Edwards 3-REMICA Скачать руководство пользователя страница 2

P/N: 387466 REV: 3.0 

05SEP07 

Installation Sheet 

2 / 2 

 

3-REMICA - Remote Microphone 

Wiring diagrams 

A

A

B

B

JP2

JP1

JP2

JP1

A

B

A

B

Place jumper to position B when
audio output is connected to the
Remote Microphone input. 

Place jumper to position B when

audio output is connected to the
Remote Microphone input. 

Place jumper to position A when
audio output is connected to an
Audio Source Unit  input. 

Place jumper to position A when
audio output is connected to an
Audio Source Unit  input. 

AUDIO IN

KEY IN

From Remote Microphone 
[2] [3]

From Remote Microphone [2] [3]

NC
C
NO

To trouble relay
interface circuit

From primary

24VDC riser

From secondary

24VDC riser

AUDIO IN

KEY IN

AUDIO OUT

KEY OUT

To Audio Source Unit or 

next Remote Microphone 

Unit [1] [3]

TB1

1

2

3

4

5

6

7

8

9 10 11 12 13 14 15 16 17 18 19 20

Notes

[1]

Power-limited and supervised.

[2]

Terminate the KEY IN input with a 1.8 k  EOL resistor when it is not used.

[3]

Wiring must be enclosed in conduit.

From annunciator controller

To next annunciator strip

 

Figure 1: Field wiring for the 3-REMICA 

Signature Single Input Module

(Personality Code 3)

DATA OUT (+)

DATA IN (+)

DATA IN (-)

DATA OUT (-)

TO

NEXT

DEVICE

FROM

PREVIOUS

DEVICE

TB1-20

TB1-19

3-REMICA

Support standoffs for
mounting Signature module

 

Figure 2: Trouble relay interface circuit wiring 

Отзывы: