P/N 3101032-EN • REV 03 • ISS 02DEC15 

 

1 / 2 

 

FSRZI-A(-SA) Remote Zone 
Indicators Installation Sheet 

 

Description 

The FSRZI-A and FSRZI-SA are remote zone indicators for F-Series 
fire alarm control panels. The FSRZI-A provides five red LEDs for 
indicating alarm zones. The FSRZI-SA provides five bi-color LEDs (red 
for alarm zones; yellow for supervisory and monitor zones). 
Configuration jumpers determine which zones are indicated. 

FSRZI-A and FSRZI-SA remote zone indicators include a cover plate 
for installation in a standard, single-gang electrical box. You can install 
one or two FSRZI-A and FSRZI-SA remote zone indicators (with or 
without an FSRSI remote system indicator) in an approved 2-, 3-, or 4-
gang electrical box. Cover plates for 2-, 3-, and 4-gang electrical boxes 
(model numbers FSAT2, FSAT3, and FSAT4) are ordered separately. 

A paper insert is provided for creating custom LED labels. 

FSRZI-A and FSRZI-SA remote zone indicators are configured using 
the jumpers described in the tables below.  

Table 1: Group selection jumper 

J5 

Description 

ON 

Selects peripheral group 1 

OFF 

Selects peripheral group 2 

Note: 

Only two remote zone indicators are allowed per peripheral 

group. 
 

Table 2: Zone selection jumpers 

J4 

J3 

J2 

Description 

ON 

OFF 

OFF 

LEDs used to indicate zones 1 to 5 
(IDC 1 to IDC 5 on the control panel) 

OFF 

ON 

OFF 

LEDs used to indicate zones 6 to 10 
(IDC 6 to IDC 10 on the control panel) 

OFF 

OFF 

ON 

Not used 

Note: 

Install a jumper on J3 only when connected to a 10-zone control 

panel. 

Installation  

Caution: 

Make sure all power is disconnected from the panel before 

installing. Observe static-sensitive handling practices. 

For more information, refer to the technical reference manual listed 
inside the control panel door. 

To install the remote zone indicator: 

1.  Configure the jumpers as described in Table 1 and  

Table 2. 

2.  Verify that all field wiring is free of opens, shorts, and ground 

faults. 

3.  Wire the remote zone indicator as shown Figure 1. 

4.  Mount the remote zone indicator in the electrical box using the two 

plain machine screws. See Figure 2. 

Note: 

If you are surface mounting the remote zone indicator, you 

must install washers (provided) between it and the surface mount 
box. 

5.  Attach the faceplate to the remote zone indicator. Use the two 

white machine screws provided with the faceplate. 

Note: 

Remote zone indicators will not operate properly until detected 

by the control panel. For more information, see the technical reference 
manual listed inside the control panel door. 

Figure 1: Wiring diagram 

 

 
1.  All wiring is supervised and power-limited. 
[2]  AUX power supplied by the control panel can’t exceed 0.5 A. If 

more than 0.5 A is required, you must use a power-limited and 
regulated 24 VDC auxiliary/booster power supply that is UL/ULC 
Listed for fire protective signaling systems. 

[3]  If powered from an external supply, the supply must be installed in 

the same room as the control panel and their 24 VDC commons 

(−) wired together. 

J5

J4

J3

J2

Regulated 24 VDC 
from control panel or
external power supply 
[2] [3]

From

control panel

+

C

+

C

To

next remote

module

+

C

+

C

firealarmresources.com