3-ASU and 3-ASU/4 Audio Source Unit
Installation Sheet
Description
The 3-ASU and 3-ASU/4 provide controls for emergency
paging. The 3-ASU/4 also provides a four-slot rail for installing
local rail modules.
Both units can store
and play back prerecorded messages and
have inputs for connecting remote microphones and MN-
FVPN
VoIP Encoder/Decoder modules.
The 3-ASU and 3-ASU/4 require one chassis space in an
enclosure. The 3-ASU includes a filler plate that mounts on the
cabinet inner door to prevent access to the electronics.
Installation
WARNING:
Remove all sources of power from the cabinet
before installing or removing components. Failure to do so may
result in serious injury or loss of life.
1. Attach the cha
ssis to the backbox using the hardware
provided. Align the backbox mounting studs with the holes
indicated in Figure 1.
2. Attach the ASU to the chassis using six 6/32 x 3/8 pan
head screws. Press the RCIC card onto the PEM studs.
See Figure 2.
3. Connect the ribbon cable (P/N 250195-
01) between the
ASU card and the RCIC card.
4. If used, install the 3-ASUMX memory card. Make sure the
write protect switch is in the “off” or “write enabled”
position.
5.
Connect the RCIC card to the other chassis rail
assemblies. See Figure 6 or Figure 7.
6. Plug the ribbon cable (P/N 250194-00) from the 3-ASU
cover assembly into J3 on the ASU card. See
Figure 3.
7. Lift the 3-ASU cover assembly onto the chassis mounting
studs then attach it
with the locknuts provided in the
hardware kit. See
Figure 4.
Figure 1: Chassis mounting diagram
Note:
3-
ASU/4 chassis shown.
Figure 2: Circuit board mounting diagram