3-REMICA
Remote Microphone
Product description
FRONT
SIDE
The 3-REMICA provides remote paging capability at stations
located throughout a building or campus. The 3-REMICA can
be connected to other remote microphone units to provide up
to 63 stations on the paging circuit.
The 3-REMICA occupies 2 slot positions in a 2-space, 6-space
or 10-space remote annunciator cabinet. When installed in a
cabinet with an annunciator controller, the 3-REMICA must
occupy the slot positions next to the controller.
The 3-REMICA housing assembly provides standoffs for
mounting a Signature single input module when the system
application requires electrical supervision. The 3-REMICA
trouble relay contacts change state whenever an electrical
short or open is detected on either the microphone or audio
inputs, or whenever power is interrupted to the unit.
Specifications
Power requirements
Voltage: 21 to 27 VDC
Current: 52 mA
Space requirements: 2 spaces in annunciator enclosure
Audio Output: 1 VRMS @ 400 Hz to 4 kHz
Trouble relay contacts
Current: 1 A @ 30 VDC resistive
UL rating: Common
Wiring
Termination: All wiring connects to terminal block
Size: 14 AWG (1.5 sq. mm) max.
Resistance: 210
Ω
max.
Capacitance: 1 µF
Operating environment
Temperature: 32 to 120°F (0 to 49°C)
Humidity: 93% noncondensing
Jumper settings
Jumper JP1 and JP2:
Position A: Selects AC supervision when connecting the audio
output to 3-ASU.
Position B: Selects DC supervision when connecting the audio
output to 3-REMICA.
Installation instructions
Warnings
•
This product contains components that are sensitive to
static electricity. Failure to follow proper handling
procedures to prevent damage from electrostatic
discharge may result in equipment failure.
•
Ensure the 24VDC riser is deenergized before making
cable connections.
To install the 3-REMICA:
1. Remove the top module retainer bracket on the inner door
of the remote annunciator enclosure.
2. Loosen the bottom module retainer bracket.
3. Insert the bottom of the 3-REMICA into the bottom module
retainer bracket next to the annunciator panel controller.
4. Tilt the 3-REMICA forward until the top touches the inner
door.
5. Tighten the bottom module retainer bracket.
6. Secure the top module retainer bracket to the inner door.
7. Connect the cable assembly from P3 on the annunciator
panel controller to P4 on the 3-REMICA.