless explicitly authorised
by the company.

Instruct the product user about the control systems provided and the
manual opening operation in case of emergency.

Do not allow persons or children to remain in the automation operation
area.

Keep radio control or other control devices out of children’s reach, in
order to avoid unintentional automation activation.

The user must avoid any attempt to carry out work or repair on the
automation system, and always request the assistance of qualified
personnel.

Anything which is not expressly provided for in the present instructions,
is not allowed.

2) GENERAL OUTLINE

Low-voltage operator (24Vdc) suitable for residential use. Designed for
swing gates having small-sized pillars. The operating arm, with its special
antishearing shape, allows the leaves to be manoeuvred even when the
operator is positioned well away from their fulcrum. The irreversible
electromechanical gearmotor keeps the gate locked in the closing and
opening positions.
The release lever, fitted to the outside of each operator, allows the manual

manoeuvre to be carried out very easily.

WARNING! 

The installation, the maintenance and the repair should be

done by responsible and qualified persons with an updated knowledge of
the current safety standards. It’s strictly forbidden to service the automation
when the power is on.

ATTENTION! 

The 

VIRGO

 model controller is not equipped with mechanical

torque adjustment. It is compulsory to use a control panel of the same
manufacturer, in compliance with the basic safety requirements of directives
73/23/CEE, 89/336/CEE, 98/37/CEE equipped with appropriate electric
adjusment of the torque.

3) TECHNICAL SPECIFICATIONS
3.1) VIRGO OPERATOR

Motor: ............................................................................ 24Vd.c. 2500 min

-1

Power: .................................................................................................. 40W
Insulation class: ........................................................................................ F
Lubrication: ................................................................... Permanent grease
Reduction ratio: ............................................................................... 1-1224
Output shaft revolutions: ......................................................... 2 min

-1 

MAX

Opening time 90

°

: ................................................................................. 14s

Torque supplied: ............................................................................ 170 Nm
Max leaf weight and length: .................. 2000N (~200kg) for 2m long leaf
Impact reaction: ................................................... Integrated torque limiter

................................................................................. on LINX control panel

Motion drive: ............................................................................... Lever arm
Stop: ................. Incorporated electrical limit sw mechanical locks
Manual manoeuvre: ....................................... Release lever with CLS key
Number of manoeuvres in 24h: .............................................................. 60
Environmental conditions: ............................................ from -15 to +60 

°

C

Degree of protection: ......................................................................... IP 44
Operator weight: ................. VIRGO:80N (~8kg) - VIRGO SQ:60N (~6kg)
Dimensions: .................................................................................. see fig.1

3.2)

 

LINX CONTROL PANEL

Power supply: ......................................................... 230Va.c. 

±

10% 50Hz*

Mains/low voltage insulation: ....................................... > 2MOhm 500Vdc
Working temperature ............................................................. : -10 / +55

°

C

Dielectric strength: ................................ mains/l.v. 3750Va.c. for 1 minute
Motor output current: ......................................................... 3.5A+3.5A max
Motor relay commutation current: ........................................................ 10A
Maximum motor power: ....................................................... 40W (24Vd.c.)
Power supply for accessories: ............. 24Va.c. (180mA max absorption)

....................................................... 24Va.c.safe (180mA max absorption)

Gate-open warning light: .......................... N.O. contact (24Va.c./1A max)
Blinker: ........................................................................... 24Va.c. 25W max
Dimensions: ............................................................................. see figure 1
Fuses: ...................................................................................... see figure 2
(*other voltages available on request)

3.3) VIRGO BAT BATTERY KIT (OPTIONAL - Fig.14)

Allows operation to continue even when the mains power supply is off for
a short time.
Charge voltage: ........................................................................... 27.2Vd.c.
Charge current: ............................................................................... 130mA
Data detected with external temperature of: ...................................... 25

°

C

Battery capacity: ................................................................. 2x (12V 1.2Ah)
Exhausted battery protection threshold: ..................................... 20.4Vd.c.
Battery recharge time: .................................................................... 12/14 h

NOTE: In case of operation with battery back up, the outputs to terminals
8-9 (Vsafe 24Va.c.) and 10-11 (Vsafe 24Va.c.) show a voltage of 24Vd.c.
polarised as indicated in Fig.13.
At the time of installing the VIRGO BAT Kit, check that the safety devices
are connected correctly.

