Technical Bulletin 

 

 

SuperDuct Signature Duct Smoke Detector 

 

 

 
SuperDuct Signature Duct Smoke 
Detector 

P/N 3100738 • Rev 02 • 18JAN17

 

 

Content 

Introduction ............................................................................ 1

 

Related documents .................................................................. 1

 

Duct smoke detector limitations ............................................... 1

 

Product description ............................................................... 1

 

Overview .................................................................................. 1

 

Description ............................................................................... 2

 

Features ................................................................................... 2

 

Specifications ........................................................................... 3

 

Accessories .............................................................................. 3

 

Operation ................................................................................ 4

 

Controls and indicators ............................................................. 4

 

Normal state ............................................................................. 4

 

Alarm state ............................................................................... 4

 

Trouble state ............................................................................ 4

 

Installation .............................................................................. 4

 

Installation guidelines ............................................................... 4

 

Installation sequence................................................................ 5

 

Installing the sampling tube from the front of the detector ........ 5

 

Supporting sampling tubes greater than 36 inches long .......... 5

 

Wiring ....................................................................................... 6

 

Configuration ............................................................................ 6

 

Maintenance and service ....................................................... 6

 

Recommended service schedule ............................................. 6

 

Testing the duct smoke detector .............................................. 6

 

Troubleshooting ....................................................................... 6

 

Cleaning the duct smoke detector ............................................ 6

 

 

Introduction 

This document provides technical information for the 
SuperDuct Signature Duct Smoke Detector (referred to simply 
as duct smoke detector for the remainder of this document.) 

This document applies to the following duct smoke detector 
model: SIGA-SD. 

Related documents 

In addition to this document, important information regarding 
the proper installation and maintenance of duct smoke 
detectors is provided in the following standards: 

• NFPA 

70 

National Electrical Code

 

• NFPA 

72 

National Fire Alarm Code

 

• NFPA 

90A 

Installation of Air Conditioning and 

Ventilating Systems

 

• UL 

268A 

Smoke Detectors for Duct Applications

 

• ULC 

529 

Smoke Detectors for Fire Alarm Systems

 

• NEMA

 Guide for Proper Use of Smoke Detectors in Duct 

Applications

 

Duct smoke detector limitations 

SuperDuct duct smoke detectors will not operate without 
electrical power. 

SuperDuct duct smoke detectors will not operate as designed 
outside of the listed electrical and environmental 
specifications. 

SuperDuct duct smoke detectors will not sense smoke unless 
the ventilation system is operating and the sensor’s cover is 
properly installed. 

SuperDuct duct smoke detectors may not operate as designed 
unless installed in accordance with these instructions and all 
applicable national and local codes as determined by the local 
authority having jurisdiction. 

Product description 

Overview 

The duct smoke detector is used to detect smoke under 
extended temperature ranges, typically in self-contained 
commercial rooftop HVAC systems. In self-contained 
commercial HVAC units, the HVAC equipment is enclosed in 
a single package to protect the internal components 
(compressor, condensing unit, heating coils, etc.) from adverse 
environmental conditions. Hinged or removable service panels 
provide access to the equipment. 

Содержание 3100738

Страница 1: ...e following standards NFPA 70 National Electrical Code NFPA 72 National Fire Alarm Code NFPA 90A Installation of Air Conditioning and Ventilating Systems UL 268A Smoke Detectors for Duct Applications...

Страница 2: ...es are stored in nonvolatile memory This information can be retrieved and reviewed when desired Air is introduced to the duct smoke detector s sensing chamber through a sampling tube that extends into...

Страница 3: ...rm red Power green Common alarm relay Unsupervised and power limited Quantity 1 Type Form C Ratings 2 0 A at 30 Vdc resistive Operating voltage 15 2 to 19 95 Vdc Operating current Standby 45 A Alarm 4...

Страница 4: ...ed when the amount of smoke in its sensing chamber exceeds its alarm threshold setting or when an alarm test is initiated Upon entering the alarm state the duct smoke detector s Alarm LED turns on Com...

Страница 5: ...velocity 2 Drill the mounting holes 3 Assemble the detector 4 Mount the detector on the HVAC duct 5 Verify the detector pressure differential Installing the sampling tube from the front of the detecto...

Страница 6: ...ion for more than 5 seconds Using an SD TRM hold the SD MAG test magnet to the target area for more than 5 seconds Once activated verify the following The detector s Alarm LED is flashing If connected...

Страница 7: ...oft bristle brush remove loose dirt and debris from inside the detector housing and cover Use isopropyl alcohol and a lint free cloth to remove dirt and other contaminants from the gasket on the detec...

Страница 8: ...uct Signature Duct Smoke Detector 8 70 in 22 1 cm 7 75 in 19 7 cm 8 15 in 20 7 cm 2 28 in 5 78 cm 5 45 in 13 84 cm 5 40 in 13 72 cm 1 38 in 3 51 cm 1 90 in 4 83 cm 3 08 in 7 82 cm 1 60 in 4 06 cm Figu...

Страница 9: ...Active SIGA LED 1 Notes 1 No more than one remote test station or LED indicator can be connected to the detector at the same time Wiring is unsupervised Maximum wire resistance is 10 ohms per wire Pow...

Отзывы: