Table 4: Audible directional characteristics (horizontal pattern)
Angle (°) [1]
Output (dB) [2]
0
85
+90
82
-90
82
[1] Angles are measured from a perpendicular axis; positive angles to
the right.
[2] Peak output at 16 VDC, set for steady tone
.
Table 5: Audible directional characteristics (vertical pattern)
Angle (°) [1]
Output (dB) [2]
0
85
+90
82
-90
82
[1] Angles are measured from a perpendicular axis; positive angles are
up.
[2] Peak output at 16 VDC, set for steady tone.
Table 6: Nominal operating horn-strobe current in RMS (mA)
Voltage
Strobe output (cd)
15
30
75
110
Temporal
16 VDC
219
266
381
437
16 VFWR
308
362
510
579
24
VDC
151
176
243
278
24 VFWR
228
258
349
395
33
VDC
112
132
177
199
33 VFWR
186
208
267
291
Continuous
16 VDC
221
258
371
433
16 VFWR
305
358
514
576
24
VDC
147
171
239
274
24
VFWR
211
247
335
377
33
VDC
110
129
175
196
33 VFWR
178
199
257
287
VDC = Volts direct current, regulated and filtered
VFWR = Volts full wave rectified
Figure 5: UL 1971 minimum light output (% of rating vs. angle)
(1
)
Angle
(2)
Minimum UL required candela light output
____ % of rated candela vertical specification
- - - -
% of rated candela horizontal specification
Figure 6: Typical horizontal light output profile, 110 cd setting
(1)
Intensity
(cd)
(2)
UL minimum requirement
(cd)