EDGE™ MTP

®

 TAP Module 

Installation and Testing

1. 

General

This procedure describes EDGE™ MTP Tap Modules, which are 

available for both multimode and single mode applications. 

Compatible with all EDGE rack-mountable connector housings, MTP 

Tap modules have three MTP connectors per module, either one front-

mounted and two MTP connectors in the back of the module or two 

MTP connectors on the front of the module and one MTP connector in 

the back (Figure 1). 

 

 

 

The module contains 12 fiber optic splitters which divide the incoming optical signals into two outputs, one 

for live link traffic and one for monitoring. The monitor traffic is routed via the “TAP”-labeled MTP port to a 

monitoring device which filters the data and sends it to various software tools for analysis, where it is then viewed 

in application-layer software for security threats, performance issues, or system optimization. 

IMPORTANT: 

 Please note that Tap module systems have two outputs for each input, which may require two power 

meters, and depending on the system configuration, possibly require an additional crafts person in 

another location when testing.

TPA-6131

TAP

LIVE

LIVE

LIVE

LIVE

TAP

Figure 1 

related literature  |

SRP-003-794, EDGE™ Solution

Table of Contents
1. General

   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .

1

2. Precautions

   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .

2

3. 

Tools and Materials

   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .

2

4. 

Connector and Adapter Cleaning 

   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .

2

5. 

The Functionality of the Tap Module Splitters

   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .

3

6. 

Installing EDGE™ MTP Tap Modules 

   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .

4

7. 

Referencing the Test Equipment for an MTP Tap Module

   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .

4

8. 

Testing the Live Portion of the System

   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .

6

9. 

Testing the Tap Portions of the System

   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .

9

10. 

Simultaneous Testing of the Live and Tap Portions of an MTP Tap Module 

   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .

12

Содержание MTP Tap Module

Страница 1: ... port to a monitoring device which filters the data and sends it to various software tools for analysis where it is then viewed in application layer software for security threats performance issues or system optimization IMPORTANT Please note that Tap module systems have two outputs for each input which may require two power meters and depending on the system configuration possibly require an addi...

Страница 2: ...d Materials The following tools and materials are required for this procedure Two 2 power meters with LC port adapters Two 2 LC LC jumpers One 1 SC LC jumper for the light source Three 3 LC LC single mode adapters Light source with SC port adapter At least one MTP to LC harness with Universal Polarity Wiring Multimode module harness p n H750512TE8 KW003F Single mode module harness p n H900412GE8 K...

Страница 3: ... modules must be tested with directionality in mind The source must be always connected to the input of the splitter and a meter must be connected to at least one of the outputs of the splitter Connecting a source to the output of a splitter will result in high attenuation Likewise connecting network transmitters to the output of a splitter can result in damage to the receiver port Thus it is impo...

Страница 4: ...either 1310 or 1550 nm To reference the source and two meters Step 1 Clean and insert the SC end of the SC to LC jumper Reference Jumper no 1 or RJ1 into the output of the light source Step 2 Clean and insert the LC end of RJ1 jumper into the LC port adapter of Meter no 1 M1 Figure 6 For multimode only Wrap the jumper 5 times and secure it in a 22 mm mandrel with tape standard 50 µm multimode proc...

Страница 5: ... Figure 8 Step 10 Verify that the RJ1 RJ3 mated pair are acceptable with a loss 0 10 dB for multimode and 0 20 dB for single mode Step 11 Disconnect RJ1 s LC connector from the LC adapter and protect it with a clean dust cap Step 12 Leave the LC adapter on the end of RJ3 for the remainder of this procedure since it will be required for mating to theTAP port test harness 7 3 Referencing is now comp...

Страница 6: ...ized 50µm 850 nm Bend improved single mode 1310 nm Component Loss max dB 1 Loss max dB 1 MTP mated pair loss 0 35 0 75 LC mated pair loss 0 15 0 25 Splitter 50 50 dB 3 7 3 5 Splitter 70 30 dB 2 4 5 8 2 1 5 8 Fiber attenuation 2 8 dB km 0 4 dB km 1 Insertion loss specifications when mated to other system components of a like performance specification Tap Module A TPA 6133 Near end Budget loss for a...

Страница 7: ...tep 1 Install the Light Source RJ1 LC connector adapter on the LC number 2 of a test harness plugged into the front mounted LIVE Port of the MTPTap module Step 2 Install RJ2 s LC connector into the number 1 port of the Edge module Module B in Figure 10 Figure 10 Light Source Test harness M1 RJ2 RJ1 and adapter Do NOT disconnect Do NOT disconnect 0 00 dB Pretium EDGE Module B B 2 3 B 1 2 1 A TPA 61...

Страница 8: ...r on the number 1 LC connector of the harness plugged into the LIVE Port of the MTPTap module Figure 11 8 7 Note that steps 8 4 and 8 6 can be combined if using an optical test set with both a source and a meter on one unit This will test two fibers at a time because there will be two sources and meters It is important that the source is always plugged into the transmit even fibers and that the me...

Страница 9: ...ystem loss for theTAP system add the loss values of the components that are in the system as illustrated in Figures 12 and 13 Figure 12 Figure 13 Tap Module A TPA 6136 Budget loss for a Tap multimode system using OM4 fiber and 50 50 splitters 0 35 0 35 0 15 3 7 50 50 splitter MTP mated pair MTP mated pair 0 15 0 35 3 7 0 35 0 15 4 7 dB LC mated pair 0 15 LC mated pair Tap port test harness Tap por...

Страница 10: ...t Sequence 9 4 To begin testing theTAP portion of the MTPTap module from the A LIVE Port harness to the module TAP port test harness Figure 14 Step 1 Install the Light Source RJ1 LC connector adapter onto the LC number 2 connector of a test harness plugged into the LIVE port of the MTPTap module Step 2 Install RJ2 s LC connector adapter onto the LC number 1 connector of a harness plugged into the ...

Страница 11: ...Install the Light Source RJ1 LC connector into LC number 2 port of the Edge module B at the Far End Step 2 Install RJ2 s LC connector adapter onto LC number 2 of the harness plugged into theTAP port of the MTPTap module Module A Figure 15 9 7 Note steps 9 4 and 9 6 CANNOT be combined if using an optical test set with both a source and a meter in one unit TAP port test harness M1 RJ1 Do NOT disconn...

Страница 12: ...ource RJ1 LC connector into the number 2 port of the Edge module Module B Step 2 Install Meter 1 RJ2 s LC connector adapter onto LC number 1 of the harness plugged into the front mounted LIVE Port of the MTPTap module Step 3 Install Meter 2 RJ3 s LC connector adapter onto LC number 2 of the harness plugged into theTAP port of the MTPTap module Step 4 Continue testing through on the even fibers of ...

Страница 13: ...ll the Light Source RJ1 LC connector adapter onto LC number 2 of the harness plugged into the LIVE Port of the MTPTap module Step 2 Install Meter 1 RJ2 s LC connector into the number 1 port of the Edge module Module B Step 3 Install Meter 2 RJ3 s LC connector adapter onto LC number 1 of the harness plugged into the TAP port of the MTPTap module Step 4 Continue testing through on the even fibers of...

Отзывы: