P/N 3101077 • REV 05 • REB 23JAN13 

 

3 / 6 

Table 1: Operating current in mA (RMS) 

Voltage  

Low dBA  

High dBA 

16 VDC  

17 

28 

24 VDC 

24 

41 

33 VDC 

31 

52 

16 VFWR 

41 

48 

24 VFWR 

51 

60 

33 VFWR  

60 

66 

VDC = Volts direct current, regulated and filtered  
VFWR = Volts full wave rectified 

Table 2: Sound level output (dBA) per CAN/ULC-S525 

Signal 

Voltage (VDC)  Low dBA  

High dBA 

Reverberant room per UL 464 [1] 

Temporal  

16 

71.3 

77.2 

 

24 

75.0 

79.8 

 

33 

77.7 

81.5 

Steady  

16 

75.8 

80.5 

 

24 

79.2 

84.1 

 

33 

82.0 

86.0 

Reverberant room per UL 268 [2] 

Temporal  

16 

77.3 

83.2 

 

24 

81.0 

85.8 

 

33 

83.7 

87.5 

Steady  

16 

81.8 

86.5 

 

24 

85.2 

90.1 

 

33 

88.0 

92.0 

[1] For UL 464 applications, low dBA settings are for private mode only 
[2] For UL 268 applications, the high setting must be used for 
evacuation 

Table 3: Audible directional characteristics 

Angle (degrees) 

Output sound pressure level 

90 (reference) 

0 dBA 

80 and 100 

−3 dBA 

70 and 110 

−6 dBA 

Horizontal axis and veritical axis reflect the same pattern 

Table 4: Sound pressure level per CAN/ULC-S525 

Signal 

Voltage 

High dBA 

Low dBA 

Temporal 

Reg. 24 VDC 

95 

91 

Reg. 24 
VFWR 

99 

95 

Steady 

Reg. 24 VDC 

93 

89 

Reg. 24 
VFWR 

96 

92 

 

Maintenance 

Do not change the factory-applied finish. 

Specifications 

 

Operating voltage (sounder 
power) 

24 VDC or 24 VFWR 

Current 
 

Operating 

 

Supervisory  

 
See Table 1 
DC = 1.46 mA, FWR = 2.15 mA 

Default settings  
 

Output volume 

 

Output tone 

 
High dBA  
Temporal pattern 

Sound level output 
 

UL 

 

ULC 

 
See Table 2 
See Table 4 

Temporal pattern 

0.5 s on, 0.5 s off, 0.5 s on, 0.5 s off, 
0.5 s on, 1.5 s off, repeat cycle 

Compatible detectors 

FX-PD, E-PD, FX-PHD, E-PHD, 
FX-HD, E-HD, V-PS, V-PHS, V-HRD, 
and V-HFD  

Compatible electrical boxes 

AB4G-SB surface box for audible 
base 

North American 4 in. square x 
2-1/2 in. (64 mm) deep box 

Standard European 100 mm² box 

Wire size 

12 to 18 AWG (0.75 to 2.5mm²) 
Sizes 16 and 18 AWG are preferred 

Base diameter 

6.0 in. (152 mm) 

Height from box (including 
detector) 

2.58 in. (66 mm) 

Maximum distance from 
ceiling (wall mount) 

12 in. (305 mm) 

Operating environment 
 

Temperature 

 

Relative humidity 

 
32 to 120°F (0 to 49°C) 
0 to 93% noncondensing  

Storage temperature range 

–4 to 140°F (–20 to 60°C) 

Regulatory information 

 

Manufacturer 

Edwards, A Division of UTC Fire & Security 
Americas Corporation, Inc. 
8985 Town Center Parkway, Bradenton, FL 
34202, USA 

Year of 
manufacture 

The first two digits of the DATE MFG number 
(located on the product identification label) are 
the year of manufacture. 

UL/ULC rating 

Regulated 24 DC or 24 FWR 

North American 
standards 

Meets: UL 268, UL 464, CAN/ULC-S525, and 
CAN/ULC-S529 
Follow: CSA C22.1 and CAN/ULC-S524. 

This device is prohibited from being installed in a 
dwelling unit as defined in the 

National Building 

Code of Canada

 

Contact information 

For contact information, see www.edwardsutcfs.com. 

 