After considering these factors, choose a location: 

o

 

Where the temperature and humidity are within the product 

temperature range. 

o

 

Away from ventilation sources that can prevent smoke from 
reaching the smoke alarm. 

o

 

‘Smoke alarms and smoke detectors shall not be installed 

within a 36 in. (910 mm)  horizontal path from a door to a 
bathroom containing a shower or tub unless listed for 
installation in close proximity to such locations.’ 

 

The product shall be located on the ceiling or, if on a sidewall, between 
the ceiling and 12 in. (300 mm) down from the ceiling to the top of the 
detector. 
 

In rooms with sloped, or peaked ceilings, place smoke alarms 3 feet 
(910 mm) down or away from the highest point of the ceiling. 
 
If mounting to suspended ceiling tile, secure the tile with the 

appropriate fastener to prevent tile removal. 
 
Smoke Alarms are not to be used with alarm guards unless the 
combination has been evaluated and found suitable for that purpose. 

 
Note: A smoke alarm does not provide warnings for fires resulting from 
explosions, smoking in bed, or other furniture; ignition of flammable 
liquids, vapors,  and gasses; and children playing with matches or 

lighters. 
 

Locations to Avoid 

o

 

Areas where normal ambient temperature exceeds products 
operating temperature range. 

o

 

Dirty, dusty, insect infested areas. 

o

 

In or near areas with combustion particles (kitchens, garages, 

furnaces, hot-water heaters, gas space heaters). 

o

 

On the ceiling in rooms next to kitchens, where there is no 
transom between the kitchen and such rooms. 

o

 

Damp or humid areas, or near bathrooms with showers.  

o

 

Near fresh-air inlets or returns or very drafty areas. 

o

 

Near heating/air conditioning vents, fans, and fresh air intakes, 
which can drive smoke away from the smoke alarm. 

o

 

In dead-air spaces at the top of peaked ceilings or in corners 
where  walls and ceiling meet. Dead air can prevent smoke 
from reaching a smoke alarm/alarm. 

o

 

Within 10 feet (3 m) of fluorescent light fixtures. 

o

 

Not suitable for outdoor use. 

 

 WARNING! LIMITATIONS OF SMOKE ALARMS 

Wireless smoke alarms are very reliable, but may not work under all 
conditions. No fire alarm provides total protection of life or property.  
 

Smoke Alarms require a source of power to work. 

This smoke alarm will not operate and the alarm will not sound if 
batteries are dead or not installed properly. 
 

Smoke Alarms may not be heard.

 A sound sleeper or someone who 

has taken drugs or alcohol may not awaken if the alarm is installed 
outside a bedroom. Closed or partially closed doors and distance can 
block sound. This alarm is not designed for the hearing impaired. 

 

Smoke Alarms may not always activate and provide warning early 
enough.

 Smoke alarms only activate when enough smoke reaches the 

alarm. If a fire starts in a chimney, wall, roof, on the other side of closed 
doors, or on a different level of the property, enough smoke may not 
reach the alarm for it to alarm. 

 
Smoke Alarms are a significant help in reducing loss, injury and even 
death. However, no matter how good a detection device is, nothing 
works perfectly under every circumstance and we must warn you that 

you cannot expect a smoke alarm to ensure that you will never suffer 
any damage or injury. 
 
Current studies have shown smoke alarms may not awaken all 

sleeping  individuals. It is the responsibility of individuals in the 
household that are capable of assisting others to provide assistance to 
those who may not be awakened by the alarm sound, or to those who 
may be incapable of safely evacuating the area unassisted. 

 

  WARNING 

The  product  should be installed in a location that 

must maintain a minimum distance of 7.87 inches (20 cm) between the 

product and a person. 
 
 

3.

 

Mounting 

the Sensor

 

Note: Add the product to the Control Panel before physically mounting 
the smoke alarm in the desired location. 

 
A.

 

Disconnect alarm-notification appliances, service-release devices, 
and extinguishing systems. Test communications between the 
control panel and smoke alarm before permanently mounting the 

smoke alarm as follows: 

 

Hold the smoke alarm where you plan to install it. 

 

Press the smoke alarm test button for 8-to-10 seconds. The 

smoke alarm sends a signal to the control panel. 

 

At the control panel, verify the signal was received and RF 

signal strength is adequate. If no signal is received or the RF 
signal is low, relocate the smoke alarm and retest. 

 
B.

 

Using two supplied screws and anchors, mount the base with this 
arrow pointing towards the wireless Control Panel. 

 

 

 
 
C.

 

Attach the smoke alarm to the mounting base as follows: 

 

Line up the raised alignment tab on the lip of the smoke 

alarm with the arrow on the mounting base. 

 

Insert the smoke alarm into the base and turn clockwise 

about 15 degrees until it snaps into place. 

 
Note:  The  product  cannot be attached to the mounting base if no 
batteries are installed. 

 