CMU 200 - User manual

RS485 bus termination and stabilisation

baud rate

RS485 bus termination and stabilisation

TERMINATION

At high transmission rates or long distance, RS485 bus termination is necessery.

The termination on RS485 bus must be set on both ends of the RS485 bus.

STABILISATION

Some device, to work properly, demands that RS485 must always be in known and valid state. 
That is, when + (positive) pin is more than 200 mV positive than – (negative) pin. Pins + and – 
are sometimes marked as A and B. In case that no device on RS485 bus is transmitting or in 
case of short circuit, there is no voltage difference between those pins and some device do not 
work correctly. 

On this port board so called „true fail-safe“ RS485 chip is used so board works correctly without 
stabilisation at invalid RS485 bus state. But still switches for stabilisation are provided on port 
board. 

The stabilization on RS485 bus may be set on one device only!

Switches at the lower side of connector:

Switch

1 (J13)

2 (J12)

3 (J11)

Description

RS485 stabilisation

RS485 termination

RS485 stabilisation

Page:

Company:

Device:  

Document: 

Code:

Version:

Date:

16

Ediseja 21 CMU 200

User manual CMUMU200

V3

01.02.13

Picture 3.2: RS485 BUS schematic

Содержание CMU 200

Страница 1: ...CMU 200 User manual ...

Страница 2: ...rega Flander Date 01 02 13 Reference document Consultants Approved by Grega Flander Code CMUMU200 History 1 first release 2 39 channel star coupler added 3 ethernet port added DC power suppy added schematics redrawn some schematic added Page Company Device Document Code Version Date 2 Ediseja 21 CMU 200 User manual CMUMU200 V3 01 02 13 ...

Страница 3: ...diseja 21 d o o Drenov Gric 175 1360 Vrhnika Slovenia EU Tel 386 1 75 02 275 Email grega flander ediseja21 com www ediseja21 com Copyright Copyright Ediseja 21 2011 All rights reserved Warnings In this paper the following terms are used Danger indicates that death severe personal injury or substantial property damage will result if proper precautions are not taken Warning indicates that death seve...

Страница 4: ...es after being familiar with warnings and safety notices in this paper and other safety regulations Warning Device must operate completely assembled Device must be used as described No modifications of the device should be made Warning Do not open device while it is energized Hazardous voltage is present inside the device Disconnect all connectors before opening Warning If device is damaged discon...

Страница 5: ...Hx1 FOTx30 232x1 12 13 2 2 CONVERTERS 14 2 2 1 20 CHANNEL RS232 TO FIBER OPTIC CMU 200 HACx2 232x20 FOTx20 7 14 3 HARDWARE DESCRIPTION 15 3 1 RS232 INTERFACE 15 3 2 RS485 INTERFACE 15 3 3 FO MM INTERFACE BOARD 18 3 4 ETH INTERFACE BOARD 19 4 INSTALLATION 22 4 1 INSTALLATION 22 5 COMMISSIONING AND MAINTENANCE 23 5 1 COMMISSIONING 23 5 2 MAINTENANCE 23 6 TECHNICAL DATA 24 6 1 DIMENSIONS 26 7 ORDERIN...

Страница 6: ...oses different software versions and different hardware configuration have been developed Software Software is application dependent and allows different hardware configurations Software s task is switching between communication ports and allows almost any combination between them Hardware CMU 200 can handle up to 40 different interface boards Currently available interface boards non isolated RS23...

Страница 7: ...DESCRIPTION Typical applications Company Device Document Code Version Date Page Ediseja 21 CMU 200 User manual CMUMU200 V3 01 02 13 7 Picture 1 1 CMU 200 HACx2 232x39 2 star coupler typical application ...

Страница 8: ...CMU 200 User manual Page Company Device Document Code Version Date 8 Ediseja 21 CMU 200 User manual CMUMU200 V3 01 02 13 Picture 1 2 Two 30 port star coupler connection for 60 slave device application ...

Страница 9: ...some devices are drawn Due to many options it is not possible to present every possible variant If there is no variant needed please contact us 2 1 STAR COUPLERS Company Device Document Code Version Date Page Ediseja 21 CMU 200 User manual CMUMU200 V3 01 02 13 9 ...

Страница 10: ...3 CHANNEL RS232 to 2xRS232 CMU 200 HACx2 232x39 2 Page Company Device Document Code Version Date 10 Ediseja 21 CMU 200 User manual CMUMU200 V3 01 02 13 Picture 2 1 CMU 200 HACx2 232x39 2 3 port star coupler 13 channels schematic ...

Страница 11: ...2 to 2xFIBER OPTIC CMU 200 HACx2 232x13 FOTx26 2 Company Device Document Code Version Date Page Ediseja 21 CMU 200 User manual CMUMU200 V3 01 02 13 11 Picture 2 2 CMU 200 HACx2 232x13 FOTx26 2 3 port star coupler 3x13 channels schematic ...

Страница 12: ... to 39xFO CMU 200 HACx2 485x1 FOTx39 12 Page Company Device Document Code Version Date 12 Ediseja 21 CMU 200 User manual CMUMU200 V3 01 02 13 Picture 2 3 CMU 200 HACx2 485x1 FOTx39 12 40 port 1master 39 slaves star coupler schematic ...

Страница 13: ...232 CMU 200 HACx2 ETHx1 FOTx30 232x1 12 Company Device Document Code Version Date Page Ediseja 21 CMU 200 User manual CMUMU200 V3 01 02 13 13 Picture 2 4 CMU 200 HACx2 ETHx1 FOTx30 232x1 12 32 port 1master 31 slaves star coupler schematic ...

Страница 14: ... 1 20 CHANNEL RS232 TO FIBER OPTIC CMU 200 HACx2 232x20 FOTx20 7 Page Company Device Document Code Version Date 14 Ediseja 21 CMU 200 User manual CMUMU200 V3 01 02 13 Picture 2 5 CMU 200 HACx2 232x20 FOTx20 7 20 channel converter schematic ...

Страница 15: ...485 INTERFACE Description Single galvanically isolated half duplex RS485 port with Phoenix 3 pin screw connector Automatic switch to receive after end of transmission with additional terminating and stabilizating resistors Hardware settings For proper functioning of that board some settings must be done board address Company Device Document Code Version Date Page Ediseja 21 CMU 200 User manual CMU...

Страница 16: ...ase that no device on RS485 bus is transmitting or in case of short circuit there is no voltage difference between those pins and some device do not work correctly On this port board so called true fail safe RS485 chip is used so board works correctly without stabilisation at invalid RS485 bus state But still switches for stabilisation are provided on port board The stabilization on RS485 bus may ...

Страница 17: ...all standard communication protocols that do not request special timings If special protocols small request respond time required are used please note it in order 48L interface BAUD rate Switches 1 J4 2 J5 3 J6 300 OFF OFF OFF 600 OFF OFF ON 1200 OFF ON OFF 2400 ON OFF OFF Connector pin table MSTB 1 2 3 Description GND B A Company Device Document Code Version Date Page Ediseja 21 CMU 200 User manu...

Страница 18: ...nector or other connectors see ordering with both positive or negative logic Hardware settings Page Company Device Document Code Version Date 18 Ediseja 21 CMU 200 User manual CMUMU200 V3 01 02 13 Picture 3 4 Data rate vs cable lenght Picture 3 3 485 interface board appearance left and 48L interface board appearance right ...

Страница 19: ...ity it is recommended that positive logic on FO interfaces is used light OFF in idle state In other case if optic loop on one port is broken communication with other slave ports also will not work 3 4 ETH INTERFACE BOARD Description Single virtual com port with RJ45 connector Settings Company Device Document Code Version Date Page Ediseja 21 CMU 200 User manual CMUMU200 V3 01 02 13 19 Picture 3 5 ...

Страница 20: ...CMU 200 User manual Lantronix Redirector Page Company Device Document Code Version Date 20 Ediseja 21 CMU 200 User manual CMUMU200 V3 01 02 13 Picture 3 6 Lantronix Port Redirector settings ...

Страница 21: ...ETH INTERFACE BOARD Lantronix Device Installer Company Device Document Code Version Date Page Ediseja 21 CMU 200 User manual CMUMU200 V3 01 02 13 21 Picture 3 7 Lantronix Device Installer settings ...

Страница 22: ...ce for damage at unpacking If device is damaged it must not be installed but It should be send to the manufacturer for repair The device should not be opened The device should be mounted on 19 rack via 4x M6x10 mm screws Attach ground wire before attaching power supply Device must be grounded during operation The power supply of the device should be provided with an external disconnector for the s...

Страница 23: ...perate completely assembled Device must be used as described No modifications of the device should be made Attach ground wire before attaching power supply Device must be grounded during operation Check if the power supply voltage complies with device operation voltage Do not open device while it is energized Hazardous voltage is present inside the device If single mode fiber optic interface is us...

Страница 24: ...ll duplex Speed up to 230 k BAUD Number of ports 1 Distance up to 15 m Isolation none GND earthed interface type 232 or 23R 1000 V DC interface type 23I or 2RI Connector type DB9 female Lines in 1 Rx Lines out 1 Tx Communication port RS485 Type RS485 Direction half duplex Speed 19200 115200 or 300 2400 BAUD see ordering Number of ports 1 Distance up to 1200 m Isolation 1000 V DC Connector type MST...

Страница 25: ...mber of ports 1 Distance up to 500 m Connector type ST if other connector type is needed see ordering Communication port ETH Type ethernet Direction full duplex Speed 300 to 230 k BAUD Number of ports 1 Manufacturer Lantronix Type Xport XP1001000 03R Link WWW lantronix com slowest interface defines device s maximum speed Device Weight 3 kg Dimensions see picture W H D 19 rack 3U 133 mm 154 mm conn...

Страница 26: ...ack Class I Overvoltage category II Communication indicator Receiveing yellow LED marked Rx Tranmitting green LED marked Tx 6 1 DIMENSIONS Page Company Device Document Code Version Date 26 Ediseja 21 CMU 200 User manual CMUMU200 V3 01 02 13 Picture 6 1 CMU 200 dimensions ...

Страница 27: ...T x n FO multimode SMA FOA x n Ethernet one virtual com port ETH x n n number of interfaces maximum number of interfaces in CMU 200 is 40 Each 23R and 2RI interface must be treated as two interfaces Function three ports star coupler up to 13 independent channels 2 converter up to 20 independent channels 7 40 port star coupler 1 master up to 39 slaves 12 For other functions please contact us Softwa...

Страница 28: ...razvoj elektronskih naprav d o o Drenov Gric 175 1360 Vrhnika Slovenia EU Tel 386 1 75 02 275 grega flander ediseja21 com www ediseja21 com Page Company Device Document Code Version Date 28 Ediseja 21 CMU 200 User manual CMUMU200 V3 01 02 13 ...

Отзывы: