2 / 4 

 

P/N 3100562 • REV 2.0 • ISS 19AUG10 

2.  Set the chime signal, sound output level, and desired 

operation settings. See Figure 1. 

• 

To change the chime signal from steady to temporal, 
cut from circle J1 to the edge of the circuit board. 

• 

To change the chime operation from noncoded to 
coded (single-stroke), cut from circle J2 to the edge of 
the circuit board. 

• 

To change the chime sound output level from high dB 
to low dB, cut the J3 trace between the holes. 

3.  Slide the candela switch to the desired candela output by 

aligning it with the indicator located beside the switch. See 
Figure 2. 

4.  Connect the chime terminals to the signal circuit field 

wiring. For the unit to function properly, observe polarity. 
See Figure 1. 

• 

For single-stroke coded voltage operation, see 
Figure 3. 

• 

For constant noncoded voltage operation, see 
Figure 4. 

5.  Mount the unit onto a compatible electrical box, making 

sure not to overtighten the mounting screws. 

6.  Replace the cover by aligning it at the bottom, then 

snapping it in at the top. 

7.  Test the unit for proper operation. 

Figure 1: Chime settings 

J2 J3

J1

2

3

1

 

1. 

J1: Chime signal jumper 

2. 

J2: Coded/non-coded jumper 

3. 

J3: Chime sound output 

Figure 2: Candela switch 

110

75
30
15

 

Wiring 

Figure 3: Wiring for single-stroke coded voltage operation 

-

-

+

STROBE -

2

CHIME +

CHIME -

H

S

4

3

1

5

+

+

-

6

 

1. 

Chime in (coded power signal) 

2. 

Strobe in (continuous power signal) 

3. 

Resistor, value determined by the control panel 

4. 

Genesis Signal Master 

5. 

To next appliance, EOL resistor, or Class A circuit return 

6. 

One wire each side of screw head 

Notes 
• 

Polarity shown in alarm condition 

• 

The strobe circuit can be silenced without turning off strobes 

 

Figure 4: Wiring for constant noncoded voltage operation 

-

+

-

+

1

2

+

-

+

-

 

1. 

From NAC output 

2. 

To next appliance, EOL, or Class A return

 

Note: Signal polarity is shown in the alarm condition. 
 

Maintenance 

This unit is not serviceable or repairable. Should the unit fail to 
operate, contact the supplier for replacement. 

Perform a visual inspection and an operational test twice a 
year or as directed by the local authority having jurisdiction. 

Do no change the factory-applied finish. 