background image

© 2010 UTC Fire & Security. All rights reserved. 

1 / 8 

P/N 3100008 • REV 4 • ISS 09AUG10 

 

5531M and 5531MHV Adaptatone Installation 

Sheet 

 

Description 

Edwards Adaptatone Millennium is intended for industrial 
applications where high audible output and microcomputer 
reliability are required.  The Adapatatone Millennium series are 
UL and cUL Listed as Audible Signal Appliances for use in the 
hazardous locations listed in Table 1. 

The Adaptatone operates from local power.  It accommodates 
up to four normally-open contacts on its inputs.  The tone that 
sounds in response to an active input is determined by setting 
miniature programming switches inside the unit.  Table 6 has 
switch settings for setting tones. 

Four tones may be programmed into the unit at any time.  
These tones operate on a pyramid-type priority system.  The 
tone programmed on SW1 overrides the tones programmed on 
SW2, SW3, and SW4.  The tone on SW2 overrides the tones 
programmed on SW3 and SW4.  Likewise, the tone on SW3 
overrides the tone programmed on SW4.  The tone 
programmed on SW4 has the lowest priority and cannot 
override any other programmed tone. 

Speaker direction and the output level are easily adjustable.

 

Recording a Voice Message (5531MV 
Series) 

WARNING

:  High voltage is present when product is 

energized. 

1.  Put switches A and B on the programming dipswitch in the 

proper position for the message to be recorded (Figure 6).  
For programming a message longer than five seconds, 
use Message Location 1. 

 

Message 
Location 

Start Switch 

Settings 

Switch B 
Settings 

1 0 

Sec 

CLOSED 

CLOSED 

2 5 

Sec 

OPEN 

CLOSED 

3 10 

Sec 

CLOSED 

OPEN 

4 15 

Sec 

OPEN 

OPEN 

 

2.  Put switch PGM on the programming dipswitch in the 

“CLOSED”  position for programming mode (Figure 6). 

3.  Press and hold the record button while speaking clearly 

into the microphone to record your message.  Release the 
button when recording is complete. 

4.  To test the message, press and hold PLAY while in 

programming mode. 

NOTE:  This will play only the current location. 

WARNING:

  High volume may cause harm to personnel in 

close proximity. 

5.  Adjust the volume as necessary.  Set the main volume 

using the potentiometer on the main board (Figure 5 and 
Figure 6) and then set the voice volume using the 
potentiometer on the voice module board (Figure 6). 

Installation 

The Adaptatone may be mounted to any flat surface or may be 
used as a freestanding unit mounted to a rigid pipe.  The 
Adaptatone must be installed in accordance with the latest 
edition of the National Electrical Code or other regulations 
applicable to the country and locality of installation and by a 
trained and qualified electrician. 

For catalog numbers ending in "AQ", 24 VAC power must be 
transformer isolated from mains or line power. 

Содержание 5531M

Страница 1: ...n product is energized 1 Put switches A and B on the programming dipswitch in the proper position for the message to be recorded Figure 6 For programming a message longer than five seconds use Message...

Страница 2: ...apped holes in housing bosses before securing with a screwdriver Torque signal box cover screws to a minimum of 20 in lbs This ensures the required tight fit 6 Tightly secure the signal box cover usin...

Страница 3: ...0 3 8 Figure 1 Mounting the Adaptatone Figure 2 Terminal block TB1 Figure 3 Wiring to terminal block TB1 input circuit Figure 4 Wiring the Adaptatone Figure 5 PC board locations Figure 6 PC board loca...

Страница 4: ...g for compatibility with earlier versions of Adaptatone Figure 8 Installing with multiple dry relay contacts method 2 24V input board Figure 9 Installing with an open collector transistor 24 V input b...

Страница 5: ...MV 24N5 5531MV 120N5 135 C T4 100 C T5 5531M 24Y6 5531M 120Y6 5531MHV 24Y6 5531MHV 120Y6 5531MV 24Y6 180 C T3A 100 C T5 Table 2 Input board Catalog number Voltage Current 5531M 24AQ 5531M 24N5 5531M 2...

Страница 6: ...alternately 87 ms each 02 Siren OFF OFF OFF OFF ON ON 600 1250 Hz up and down sweep in 8 s and repeat 03 Stutter OFF OFF OFF ON OFF OFF Percussive 470 Hz 83 ms on 109 ms off 04 Slow Whoop OFF OFF OFF...

Страница 7: ...and 746 Hz alternating for 0 003 s each 29 Genesis Horn Cont ON OFF ON OFF ON OFF Continuous Genesis horn 2A Genesis Horn Temp ON OFF ON OFF ON ON Temporal Genesis horn 2B Warning 1 ON OFF ON ON OFF O...