DANGER

 

 Only qualified electricians or contractors should 

attempt such installations, which must comply 

strictly with applicable codes, standards and regu-

lations.

1.1 UNPACKING/INSPECTION

After unpacking, carefully inspect the contents for damage.

This standby generator set is ready for installation with a factory 

• 

supplied and pre-mounted base pad and has a weather protec-

tive enclosure that is intended for outdoor installation only.

 

 If this generator is used to power electrical load 

circuits normally powered by a utility power 

source, it is required by code to install a transfer 

switch. The transfer switch must effectively isolate 

the electrical system from the utility distribution 

system when the generator is operating (NEC 700, 

701 & 702). Failure to isolate an electrical system 

by such means will result in damage to the gen-

erator and also may result in injury or death to 

utility power workers due to backfeed of electrical 

energy.

If any loss or damage is noted at time of delivery, have the 

person(s) making the delivery note all damage on the freight bill 

or affix their signature under the consignor's memo of loss or 

damage.
If a loss or damage is noted after delivery, separate the damaged 

materials and contact the carrier for claim procedures.
“Concealed damage” is understood to mean damage to the con-

tents of a package that is not in evidence at the time of delivery, 

but is discovered later.
To properly open the roof, press down on the center top lip and 

release the latch. If pressure is not applied from the top, the roof 

may appear stuck. Always verify that the side lock is unlocked 

before attempting to lift the roof.

1.2 PROTECTION 

SYSTEMS

Unlike an automobile engine, the generator may have to run for 

long periods of time with no operator present to monitor engine 

conditions.  For that reason, the engine is equipped with the fol-

lowing systems that protect it against potentially damaging condi-

tions:
1.  Low Oil Pressure Sensor
2.  High Temperature Sensor
3. Overcrank
4. Overspeed
5. RPM 

Sensor

6. Low 

Battery

There are readouts on the control panel to notify personnel that one 

of these failures has occurred.  There is also a System Set LED 

(single cylinder) or a Status message on the display (V-twins) that 

displays when all of the conditions described in the "System Set 

LED" section are true.

1.3   NEC REQUIREMENT FOR ARC FAULT 

CIRCUIT INTERRUPTION BREAKER FOR 
BEDROOMS

In 2001, the National Electric Code (NEC) introduced a requirement 

for new construction. This new requirement indicates the need for 

Arc Fault Circuit Interrupters to be used to protect the complete 

branch circuit that feeds a dwelling bedroom. The actual NEC 

requirement is indicated below.

1.3.1   SECTION 210.12 ARC FAULT CIRCUIT INTER-

 

‹

RUPTER PROTECTION

1.  Definition:  An arc fault circuit interrupter is a device intended 

to provide protection from the effects of arc faults by recog-

nizing characteristics unique to arcing and by functioning to 

de-energize the circuit when an arc fault is detected.

2.  Dwelling Unit Bedrooms:  All branch circuits that supply 125 

volt, single-phase, 15 and 20 ampere outlets installed in 

dwelling unit bedrooms shall be protected by an arc fault cir-

cuit interrupter listed to provide protection of the entire branch 

circuit.

Section 210.12 requires that AFCI protection be provided on branch 

circuits that supply outlets (receptacle, lighting, etc.) in dwell-

ing bedrooms. The requirement is limited to 15 and 20 ampere, 

125 volt circuits. There is no prohibition against providing AFCI 

protection on other circuits or in locations other than bedrooms. 

Because circuits are often shared between a bedroom and other 

areas such as closets and hallways, providing AFCI protection on 

the complete circuit would comply with 210.12.
If during the installation of the home standby system the decision 

is made to provide back up power to a bedroom branch circuit, 

then the circuit breaker in the transfer switch should be replaced 

with an Arc Fault Circuit Interrupter.
It is most important that breakers only be switched like for like. 

For instance, if replacing a 15A breaker, it MUST be replaced with 

a 15A AFCI breaker. Likewise, a 20A breaker MUST be replaced 

with a 20A AFCI.
These AFCI breakers are available at the nearest hardware store.
Eaton Cat # 

Description

BR115AF 

1" 15A Single Pole AFCI

CH115AF 

3/4" 15A Single Pole AFCI

BR120AF 

1" 20A Single Pole AFCI

CH120AF 

3/4" 20A Single Pole AFCI

Section 1 — General Information

Air-cooled Generators

 4 

Содержание 10kW

Страница 1: ...20kW Air cooled Automatic Standby Generators DANGER DEADLY EXHAUST FUMES OUTDOOR INSTALLATION ONLY Not intended for use as Primary Power in place of utility or in life support applications LISTED C US...

Страница 2: ...on each indicates follows This symbol points out important safety informa tion that if not followed could endanger per sonal safety and or property of others This symbol points out potential explosion...

Страница 3: ...re Initial Startup 14 2 2 Electrical Checks 14 2 3 Generator Tests Under Load 15 2 4 Checking Automatic Operation 15 2 5 Engine Governor Adjustment 16 2 6 Voltage Regulator Adjustment 16 Section 3 Ope...

Страница 4: ...able codes and standards Install a battery operated carbon monoxide alarm indoors according to manufacturer s instructions recommendations Adequate unobstructed flow of cooling and ventilating air is...

Страница 5: ...ator is installed in accordance with the manufacturer s instructions and recommendations Following proper installa tion do nothing that might alter a safe installation and render the unit in noncompli...

Страница 6: ...rred There is also a System Set LED single cylinder or a Status message on the display V twins that displays when all of the conditions described in the System Set LED section are true 1 3 NEC REQUIRE...

Страница 7: ...ration of the engine s life This engine is certified to operate on Liquid Propane fuel and pipeline Natural Gas The emission control system on the generator consists of the following Fuel Metering Sys...

Страница 8: ...site Base Oil Filter Battery Compartment Fuel Regulator Fuel Inlet back Air Filter Circuit Breakers GFCI Outlet All 17 20kW Control Panel Figure 1 3 14 17 and 20kW V twin GT 990 GT 999 Engine door rem...

Страница 9: ...cent for each 1 000 feet above sea level and also will decrease about 1 percent for each 6 C 10 F above 16 C 60 F ambient temperature Load current values shown for 120 volts are maximum TOTAL values f...

Страница 10: ...talled verify that the fuel pressure NEVER drops below four 4 inches water column for natural gas or 10 inches water column for liquid propane Prior to installation of the generator the installer shou...

Страница 11: ...oor and close the roof 8 Reverse the procedure to convert back to natural gas Figure 1 4 Fuel Selector NOTE Use an approved pipe sealant or joint compound on all threaded fittings to reduce the possib...

Страница 12: ...st four 4 feet of clear ance above the generator three 3 feet of clearance on sides and front and 18 inches of clearance at back of unit Install the unit where rain gutter down spouts roof run off lan...

Страница 13: ...has been demonstrated that a fire within the enclosure will not ignite combustible materials outside the enclosure Annex A Explanatory Material A4 1 4 2 Means of demonstrating compliance are by means...

Страница 14: ...t of the generator should be 36 inches This would include shrubs trees and any kind of vegetation Clearance at the top should be a minimum of 48 inches from any structure overhang or projections from...

Страница 15: ...loding A battery presents a risk of electrical shock and high short circuit current The following pre cautions are to be observed when working on batteries Remove the 7 5A fuse from the generator cont...

Страница 16: ...o the dipstick FULL mark with the recommended oil Do not fill above the FULL mark 5 Check the fuel supply Gaseous fuel lines must have been properly purged and leak tested in accordance with applicabl...

Страница 17: ...o its ON or CLOSED position Loads are now powered by the standby generator 9 Turn ON the load center fed by the transfer switch T1 and T2 10 Connect an accurate AC voltmeter and a frequency meter acro...

Страница 18: ...UNITS NOTE All V twin units DO NOT require an engine governor adjustment due to their design 2 5 3 ADDITIONAL CORROSION PROTECTION Periodically spray all engine linkage parts and brackets with corro...

Страница 19: ...nerator Control Panel ENTER ECS 3 1 2 SETTING THE EXERCISE TIMER This generator is equipped with an exercise timer Once it is set the generator will start and exercise every seven days on the day of t...

Страница 20: ...ys This page can be accessed at any time with several presses of the dedicated Escape key Each press of the Escape key takes you back to the previous menu until the main menu is reached This page disp...

