Ecus La FAB' MDC ISBC Mini-X Скачать руководство пользователя страница 1

Version

1.39:35.59

Date

03/24/21

Serie

Author EHA

Controle  NRE

 ISBC-4*81*-**-CmX(6-10)-*

Thank you for choosing our ISBC product, a Micro-DataCenter 
that brings together all the functions of a real DataCenter in a 
cabinet, quick and easy to install.

Depending on function and option selected, the component 
may differ (UPS, fire-fighting, Acces management, Monitoring 
etc), please refer to specific manual on 

www.ecus.fr/documentations-ecus

ecus

 -  capital de 100.000€  - FR02377732482

n

°5 Zac du quartier de la loge - RN141 - 16590 BRIE - FRANCE – Tel : +33 (0)545 65 77 77 - fax : +33 (0)535 54 28 82  email:

[email protected]

User and Installation manual

User and Installation manual

ISBC Mini-X

ISBC Mini-X

To get the most out of your product and to ensure

safe use, we recommend that you read and keep

this manual. 

Содержание La FAB' MDC ISBC Mini-X

Страница 1: ...e component may differ UPS fire fighting Acces management Monitoring etc please refer to specific manual on www ecus fr documentations ecus ecus capital de 100 000 FR02377732482 n 5 Zac du quartier de...

Страница 2: ...ule 13 Baie avec option 13 tanch it au sol 13 Temp rature recommand e pour l I T 13 R gulateur afficheur ST1 14 Alarmes 15 Principales signalisations d alarmes 15 Param tres de r gulation ST1 16 Modif...

Страница 3: ...osting of I T systems in the same way as a legacy data center We protect the systems against intrusion and the penetration of foreign bodies by a high protection rate against overheating by a closed l...

Страница 4: ...ront and solid sheet metal at the rear with a 180 opening angle double leaf optional Three point locking swivel handle and key lock access control in option Four 19 depth adjustable uprights front and...

Страница 5: ...Typical layout La FAB MDC by ecus Page 5...

Страница 6: ...ge 6 19 cabinet Power source A Client panel Power source B Client panel 19 Area for IT device A B Single power supply A B Double power supply UPS A option AC Exchanger PDU A A STS B EPO A STS B Extern...

Страница 7: ...t of the ISBC see technical specifications plus the weight of the equipment to be inserted The ISBC must be installed on a perfectly level floor One side of the cabinet can be attached to a wall At th...

Страница 8: ...Example of two ISBC mini X cabinets Equipped with two 10kW chillers Inertial tank for efficiency gain mandatory in free cooling Sectional view La FAB MDC by ecus Page 8...

Страница 9: ...attention must be paid to the materials used to make up the water circuits and any additives added to the water Ecus sells hydraulic kits to facilitate the installation of your mini X please refer to...

Страница 10: ...removed to the external cooler Condensates A cabinet that is proven to be watertight does not generate condensate after the doors are closed Condensate must be drained through a plastic pipe with the...

Страница 11: ...La FAB MDC by ecus Page 11 X1...

Страница 12: ...e heat in the rack cabinet AE100 setpoint 20 C pure water flow 1000l h air flow 1500m3 h closed loop AE65 setpoint 20 C pure water flow 1000l h air flow 1100m3 h closed loop La FAB MDC by ecus Page 12...

Страница 13: ...y U between the 19 uprights with the 1U containment panel set provided Cabinet with option The options UPS monitoring fire protection etc require additional commissioning please refer to their respect...

Страница 14: ...ST1 The front panel contains the display and the keypad made up of 4 buttons that when pressed alone or combined with other buttons are used to program the controller Display Fonctions La FAB MDC by e...

Страница 15: ...figuration parameters c To prevent random manipulation by unauthorized persons access to the configuration parameters is protected by a password that prevents unwanted modifications or access by unaut...

Страница 16: ...ing type c d F parameters This procedure can be used to access all the control parameters The password 77 can only be changed from the supervisor or using the configuration tool La FAB MDC by ecus Pag...

Страница 17: ...La FAB MDC by ecus Page 17...

Страница 18: ...tputs on the alarms in special operation depends on the dependence parameter see the chapter on Functions The controller also indicates alarms due to faults on the controller itself on the probes or i...

Страница 19: ...ific manuals Troubleshooting and service The ISBC is designed to be maintained and repaired by any refrigeration or electrical professional depending on the failure The sensitive components can be rep...

Страница 20: ...et BE CAREFUL not to damage the fittings under the exchanger when removing it Switch off the heat exchanger Close the water inlet outlet valves Disconnect the controller plug from the exchanger via th...

Страница 21: ...ng back to the front Condensate formation condensate is created when humid air comes into contact with a cold wall If condensate appears on the glass or a panel inside the cabinet this indicates that...

Страница 22: ...Appendix Simplified electrical recomended diagram any option La FAB MDC by ecus Page 22...

Страница 23: ...Programming 3 ways valve La FAB MDC by ecus Page 23 Switches sur ON...

Страница 24: ...Maintenance plan La FAB MDC by ecus Page 24...

Страница 25: ...La FAB MDC by ecus Page 25...

Страница 26: ...La FAB MDC by ecus Page 26...

Страница 27: ...La FAB MDC by ecus Page 27...

Страница 28: ...n Mesurer la tension en entr edu coffret de distribution V X X PDU Contr le des fixations V rifier le syst med accroche N A X X Test des fonctions et LED V rifier la marche des Leds et l affichage cra...