4-14
indicator, connection type indicator for connection through local or remote port and
units and multipliers. The LCD does not have a backlight
•
Figure 4-13 LCD with all segments turned on
To progress to the next page, press the
Select
button. Each time the button is pressed the
display moves to the next page. The display may also be setup to automatically cycle
the display through the pages, pausing if the
Select
button is pressed.
For more detailed information on the LCD and
Select
Display”.
Reconnect/Boost or Billing Reset Button
An optional
Reconnect, Boost
, or
Billing Reset
button may be fitted above the select
button (See Figure 4-14). The push button has a 2.5mm diameter hole through it,
allowing it to be sealed using standard sealing wire.
•
Figure 4-14 Location of the
Billing Reset
/
Boost
button
When used as a
Reconnect
button, holding the button down for at least half a second
will connect the customers supply, if it is enabled for connection. The display will show
“Connect”. If it is not enabled, the display will show “not enabled” and the contactor
state will not change.
Pushing both the
Select
button and the
Reconnect
button at the same time will cause the
contactor to be disconnected. The message “Disconnect” will be displayed on the LCD.
The
Reconnect
button can also cause a boost operation for load control outputs,
depending on configuration.
4-14 EDMI Atlas Hardware Reference Manual