4) OPERATOR INSTALLATION
4.1) Preliminary checks

Check that:

The gate structure is sufficiently sturdy and rigid.
The fixing position must be worked out according to the leaf structure. In
any case, the manoeuvring arm must push against a reinforced leaf
point (fig. 2).

The leaves can be moved manually along their entire stroke.
If the gate has not been installed recently, check the wear condition of all
its components. Repair or replace defective and worn parts.
Operator reliability and safety are directly affected by the condition of
the gate structure.

Содержание Virgo

Страница 1: ... 02 04 04 VIRGO Via Lago di Vico 44 36015 Schio VI Tel naz 0445 696511 Tel int 39 0445 696533 Fax 0445 696522 Internet www bft it E mail sales bft it AUTOMAZIONI A BRACCIO PER CANCELLI A BATTENTE ARM AUTOMATIONS FOR SWING GATES AUTOMATIONS A BRAS POUR PORTAILS BATTANTS ARM AUTOMATIONEN FUER FLUGELGITTERTIRE AUTOMATIZACIONES A BRAZO PARA PORTONES CON BATIENTE AUTOMATIZAÇÕES DE BRAÇO PARA PORTÕES DE...

Страница 2: ...ower supply is off or any faults are present the manual emergency manoeuvre can be carried out by operating the external release lever Fig 1 ref S 1 Insert the release key and turn it clockwise Fig 1 ref 1 2 Move lever S until the lock is released Fig 1 ref 2 3 Keep the lever in the release position by turning the key clockwise Fig 1 ref 3 4 Push the leaf slowly to open or close the gate To reacti...

Страница 3: ...ase of emergency Do not allow persons or children to remain in the automation operation area Keep radio control or other control devices out of children s reach in order to avoid unintentional automation activation The user must avoid any attempt to carry out work or repair on the automation system and always request the assistance of qualified personnel Anything which is not expressly provided fo...

Страница 4: ...connection to the mains use a multipolar cable with a minimum of 3x1 5mm2 cross section and complying with the previously mentioned regulations For example if the cable is out side in the open it has to be at least equal to H07RN F but if it is on the inside or outside but placed in a plastic cable cannel it has to be or at least egual to H05VV F with section 3x1 5mm2 JP1 1 2 Motor 2 connection VI...

Страница 5: ... waiting for the end of the TCA set OFF Command not entered Photocells on opening photc open OFF ON In case of obscuring this excludes photocell operation on opening During the closing phase it immediately reverses the motion OFF In case of obscuring the photocells are active both on opening and on closing When a photocell is obscured on closing it reverses the motion only after the photocell is d...

Страница 6: ...or damage to things 11 STATISTICS Having connected the UNIPRO programmer to the control unit enter the CONTROL UNIT STATISTICS menu and scroll the screenful showing the statistical parameters Board microprocessor software version Number of cycles carried out If motors are replaced count the number of manoeuvres carried out up to that time Number of cycles carried out from the latest maintenance op...

Страница 7: ...wing procedure very carefully Check the correct functioning of all safety devices limit microswitches photocells sensitive edges etc Check that the thrust anti squash force of the leaf is within the limits set by current regulations Check the manual opening command Check the opening and closing operations with the control devices in use Check the standard and customised electronic functioning logi...

Страница 8: ...N OFF off OK PRG OK i Mot ON ON OFF off OK PRG OK BLOC persist ON OFF off OK PRG OK Preal ON OFF off OK PRG OK radio prog ON OFF off OK PRG OK fixed code ON OFF off OK PRG OK OK TCA 0010 PRG OK OK 0050 PRG m1 t OK OK 0050 PRG m2 t OK OK 0045 PRG m1 t slow OK OK 0045 PRG m2 t slow OK OK 0010 PRG open delay time OK OK cls delay time 0010 PRG OK OK m1 fast time 0050 PRG OK OK 0050 PRG OK OK slow spee...

Страница 9: ...1 PRG READ OK OK OK ERASE 64 Press P1 pushbutton on radio control device Press the required T key on radio control device Ð see Fig B3 Release P1 on radio control device ADD 2ch hidden button release desired button 01 OK 01 t1 COD RX OK 1A9C OK 22FD OK 01 OK RADIO MENU ADD Allows you to add one key of a radio control device to the receiver memory after storage it displays a m e s s a g e s h o w i...

Страница 10: ...VIRGO Ver 03 51 D811415_03 Fig 1 Fig 3 Fig 2 Fig 5 Fig 6 SX 300 MIN 30 123 180 215 635 230 Fig 4 SX 300 MIN 135 123 52 52 335 120 90 390 230 120 390 230 120 90 Max 210 335 ...

Страница 11: ...O Ver 03 D811415_03 Fig 7 Fig 9 Fig 11 Fig 8 Fig 10 P1 P3 P2 T VIRGO VIRGO SQ Fti Fri 4x1mm 2 5x1 5 mm 2 2x1mm 2 3x1mm 2 2x1mm 2 RG58 4x1mm 2 2x1mm 2 Fre Fte S 3x1 5mm2 SX DX S S S L GND S C N L P F D B B 1AF ...

Страница 12: ...Fig 12 Fig 13 C1 FC1 A C C2 FC2 LEFT FC1 Close FC2 Open FC1 Close FC2 Open RIGHT Fig 14 VIRGO BAT SBS 12V 1 2 AH 12V 1 2 AH R o s s o R e d R o u g e R o t R o j o V e r m e l h o SBS LINX 1 2 3 4 5 6 JP1 1 2 3 4 5 6 7 L N 0V 25V ...

Страница 13: ... SCA 26 24 25 26 27 24 V 8888 LINX OK 8888 JP1 F 1 25AT VIRGO LINX VIRGO SQ JP1 JP2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 L N 25W max M1 M2 COM NO NC NC NC NC NO NO ANT PHOT SWO M2 SWC M2 COM FAULT ANT SHIELD SCA CH R PED 24V VSafe 24V 24V NC NC SWO M1 SWC M1 COM BLU RED STOP START VIRGO BAT VIRGO SQ M1 VIRGO LINX M2 SWO M1 SWC M1 COM 14 15 16 17 18 M1 M1 BLU R...

Страница 14: ... 18 Contatti Contacts Contacts Kontakte Contactos Contatos Contatti Contacts Contacts Kontakte Contactos Contatos Contatti Contacts Contacts Kontakte Contactos Contatos 1 3 4 1 2 2 3 4 P1 P1 T1 Led T2 TRC 1 2 P 1 P 1 T 1 T 2 T 3 T 4 P1 P1 T1 Led T2 P 1 P 1 T 1 T 2 T 3 T 4 UNIPOWER LINX UNIDA UNIFLAT UNIFLAT UNIPRO UNIRADIO UNIFLAT UNIMITTO UNITRC UNIMITTO UNITRC 8888 P1 P1 P1 Contatti Contacts Con...

Страница 15: ...3 0478760988 Fax 0033 0478769223 BFT DEUTSCHLAND BFT FRANCE BFT S p a ITALIA Via Lago di Vico 44 36015 Schio VI Tel naz 0445 696511 Tel int 39 0445 696533 Fax 0445 696522 Internet www bft it E mail sales bft it BFT Torantriebssysteme GmbH Hintere Str 100 90768 Fürth http www bft torantriebe de Tel 0911 7660090 Fax 0911 7660099 ...

Отзывы: