background image

1 5W 25V

*

.9W 70V

1.8W 7 0V

0.48W 2 5V

7.5W 70V

15W 7 0V

7. 5W 25V

*

1 .8W 25V

0.94 W 25V

3.8W 70 V

* DO NOT US E

FOR 70V

+

AUDIO IN PUT CONNECTION S

From Supervised
or Non Supervised
Amplifer

+

_

1/2" Conduit Entries

Power Tap
Selection Switch
(See table 1)

Note: To conform with UL requirements, wires must be connected as shown in wiring diagram.

To Next Speaker or
End-of-Line Resistor

Wire size; 18 Gauge minimum, 12 Gauge maximum.

+

_

Figure 4.  Wiring Multiple 5553 Seres Speakers and/or supervised circuits

To ensure proper supervision of connection, do not use looped 

wires under terminal screws.  Break wire run.  Use both sides 

of terminal screws as shown.

U.S.
T 800-336-4206
F 800-454-2363

Canada
T 519 376 2430
F 519 376 7258

Asia
T 852 2907 8108
F 852 2142 5063

Australia
T 61 3 9259 4700
F 61 3 9259 4799

Europe
T 32 2 725 11 20
F 32 2 721 86 13

Latin America
T 305 593 4301
F 305 593 4300

www.edwardssignaling.com

CAUTION

 

Switch

Position

Impedance

25V

Line

SPL dB(A) 

@ 10 ft.

70V

Line

SPL dB(A)

@ 10 ft.

1

5.0K

-

-

.9W

93

2

2.5K

-

-

1.8W

96

3

1.3K

.48W

91

3.8W

98

4

666

.94W

93

7.5W

101

5

333

1.8W

96

15.0W

103

6

89

7.5W

101

Do Not Use

on 70V

7

45

15.0W

103

 

Table 1.  Power Tap Selector Switch

PAGE  4                                                                                                                                                                                                      

P/N 3101297   ISSUE 0