EDS - TECHNICAL INSTRUCTIONS

1

REFLECTIVE  TYPE

OPTICAL BEAM LINEAR

SMOKE DETECTOR

RK 100  R

RK 100 RS

TECHNICAL MANUAL

TECHNICAL INSTRUCTIONS FOR

INSTALLATION, SETUP AND

MAINTENANCE

EDS - V. Ca' Nova Zampieri 6 - 37057 S. G. Lupatoto - VERONA - Tel. +39045547529 - Fax. +390458750065  - E.Mail: [email protected]  - Web: www.eds.eu

Содержание RK 100 R

Страница 1: ...PTICAL BEAM LINEAR SMOKE DETECTOR RK 100 R RK 100 RS TECHNICAL MANUAL TECHNICAL INSTRUCTIONS FOR INSTALLATION SETUPAND MAINTENANCE EDS V Ca Nova Zampieri 6 37057 S G Lupatoto VERONA Tel 39045547529 Fax 390458750065 E Mail eds eds eu Web www eds eu ...

Страница 2: ...the device signal using the P1 trimmer the adjustment screws V1 V2 V3 on the optical block a multimeter or the STS01 instrument blue Red Led signal level indication fig 8 board 8 regulate the signal between 4 7V and 5V with the P1 trimmer 9 verify the functioning obcuring the FX 10 select the desired sensitivity of the Obscuration circuit with the SW2 selector 40 50 60 70 11 select the desired sen...

Страница 3: ... drill expansion plugs etc the following elements 1 7mm C Key 1 alignment lamp we recommend to use LAL02 lamp optional or an electric torch with powerful and contrated beam 1 multimeter werecommendananalogichandTesteroran analogical STS01 meter optional to be plugged on the special connector positioned on detector s circuit 3 2 Unscrew the 4 fixing screws fig 2 and remove the cover 3 3 Install the...

Страница 4: ...sitive to the obscuring This circuit founds its operation on the diminution of the infrared ray intensity along the optic run between the detector and the reflector caused by the smoke Turbulence circuit sensitive to the Turbulence During the beginning phase of the fire generally there are some clouds of smoke and warm air that climb toward the ceiling When these clouds and warm air intercept the ...

Страница 5: ...ou don t have a multimeter it is still possible to get good results in the optical alignment of the detector looking at the detector s blue and red leds indications Operation is the following 1 flash of the blue Led 1 Volt 1 flash of the red Led 0 5 Volts if the signal is smaller of 0 5V the blue led and red one are off if the signal in the range 0 5 1 V the red led performs 1 flash remains off fo...

Страница 6: ...nal will be decreased because of the absorption caused by the cover 10 4 The inside electronics attends 5 minutes for the installation of the cover and later performs a rapids procedure time 1 2 minutes take again the signal of the RK100R to 4 7 5V 10 5 Stopped this phase of adjustment the detector becomes operational The blue Led of Alignment stops detail cap 10 2 and and it begins to flash as de...

Страница 7: ...rm and is not removed power for over 5 seconds When the memory is not activated if the detector goes to alarm theAlarm relay and the frontal Led are disarmed as soon as it stops the alarm 14 2 Memory of the data of configuration and setting In case of black out the memory inside preserve the data To the return of the feeding the detector later once of initialization of about 2 minutes returns to n...

Страница 8: ...g 3 fig 4 fig 5 fig 6 A A A A disco bianco white disc diodo fotoemittente photoemitting diode foro hole rivelatore riflettore rivelatore LAL 02 lampada 0 10 20 30 40 50 60 0 10 20 30 40 50 60 70 80 distanza m diametro del raggio cm 70 80 90 100 ...

Страница 9: ... 5 5 5 4 3 5 6 5 5 4 0 8 5 6 3 0 X F 1 5 5 5 4 2 0 7 5 5 3 5 8 0 7 4 0 0 1 5 8 fig 7 fig 8 G N I H S A L F T L O V N O I T A L E R T L O V h s a l F N d e L e u l B h s a l F N d e L d e R 5 0 F F O F F O 1 5 0 F F O 1 5 1 1 1 F F O 2 5 1 1 1 5 2 2 2 F F O 3 5 2 2 1 5 3 3 3 F F O 4 5 3 3 1 7 4 4 e l b a i r a V F F O 5 9 4 7 4 t h g i l x i F F F O 5 9 4 n o i t a r u t a s t h g i l x i F t h g i...

Страница 10: ...tacts respectively of the alarm relay turbulence and fault normally closed NC or normally open NO position 1 2 output contact normally open NO position 2 3 output contact normally closed NC JP4 must be in position 1 2 to have the contact closed because the fault relay is normally activated The RK100 200B detector is normally factory preset with closed NC contacts For the alarm relay the indication...

Страница 11: ...ltage 11 30 Vcc ALARM relay contact TURBULENCE relay contact FAULT relay contact analog signal output 0 5V 1 2 3 4 5 6 7 8 9 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 JP1 1 2 3 JP5 1 2 3 1 2 3 1 2 3 JP2 JP4 JP3 alarm relay turbo relay fault relay P1 JP7 SW1 SW2 SW3 TURBO SENS POWER ON OFF ALI ON OFF MEM 1 2 3 4 5 6 7 8 9 V1 V2 V3 LED di Allarme LED di Allineamento RX TX JP6 Alarmrelais Turborelais Fehlerrelai...

Страница 12: ...detector is a zone of the system The state of the indicated relays correspond to the normal operation condition of the detector The alarm output is the one of the alarm relay circuit sensible to obscuration in alarm or the one from the turbulence relay circuit sensible to turbulence heat in alarm The turbulence relay if not necessary can be left unused The fault output is the one from the NC conta...

Страница 13: ...a 25 06 2010 FX01 Reflector 85mm diameter FX02 Reflector with anodized aluminium support 180x90mm dimensions FX03 Reflector with anodized aluminium support 175x205mm dimensions FX09 Reflector plastic support small dimensions 40x60mm dimensions LAL02 Optical alignment lamp The RK series detectors during installation must be optically aligned This lamp is suitable to do an optimal alignment The oper...

Страница 14: ... COURSE OF DEALING USAGE OF TRADE BY STATUTE OR OTHERWISE IS HEREBY STRICTLY LIMITED TO THE TERM OF THIS WRITTEN WARRANTY This agreement shall be the sole and exclusive remedy available to the Purchaser with respect to the purchase In the event of any alleged breach of any warranty or any legal action brought by the purchaser based on alleged negligence or other tortuous conduct by EDS the Purchas...