Jumper settings 

For circuits configured as NACs, the NAC pairs share a 

common power/signal source. Two jumpers on the module 

select the signal source for each NAC pair. See Figure 2 for 

jumper pin numbers. 

Notes  

 

Jumper positions must be set in parallel. Set jumpers in 

both JP1 and JP2 the same. Set jumpers in both JP3 and 

JP4 the same.

 

 

Jumpers have no effect when 

the IDC/NAC circuits are 

configured as IDC circuits. 

Table 1: Jumper settings for circuit power/signal source 
Circuits 

External [1] 

Internal 24 VDC [2] 

IDC/NAC1 and 2 

JP1 to 1 and 2

 

JP2 to 1 and 2

 

JP1 to 2 and 3

 

JP2 to 2 and 3

 

IDC/NAC5 and 6 

JP3 to 2 and 3

 

JP4 to 2 and 3

 

JP3 to 1 and 2

 

JP4 to 1 and 2

 

[1] Supplied via NAC IN terminals. 

[2] See total current limit in “Specifications” on page 3. 

 

Wiring 

Connect field wiring as shown in Figure 2. 

 

Wiring is supervised and power-limited. 

 

Maintain 0.25 in. (6 mm) separation between power-

limited and nonpower-

limited wiring at all times. Route the 

power-limited wiring through the notches at the right front 

of the chassis. Secure the wiring to the cabinet using 

nylon cable ties. 

 

If shielded cable is used, it must be continuous, free from 

earth ground, and must only be connected to the ground 

terminal on the source of the riser. 

 

Dedicated initiating device circuits (Class B, Style B): 

IDC3, IDC4, IDC7, IDC8. 

 

Circuits configurable as IDC or NAC (Class B, Style Y): 

IDC/NAC1, IDC/NAC2, IDC/NAC5, IDC/NAC6. 

 

Synchronized operation of Genesis strobes requires a 

separately installed synchronization device. See the 

control panel or power supply compatibility list for 

compatible synchronization devices. 

 

For a list of 3-IDC8/4 compatible devices, see the

 EST3 

Compatibility List

 (P/N 3100427-EN) and 

EST3X 

Compatibility List

 (P/N 3101801-EN). 

Figure 2: Wiring the 3-IDC8/4 

 

Legend

 

(1)  IDC/NAC1 configured as an IDC circuit 

(use a UL/ULC Listed 

 

4.7 

kΩ EOLR)

 

(2) 

Jumper JP

and JP

2 (NAC1 and 2) 

(3) 

Jumper JP3 and JP4

 (NAC5 and 6) 

(4)  From external source 

(5)  IDC/NAC5 configured as an NAC circuit 

(use a UL/ULC Listed 

 

15 

kΩ EOLR)

 

Note: Signal polarity is shown in supervisory mode. For an NAC, the 

polarity reverses when the circuit is active. 

J1

IDC/NAC

1

IDC/NAC

2

IDC

3

IDC

4

NAC IN

1/2

IDC/NAC

5

IDC/NAC

6

IDC

7

IDC

8

NAC IN

5/6

TX

RX

15 k

EOLR

Ω

4.7 k

Ω

EOLR

+

+

(1)

(5)

(4)

(2)

(3)

JP4

JP2

JP3

JP1

TB

2

TB

1

1

1

1

1

2

2

2

2

3

3

3

3

Отзывы: