D100-101-00  2 I56-1580-000

the control unit.

4.  Test the detector using the magnet as described under 

TESTING.

5.  Reset the detector at the system control panel.

6.  Notify the proper authorities that the system is back on line.

CAUTION

Dust covers are an effective way to limit the entry of dust 

into smoke detector sensing chambers. However, they 

may not completely prevent airborne dust particles from 

entering the detector. Therefore, Edwards recommends 

the removal of detectors before beginning construction or 

other dust producing activity.

Be sure to remove the dust covers from any sensors that 

were left in place during construction as part of returning 

the system to service.

CAUTION

Smoke detectors are not to be used with detector guards 

unless the combination has been evaluated and found  

suitable for that purpose.

Testing

Before testing, notify the proper authorities that the smoke 

detector system is undergoing maintenance and will tem-

porarily be out of service. Disable the zone or system 

undergoing maintenance to prevent unwanted alarms. De-

tectors must be tested after installation and as part of peri-

odic maintenance. Test EDW2151A as follows:

NOTE:

 Before testing the detector, check to ensure the 

LEDs blink.  If they do not,  the detector has lost power  

(check the wiring) or it is defective (return it for repair).

LED Status

Indicators

Magnet Test

Marker

Test Magnet 

Position

Test Magnet 

Position

Magnet Test

Marker

CSENS-RDRA

Location

Figure 1. Bottom and side views showing position of test magnet:

A.  Test Magnet (p/n M02-04-01 or M02-09-00)

  1. Place the magnet against the cover in the location 

designated by the raised mark to activate the test fea-

ture (see Figure 1).

  2. The LEDs should latch ON within 5 seconds indicat-

ing alarm and annunciating the panel.

B.  Test Module (CSENS-RDRA)

  Use the CSENS-RDRA Sensitivity reader to measure 

the sensitivity of the detectors. Please refer to the 

CSENS-RDRA instruction manual for operating details.

B.  Aerosol Generator (Gemini 501)

  Set the generator to represent 4% to 5%/ft. obscura-

tion as described in the Gemini 501 Manual. Using the 

bowl- shaped applicator, apply aerosol until unit alarms.

Notify the proper authorities that the system is back on line.

Detectors that fail these tests should be cleaned as de-

scribed under MAINTENANCE and retested. If the detec-

tors still fail these tests, they should be returned for repair.

Cleaning

Before removing the detector, notify the proper authorities 

that the smoke detector system is undergoing maintenance 

and will be temporarily out of service. Disable the zone or 

system undergoing maintenance to prevent unwanted 

alarms.