Страница 21: ...seconds Will transfer back when utility returns for 10 consecutive seconds The engine will continue to run until removed from the Manual mode 2 Auto Will start and run if Utility fails for 10 consecut...

Страница 22: ...ystem to automatic operation as outlined in Automatic Transfer Operation section 3 5 SIDE COMPARTMENT V TWIN ONLY FIGURES 3 4 3 5 Local codes may require this compartment to be locked A hasp is provid...

Страница 23: ...Temperature Switches Oil Filter Oil Drain Hose Low Oil Switch HighTemp Switch Loosen NOTE The oil drain hose may be routed in the opposite direction as shown in figure Over Speed Shutdown Alarm 4320...

Страница 24: ...The maintenance counters will be adjusted to the new time and date NOTE Since most maintenance alerts will occur at the same time most have two 2 year intervals only one will appear on the display at...

Страница 25: ...ngine by moving the AUTO OFF MANUAL switch to MANUAL and run until it is thoroughly warmed up Then shut OFF the engine by moving the switch to the OFF position 2 Immediately after the engine shuts OFF...

Страница 26: ...e location of the air cleaner Use the following procedure Figure 4 6 1 Lift the roof and remove the door 2 Turn the worm gear clamp screw counterclockwise to loos en 3 Pull the old filter off the divi...

Страница 27: ...ctrolyte has been known to be harmful to the skin and eyes and to be toxic The electrolyte is a dilute sulfuric acid that is harmful to the skin and eyes It is electrically conductive and corrosive Th...

Страница 28: ...n wrench and tighten the rocker arm jam nut Tighten the jam nut to 174 in lbs torque After tightening the jam nut recheck valve clearance to make sure it did not change Install new valve cover gasket...

Страница 29: ...2 Check the tag on the engine for oil viscosity and classification Verify that the correct recommended oil is used in the engine see the Engine Oil Recommendations section If necessary drain and refi...

Страница 30: ...ING Enclosure louvers X X W BATTERY Remove corrosion ensure dryness X X M Clean and tighten battery terminals X X M Check charge state X R EVERY 6 M Electrolyte level X R EVERY 6 M ENGINE AND MOUNTING...

Страница 31: ...2 Clean re gap or replace plug s 3 Fuel pressure incorrect 3 Confirm fuel pressure to regulator is 10 12 water column 0 36 0 43 psi for LP and 5 7 water column 0 18 0 25 psi for natural gas 4 Fuel sel...

Страница 32: ...to select the the desired screen refer to the Menu System diagram 6 1 1 CHANGING SETTINGS EDIT MENU To change a setting such as display contrast go to the EDIT menu and use the keys to navigate to the...

Страница 33: ...or Other 60 Hz The possible Status messages of the display are as follows Switched Off Time Date Ready to Run Time Date Utility Loss Delay Pausing for X Seconds Cranking Attempt X Running in Exercise...

Страница 34: ...RAL GROUND POWER LEADS AND TRANSFER SWITCH LEADS MUST BE RUN IN TWO DIFFERENT CONDUITS EXCEPTIONS IF THE INSULATION RATING ON ALL WIRING IS RATED FOR 600V AND THE LENGTH OF THE CONDUIT IS 30 ft OR LES...

Страница 35: ...NEUTRAL GROUND UTILITY METER SOCKET POWER LEADS AND TRANSFER SWITCH LEADS MUST BE RUN IN TWO DIFFERENT CONDUITS EXCEPTIONS IF THE INSULATION RATING ON ALL WIRING IS RATED FOR 600V AND THE LENGTH OF T...

Страница 36: ...34 Section 7 Installation Diagrams Air cooled Generators Generator Drawing No 0G8280 D...

Страница 37: ...35 Section 7 Installation Diagrams Air cooled Generators Generator Drawing No 0G8280 D...

Страница 38: ...e neglect improper maintenance or unapproved modifications or the use of counterfeit and or grey market parts not made supplied or approved by Generac You are responsible for contacting a Generac Auth...

Страница 39: ...section 4 below Any such emissions related part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period prior to the first scheduled replacement poi...

Страница 40: ...Part No 0H4762 Revision A 07 28 09 Printed in U S A...

Отзывы: