P/N 3101032-EN • REV 03 • ISS 02DEC15
1 / 2
FSRZI-A(-SA) Remote Zone
Indicators Installation Sheet
Description
The FSRZI-A and FSRZI-SA are remote zone indicators for F-Series
fire alarm control panels. The FSRZI-A provides five red LEDs for
indicating alarm zones. The FSRZI-SA provides five bi-color LEDs (red
for alarm zones; yellow for supervisory and monitor zones).
Configuration jumpers determine which zones are indicated.
FSRZI-A and FSRZI-SA remote zone indicators include a cover plate
for installation in a standard, single-gang electrical box. You can install
one or two FSRZI-A and FSRZI-SA remote zone indicators (with or
without an FSRSI remote system indicator) in an approved 2-, 3-, or 4-
gang electrical box. Cover plates for 2-, 3-, and 4-gang electrical boxes
(model numbers FSAT2, FSAT3, and FSAT4) are ordered separately.
A paper insert is provided for creating custom LED labels.
FSRZI-A and FSRZI-SA remote zone indicators are configured using
the jumpers described in the tables below.
Table 1: Group selection jumper
J5
Description
ON
Selects peripheral group 1
OFF
Selects peripheral group 2
Note:
Only two remote zone indicators are allowed per peripheral
group.
Table 2: Zone selection jumpers
J4
J3
J2
Description
ON
OFF
OFF
LEDs used to indicate zones 1 to 5
(IDC 1 to IDC 5 on the control panel)
OFF
ON
OFF
LEDs used to indicate zones 6 to 10
(IDC 6 to IDC 10 on the control panel)
OFF
OFF
ON
Not used
Note:
Install a jumper on J3 only when connected to a 10-zone control
panel.
Installation
Caution:
Make sure all power is disconnected from the panel before
installing. Observe static-sensitive handling practices.
For more information, refer to the technical reference manual listed
inside the control panel door.
To install the remote zone indicator:
1. Configure the jumpers as described in Table 1 and
Table 2.
2. Verify that all field wiring is free of opens, shorts, and ground
faults.
3. Wire the remote zone indicator as shown Figure 1.
4. Mount the remote zone indicator in the electrical box using the two
plain machine screws. See Figure 2.
Note:
If you are surface mounting the remote zone indicator, you
must install washers (provided) between it and the surface mount
box.
5. Attach the faceplate to the remote zone indicator. Use the two
white machine screws provided with the faceplate.
Note:
Remote zone indicators will not operate properly until detected
by the control panel. For more information, see the technical reference
manual listed inside the control panel door.
Figure 1: Wiring diagram
1. All wiring is supervised and power-limited.
[2] AUX power supplied by the control panel can’t exceed 0.5 A. If
more than 0.5 A is required, you must use a power-limited and
regulated 24 VDC auxiliary/booster power supply that is UL/ULC
Listed for fire protective signaling systems.
[3] If powered from an external supply, the supply must be installed in
the same room as the control panel and their 24 VDC commons
(−) wired together.
J5
J4
J3
J2
Regulated 24 VDC
from control panel or
external power supply
[2] [3]
From
control panel
+
−
C
+
C
−
To
next remote
module
+
−
C
+
C
−