Chapter 2
| Installing the RPS
Grounding the Chassis
– 20 –
Grounding the Chassis
The rear panel of the RPS chassis includes a dual-screw grounding terminal. It must be
connected to ground to ensure proper operation and to meet electromagnetic
interference (EMI) and safety requirements.
Figure 8: Grounding Terminal
Before connecting AC power to the RPS, ground the RPS to earth as described below.
1.
Ensure that the rack on which the RPS is to be mounted is properly grounded and
in compliance with ETSI ETS 300 253.
2.
Ensure that there is a good electrical connection to the grounding point on the
rack (no paint or isolating surface treatment).
3.
Disconnect all power cables to the switch.
4.
The RPS chassis is connected internally to 0 V. This circuit is connected to the dual-
screw grounding terminal on the rear panel of the RPS (left of the AC power
socket). The surface area around this terminal is not painted in order to provide for
a good connection. Attach a 6 AWG stranded copper wire to the grounding
terminal on the switch.
5.
Then attach the grounding wire to the ground point on the rack.
Grounding Wire
Dual-Screw Grounding Terminal
2
1