![Edwards E1M40 Скачать руководство пользователя страница 54](http://html1.mh-extra.com/html/edwards/e1m40/e1m40_instruction-manual_2366103054.webp)
A344-02-880 Issue J
Page 48
© Edwards Limited 2007. All rights reserved.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Appendix
A
A2.3
Electrical data: three-phase motors
The pumps are available with the three-phase motor specified in
. The dual voltage motors can be manually
set-up to work with the nominal supplies of 220-240 V, 380-415 V, or 208-230 V (Refer to
). Dual voltage
motors are supplied preset to the highest of the selectable voltages.
Table A1 - Electrical data (three-phase motors)
Pump
Nominal
supply (V)
Frequency
(Hz)
Power (kW)
Full load
current (A)
Start-up
current (A)
Recom-
mended fuse
rating (A)*
Electrical
connection
Figure
E2M40S
208
50
1.5
6.8
41
25
5
208-230
60
1.5
6.5
39
25
5
460
60
1.5
3.1
18.6
15
6
E2M80S
208
50
3
12.4
71
40
5
208-230
60
3
11.8
71
40
5
460
60
3
5.6
34
20
6
*
You may need to use a different fuse rating. Use the information supplied with your circuit breaker or
starter to select the correct fuse rating.