D100-101-00  1 I56-1580-000

EDW2151A Low Profile

Photoelectronic Plug-in 

Smoke Detector

INSTALLATION AND MAINTENANCE INSTRUCTIONS

Before Installing 

Please thoroughly read the manual A05-1003, 

Applica-

tions Guide for System Smoke Detectors

, which provides 

detailed information on detector spacing, placement, zon-

ing, wiring, and special applications. Copies of this manual 

are available from Edwards. 

NOTICE:

 This manual should be left with the owner/user 

of this equipment.

IMPORTANT: 

The detector must be tested and maintained 

regularly following CAN/ULC S536 requirements. The de-

tector should be cleaned at least once a year.

General Description

The EDW2151A low-profile photoelectronic detector uses 

a state-of-the-art optical sensing chamber. This detector is 

designed to provide open area protection and to be used 

with compatible ULC listed control panels only. The ca-

pability of plugging this detector into a variety of special 

bases makes it more versatile than equivalent direct-wired 

models.
Two LEDs on each detector provide local 360° visible 

alarm indication. They flash every five seconds indicating 

that power is applied and the detector is working properly. 

The LEDs latch on in alarm. Remote LED annunciator ca-

pability is standard and may be implemented through an 

optional accessory RA100ZA. The alarm can be reset only 

by a momentary power interruption. This detector may be 

tested by activating the internal reed switch with a magnet, 

or by using the CSENS-RDRA infrared sensitivity reader.

Base Selection And Wiring Guide

Refer to the installation instructions for the Plug-in Detector 

Bases for base selection and wiring instructions. Edwards 

has a variety of detector bases available for this smoke 

detector, including 2-wire applications with and without re-

lays and/or current limiting resistors, 4-wire and 120VAC 

Specifications

Size 

Height: 

2.0 inches (51 mm) installed in B401A Base

Diameter: 

4.1 inches (104 mm) installed in B401A Base

 

6.1 inches (155 mm) installed in B110LPA Base

Weight: 

3.1 oz. (88 g)

Operating Temperature Range: 

0°C to 49°C (32°F to 120°F)

Operating Humidity Range: 

10% to 93% Relative Humidity noncondensing

Operating Voltage                                              8.5 to 35VDC

Standby Current                                                  120 uA

Latching Alarm: 

Reset by momentary power interruption.

applications.

All bases are provided with screw terminals for power, 

ground, remote annunciator connections and relay contact 

connections, if applicable. The electrical ratings for each 

detector-base combination are also included in the base 

installation instructions.

Installation

Installation shall comply with the latest version of CAN/

ULC S524, Installation of Fire Alarm Systems.

NOTE:

  All wiring must conform to applicable local codes, 

ordinances, and regulations.

NOTE:

 Verify that all detector bases are installed, that 

the initiating-device circuits have been tested, and that 

the wiring is correct. (Refer to detector base manual for 

testing procedure.)

WARNING

Remove power from initiating-device circuits before install-

ing detectors.

1.  Install detectors:

  a. Place the detector into the detector base.

  b. Turn the detector clockwise until the detector drops  

  into place.

  c. Continue turning detector clockwise to lock it in place.

2.  Tamper Resistance: The detector bases can be made 

tamper resistant. When capability is enabled, detectors 

cannot be removed from the base without the use of a 

tool. See the detector base installation manual of the 

detector base for details in using this capability.

3.  After all detectors have been installed, apply power to 

625 6th Street East, Owen Sound, Ontario N4K-5P8

TEL:519-376-2430, FAX: 519-376-1296