Edwards Genesis G4LFWN-HVM Скачать руководство пользователя страница 4

4 / 6 

 

P/N 3102149-

EN • REV 02 • ISS 25MAR14

 

Table 4: Audible directional characteristics (horizontal pattern) 
Angle (°) [1] 

Output (dB) [2] 

85

 

+90 

82 

-90 

82 

[1] Angles are measured from a perpendicular axis; positive angles to 

the right. 

[2] Peak output at 16 VDC, set for steady tone

Table 5: Audible directional characteristics (vertical pattern) 
Angle (°) [1] 

Output (dB) [2] 

85

 

+90 

82 

-90 

82 

[1] Angles are measured from a perpendicular axis; positive angles are 

up. 

[2] Peak output at 16 VDC, set for steady tone.

 

Table 6: Nominal operating horn-strobe current in RMS (mA) 
Voltage 

Strobe output (cd) 

 

15 

30 

75 

110 

Temporal 

16 VDC

 

219 

266 

381 

437 

16 VFWR

 

308 

362 

510

 

579

 

24 

VDC

 

151

 

176 

243 

278 

24 VFWR

 

228 

258

 

349 

395

 

33 

VDC

 

112 

132 

177 

199 

33 VFWR

 

186 

208 

267 

291 

Continuous 

16 VDC

 

221 

258

 

371 

433 

16 VFWR

 

305

 

358

 

514

 

576

 

24 

VDC

 

147 

171 

239 

274 

24 

VFWR

 

211 

247 

335

 

377 

33 

VDC

 

110 

129 

175

 

196 

33 VFWR

 

178 

199 

257

 

287 

VDC = Volts direct current, regulated and filtered

 

VFWR = Volts full wave rectified

 

Figure 5: UL 1971 minimum light output (% of rating vs. angle) 

 

(1

)

  Angle 

(2)

 

Minimum UL required candela light output

 

____ % of rated candela vertical specification  

- - - - 

% of rated candela horizontal specification 

 

Figure 6: Typical horizontal light output profile, 110 cd setting 

 

(1)

  Intensity 

(cd)

 

(2)

  UL minimum requirement 

(cd)

 