4. Ground the Switch

Ensure the rack is properly grounded and in compliance 
with ETSI ETS 300 253. Verify that there is a good electrical 
connection to the grounding point on the rack (no paint or 
isolating surface treatment).

Attach the grounding wire #14 AWG to the grounding point 
on the switch rear panel. Then connect the other end of the 
wire to rack ground.

 

For details on grounding the switch 

with a 12 VDC PSU in an Open Rack, refer to the Edgecore 
ORSA-1U Open Rack Tray Set 

Installation Guide

.

Caution:

 The earth connection must not be removed 

unless all supply connections have been disconnected.

Attention:

 

Le raccordement à la terre ne doit pas être retiré 

sauf si toutes les connexions d’alimentation ont été 
débranchées.

5. Connect Power

Install one or two AC or DC PSUs in the switch.
The switch supports up to two PSUs that must have the 
same matching airflow direction as the installed fan trays.

Connect an external AC or DC power source to the PSUs.

36 

– 

75 VDC Return (blue 

wire)

Chassis Ground (yellow-
green wire)

-36 

– 

-75 VDC (brown 

wire)

Open Rack tray connector 
for 12 VDC PSU

2

1

1

2

2

1

1

2

3

2

1

4

1

3

2

4

Caution:

 Use a UL/IEC/EN 60950-1 certified power supply 

to connect to a DC converter, and a #14 AWG (for 36–75 VDC 
PSU) or #10 AWG (for 12 VDC PSU) wire to connect to a DC 
PSU.

Attention:

 

Utilisez une alimentation certifiée UL/IEC/EN 

60950-1 pour le connecter à un convertisseur CC et un câble 
AWG #14 (pour -36 VDC à -72 VDC) ou AWG #10 (pour 12 
VDC PSU)pour vous connecter à une alimentation CC.

6. Verify Switch Operation

Verify basic switch operation by checking the system LEDs.
When operating normally, the PS1/PS2 and Fan LEDs should 
all be on green.

7. Perform Initial System Boot

If the network operating system (NOS) installer is located on 
a network server, first connect the RJ-45 Management 
(Mgmt) port to the network using Category 5, 5e or better 
twisted-pair cable. (Not required if the NOS installer is 
located on attached storage.)

Boot the switch. Wait for the ONIE software to locate and 
execute the NOS installer, and then wait for the installer to 
load the NOS software image.
Subsequent switch boots will bypass ONIE and directly run 
the NOS software.

Note:

 Refer to the network operating system (NOS) installer 

and NOS documentation for details on software options and 
set up for ONIE.

8. Connect Network Cables

For the RJ-45 Management port, connect 100-ohm Category 
5, 5e or better twisted-pair cable.

Connect DAC cables to the QSFP+ slots. Or first install QSFP+ 
transceivers and then connect fiber optic cabling to the 
transceiver ports. 
The following transceivers are supported:

40GBASE-CR4

40GBASE-SR4

40GBASE-LR4

1

1

1

2

2

1

1

2

Содержание AS6712-32X

Страница 1: ...odules have a front to back F2B airflow direction all the installed fan tray modules must also have a F2B airflow direction Attention Le commutateur comprend des modules d alimentation et de bac de ve...

Страница 2: ...for 36 75 VDC PSU or 10 AWG for 12 VDC PSU wire to connect to a DC PSU Attention Utilisez une alimentation certifi e UL IEC EN 60950 1 pour le connecter un convertisseur CC et un c ble AWG 14 pour 36...

Страница 3: ...Rating 100 240 VAC 50 60 Hz 400 Watts AC Input 100 240 VAC 50 60 Hz 6 3 A DC Output 5 VSB 3 A 12 VDC 33 A DC PSU Power Rating 48 VDC 400 Watts DC Input 36 75 VDC 16 A maximum DC Output 5 VDC 0 5 A 12...

Страница 4: ...5 DB 9 DC 48 VDC PSU AS6712 32X AS6812 32X Open Network Installer Environment ONIE www edge core com PSU F2B F2B 2 3 1 1 2 1 3 56 cm 75 cm 4 ETSI ETS 300 253 14 AWG 12 VDC PSUs Edgecore ORSA 1U Open R...

Страница 5: ...IEC EN60950 1 DC converter 14 AWG 36 VDC 75 VDC PSU 10 AWG 12 VDC PSU DC PSU 6 LED PSU1 PSU2 LED 7 NOS 5 5e RJ 45 Mgmt NOS 2 1 1 2 3 2 1 4 1 3 2 4 1 1 1 ONIE NOS NOS ONIE NOS ONIE NOS NOS 8 RJ 45 100...

Страница 6: ...EN 55032 2012 AC 2013 Class A AS NZS CISPR 32 2013 Class A CISPR 32 2012 Class A EN 61000 3 2 2014 Class A EN 61000 3 3 2013 FCC Class A VCCI Class A CE Mark CCC GB 9254 2008 Class A BSMI EMI Standard...

Страница 7: ...2 x2 x20 x2 AC PSU DC PSU RJ45 DB 9 DC 48 VDC PSU AS6712 32X AS6812 32X ONIE F2B F2B 2 3 1 1 2 1 2 3 56 cm 75 cm 4 ETSI ETS 300 253 14 AWG 12 VDC PSU Edgecore ORSA 1U Open Rack Tray Set 3 1 1 2 1 1 2...

Страница 8: ...Converter UL IEC EN 60950 1 DC PSU 14 AWG 36 VDC 75 VDC PSU 10 AWG 12 VDC PSU DC PSU 6 LED PSU1 PSU2 LED 7 NOS 5 ohm 5 5e RJ 45 Mgmt NOS 2 1 1 2 3 2 1 4 1 3 2 4 1 1 1 ONIE NOS NOS ONIE NOS ONIE NOS N...

Страница 9: ...V 650 DC 12 VDC EN 55032 2012 AC 2013 Class A AS NZS CISPR 32 2013 Class A CISPR 32 2012 Class A EN 61000 3 2 2014 Class A EN 61000 3 3 2013 FCC Class A VCCI Class A CE Mark CCC GB 9254 2008 Class A B...

Отзывы: