background image

CMU-24VDC-ITL Cabinet Monitor Unit 

Operations Manual 

Eberle Design Inc. 

Page 7 

When a transition from the inactive state to the active state or a transition from the active 

state to the inactive state is absent for greater than 2500 milliseconds, the CMU-24VDC will 

set a status bit in the Type 189 frame. This alarm condition will not cause a FSA. It should 

cause the appropriate response in the ATC. This status is non-latching such that once a 

status bit has been set, the sensing of five valid transitions of the input will clear the status 

bit. 

2.12 CMU POWER FAILURE 

The  CMU-24VDC  will monitor the +24VDC  POWER  input  and the NRESET and 

POWERDOWN cabinet control inputs to determine a CMU Power Failure response. The 

POWERDOWN signal in the False (low) state indicates loss of power in the ATC. A CMU 

Power Failure will be recognized when both the POWERDOWN and NRESET signals are 

False (low) for greater than 100 ms or the 24VDC  POWER  voltage is less than the  DC 

Power Level Sense Dropout defined in 5.1.

 

2.12.1 24VDC POWER LEVEL SENSE 

The CMU-24VDC will monitor the CMU 24VDC POWER input and AMU 24VDC POWER 

inputs reported by each AMU-24VDC. When any 24VDC POWER voltage is less than the 

DC Power Level Sense defined in 5.1 for greater than the DC Power Fail Monitor timing 

defined in 5.2,  the  CMU-24VDC  will cause a NFSA. Once NFSA has been set, the 

POWERDOWN and NRESET signals will not be monitored until all DC  voltages have 

exceeded the DC Power Level Sense Restore level defined in 5.1.  

2.12.2 POWER INTERRUPT 

The CMU-24VDC will disable monitoring of the +12VDC and +24VDC power supply inputs 

when either the POWERDOWN or NRESET input is False (low). When the POWERDOWN 

and NRESET signals are both False (low) the CMU-24VDC will cause a NFSA. 

2.12.3 POWER RECOVERY 

When the POWERDOWN input is True (high) and the NRESET signal goes from False 

(low) to True (high) the CMU-24VDC  will begin timing the programmed Minimum Flash 

Interval. During the Minimum Flash Interval the CMU-24VDC will be in NFSA.

 

2.12.4 POWER UP 

Following initial application of 24VDC voltage the CMU-24VDC will maintain a NFSA until 

the POWERDOWN input is True (high) and the NRESET signal goes from False (low) to 

True (high). The CMU-24VDC  will then begin timing the programmed Minimum Flash 

Interval. During the Minimum Flash Interval the CMU will be in NFSA. 

2.12.5 MINIMUM FLASH INTERVAL 

During the Minimum Flash Interval the CMU-24VDC will be in NFSA. The Minimum Flash 

Interval will be programmed in the Datakey between the limits of 6 seconds to 16 seconds 

with an incremental adjustment of 1 second. The CMU-24VDC will not set a FSA during the 

Minimum Flash Interval. 

2.13 FIELD OUTPUT CHECK 

The Field Output Check is a continuous verification that the field signal output states set by 

the ATC are properly driven to the signal loads and correctly sensed by the AMU-24VDC 

and  CMU-24VDC. It is an enhanced function made possible by the Serial Bus #1 

communications between the ATC and CMU-24VDC. The CMU-24VDC will receive a Type 

61 message from the ATC that contains an image of the controller output commands to the 

load switches. When a fault condition triggers the CMU-24VDC, the Type 61 message 

information received while the fault condition was being timed will be used by the CMU-

24VDC to determine whether the sensed field signal input status corresponded to the ATC 

Содержание CMU-24VDC-ITL Series

Страница 1: ...HIS MANUAL CONTAINS TECHNICAL INFORMATION FOR THE CMU 24VDC ITL SERIES ITS CABINET MONITOR UNIT REVISION OCTOBER 2008 pn 888 3912 002 CMU 24VDC ITL Low Voltage DC Cabinet Monitor Unit Operations Manua...

Страница 2: ...No 7 246 037 Canadian Patent No 2 574 101 U S Pat No 9 460 620 MAINTENANCE NOTE THIS EBERLE DESIGN INC CABINET MONITOR UNIT HAS BEEN CAREFULLY INSPECTED AND TESTED TO ENSURE PROPER OPERATION IT IS REC...

Страница 3: ...tus 6 2 9 1 Local Flash Status Recovery 6 2 10 Circuit Breaker Trip Status 6 2 11 Flasher Unit Output Failed Alarm 6 2 12 CMU Power Failure 7 2 12 1 24VDC Power Level Sense 7 2 12 2 Power Interrupt 7...

Страница 4: ...CONFLICT Indicator 14 4 1 5 LACK OF SIGNAL Indicator 14 4 1 6 MULTIPLE Indicator 14 4 1 7 CU LOCAL FLASH Indicator 14 4 1 8 CLEARANCE Indicator 14 4 1 9 FIELD CHECK Indicator 14 4 1 10 SB 1 ERROR Indi...

Страница 5: ...t is specially configured for low voltage 24Vdc DC signal loads 1 2 CHANNEL CONFIGURATION The CMU 24VDC can be configured to monitor up to 28 physical load switch channels of three inputs per channel...

Страница 6: ...OFTWARE INTERFACE The front panel display of the CMU 24VDC provides limited operational status This status includes real time indicators for Power Serial Bus 1 activity Serial Bus 3 activity and eleve...

Страница 7: ...sts longer than the minimum defined period the CMU 24VDC will enter the Failed State Action fault mode causing the OUTPUT relay to de energize and the contacts on the OUTPUT NO pins to open The cabine...

Страница 8: ...are detected as concurrently active for less than 200 milliseconds the CMU 24VDC will not cause a LFSA When any conflicting channels are detected as concurrently active for 500 milliseconds or more t...

Страница 9: ...the CMU 24VDC may or may not cause a LFSA The Current Sense Unit CSU monitor function is hardwired to the maximum of 28 physical channels thus Virtual Channels do not have CSU monitoring capability Th...

Страница 10: ...ellow Change plus Red Clearance monitoring will be disabled when the MC COIL STATUS input is not active There is programming in the Datakey to disable Minimum Yellow Change plus Red Clearance interval...

Страница 11: ...24VDC power supply inputs when either the POWERDOWN or NRESET input is False low When the POWERDOWN and NRESET signals are both False low the CMU 24VDC will cause a NFSA 2 12 3 POWER RECOVERY When th...

Страница 12: ...CU in the Type 61 frame When a mismatch is detected while a Conflict Lack of Signal or Multiple fault is timing Field Check Status will be reported with the fault to indicate the faulty channel s and...

Страница 13: ...illiseconds the monitor circuit will force a LFSA R and illuminate the DIAGNOSTIC indicator 2 15 RECURRENT PULSE DETECTION This error detection function supplements the normal Conflict Multiple and La...

Страница 14: ...imum Recurrent Pulse detection can be disabled with the SEL1 option jumper see Section 2 15 1 2 15 1 RECURRENT PULSE DETECTION DISABLE The Recurrent Pulse Detection function can be disabled by solderi...

Страница 15: ...ed to the 24VDC supply 3 2 LED SIGNAL LOAD ELECTRICAL REQUIREMENTS LED Signal loads shall meet the following requirements under all conditions of temperature time etc 1 the signal shall emit NO light...

Страница 16: ...than the Not Active threshold defined in Cabinet Control 5 1 The CMU 24VDC will report the state of this input in the Type 189 frame 3 4 3 MAIN CONTACTOR MC SECONDARY STATUS The cabinet should be wire...

Страница 17: ...100 msec and the OUTPUT relay energized Continuously activating the input will not affect CMU 24VDC operation The EXTERNAL TEST RESET input is intended for use in testing the CMU 24VDC and should not...

Страница 18: ...ndicator will illuminate when the CMU 24VDC is in FSA as a result of a Lack of Signal Inputs fault See section 2 5 4 1 6 MULTIPLE INDICATOR A red MULTIPLE indicator will illuminate when the CMU 24VDC...

Страница 19: ...m the main CMU 24VDC power supply and 48VDC Ground A Null Modem cable is required for connection to a standard PC port 4 3 RESET BUTTON Depressing the RESET button resets the CMU 24VDC from the FSA co...

Страница 20: ...tive less than 19 5 Vrms DC Power Fail Monitor DC Power Level Sense Restore greater than 22 Vrms DC Power Level Sense Dropout less than 21 5 Vrms DC Voltage Monitors 24 Volt Monitor Active greater tha...

Страница 21: ...00 ms Field Check Fault greater than 1000 ms No Fault less than 700 ms Typical 850 ms Local Flash Status Circuit Breaker Trip Fault greater than 450 ms No Fault less than 200 ms Typical 350 ms DC Powe...

Страница 22: ...A17 PowerDown B17 PowerDown A18 SB3 TxData B18 SB3 TxData A19 SB3 RxData B19 SB3 RxData A20 SB3 Clock B20 SB3 Clock A21 LF Status B21 LF Status A22 Output Relay NO B22 Output Relay NO A23 CB Trip Stat...

Страница 23: ...CMU 24VDC ITL Cabinet Monitor Unit Operations Manual Eberle Design Inc Page 19 Pin Function I O 5 Signal Ground 6 Reserved 7 Reserved 8 Reserved 9 Reserved...

Отзывы: