2 / 3
P/N 3101962-EN • REV 003 • ISS 26OCT17
Table 1: Flash and rotation patterns
Pattern
Description
1. Steady
On steady
2. S65
65 Single FPM
3. Light Burst
1,100 FPM (seven pulses),
440 ms off,
Repeat
4. Singular Burst
310 Single FPM
5. Binary Burst
200 Double FPM
6. Quad Burst
100 Quad FPM
7. iBurst
4 pulses at 750 FPM, Off,
4 pulses at 750 FPM, Off,
6 pulses at 870 FPM, Off,
Repeat
8. Rotating 80 RPM
80 RPM
9. Rotating 95 RPM
95 RPM
10. Rotating 130 RPM
130 RPM
11. Rotating 200 RPM
200 RPM
12. Slow Rotating with Burst
2 rotations at 84 RPM,
2 pulses at 940 FPM,
Repeat
13. Flash Rotating with Burst
3 rotations at 174 RPM,
4 pulses at 900 FPM,
Repeat
14. Quad Flash with Pop
4 pulses at 650 FPM, 160ms Off,
1 pulse at 410 FPM, 410 ms Off,
Repeat
15. Variable Rotating
83 to 420 RPM repeated every 6.6s
16. Variable Flashing
137 - 535 Single FPM repeated
every 4.1s
FPM – Flashes Per Minute
RPM – Rotations Per Minute
To select a flash or rotation pattern:
1. Press and hold the push button for one second to switch the
beacon to the next pattern (Table 1).
2. Press and hold the push button for three seconds to set the
beacon to the first pattern (Steady).
Maintenance
Lens and dome replacement
WARNING:
Electrocution hazard. To prevent electrical shock,
disconnect the beacon from the supply circuit and allow five minutes
for stored energy to dissipate before disassembling.
Caution:
Do not overtighten the screws or damage to the dome may
occur.
To replace the lens or dome:
1. Release the latch on the clamp ring and remove the ring holding
the protective dome to the signal base. Lift the dome straight up off
of the signal base.
2. Loosen the three screws in the keyhole slots in the base of the
lens. Turn the lens clockwise and lift it straight up off of the support
plate.
3. Replace the lens by turning it counter-clockwise in the keyhole
slots, and then tightening the three screws.
4. Replace the dome and reinstall the clamp ring.
Cleaning
Caution
:
To prevent damage to the lens or dome, do not use abrasive
materials or cleaners.
Periodically clean the lens surface with a soft cloth or sponge and
water or a mild detergent solution to maintain optimum light visibility.
Make sure the lens is completely dry before assembling the beacon.
Figure 1: Installation
(1) Dome
(2) Lens
(3) Screw (3X)
(4) LED tower
(5) Screw (3X)
(6) LED light source support plate
(7) Beacon base
(8) Clamp ring
(9) Push button