Installation
Delivery
The mini-X cabinet is delivered pre-assembled, strapped to a pallet and shrink-wrapped with the
corners protected. When unloading, please check that no shocks have damaged the product. In case
of damage, please inform the carrier immediately or refuse the package.
- Carefully unpack the ISBC and check the minimum contents:
- The pre-wired cabinet,
- The inserted exchanger module,
- A folder containing this manual and the installation and operating documents
- The options delivered pre-assembled: Supervision, fire, UPS with standard autonomy, automatic
door opening...
- Options delivered separately: Long autonomy UPS battery, extension rack...
Place of installation
Please check that the floor can support the weight of the ISBC (see technical specifications) plus the
weight of the equipment to be inserted.
The ISBC must be installed on a perfectly level floor. One side of the cabinet can be attached to a wall.
At the front, allow enough space to insert the computer equipment, and at the back, enough space to
extract the air conditioning module.
Important: Observe distances to walls for proper use and maintenance
La FAB’ MDC
by
ecus
Page 7
Type
Mini-X 6kW
(exchanger AE65)
Mini-X 10kW
(exchanger AE100)
Free space on rear of the cabinet
800mm - 31,5 inch for maintenance access
Free space on front of the cabinet
1000mm - 39,37 inch for servers racking
Free space on sides
Not mandatory, but make wiring easier
Dimensions 42/47U
Width*Height*Depth(mm)
800X1000/1200x2000
800X1200x2000/2200
Tare weight 42/47U w/o options
Available weight fot client devices
220 kg - 485 lbs
1280 kg – 2822 lbs
223/230 kg - 491/507 lbs
1277/1270 kg – 2815/2800 lbs
Содержание La FAB' MDC ISBC Mini-X
Страница 5: ...Typical layout La FAB MDC by ecus Page 5...
Страница 11: ...La FAB MDC by ecus Page 11 X1...
Страница 17: ...La FAB MDC by ecus Page 17...
Страница 22: ...Appendix Simplified electrical recomended diagram any option La FAB MDC by ecus Page 22...
Страница 23: ...Programming 3 ways valve La FAB MDC by ecus Page 23 Switches sur ON...
Страница 24: ...Maintenance plan La FAB MDC by ecus Page 24...
Страница 25: ...La FAB MDC by ecus Page 25...
Страница 26: ...La FAB MDC by ecus Page 26...
Страница 27: ...La FAB MDC by ecus Page 27...