SAFETY RELIEF VALVE [ Figure 2, Page 7 ]

Safety relief valve is required on your boiler. Water expands 

as it is heated. If there is no place for water to expand 

into, water pressure will build up inside boiler and system. 

Should this happen, safety relief valve will automatically 

open at predetermined pressure. This will relieve the strain 

on boiler and system. Run pipe from relief valve outlet 

(pipe must be same size as outlet and open end must not 

be threaded) to open drain, tub or sink, or other suitable 

drainage point not subject to freezing. Failure to do so may 

cause water damage or injury should safety relief valve 

release. 

EXPANSION TANK

Expanding water 

fl

 ows into expansion tank. Tank should 

be correct size. Tank is 

fi

 lled with air. As water expands it 

compresses air in the tank to form air pressure cushion. 

This “spring-like” cushion serves to maintain correct 

operating water pressure regardless of water temperature. 

This assures “full measure” of water, even in highest 

radiation unit of system. It also prevents blowing off of 

safety relief valve. Air in tank in beginning (with system 

fi

 lled with cold water) is suf

fi

 cient for proper operation. 

Tank also serves as trap for excess air in system. Air 

would cause gurgling in pipes and in ef

fi

 cient circulation in 

radiators if left in system.
It is possible for tank to become “waterlogged” (

fi

 lled 

with water). It can also become over

fi

 lled with air. This 

can happen after 

fi

 lling system with new water. Fittings 

provided on tank and in line to tank are for bleeding off 

excess water or air. 
When installing this tank, it is important: 

1. 

Tank be higher than boiler top. 

2. 

Pipe to tank continuously rises up to tank (so air 

can “bubble” up to it). 

DIAPHRAGM TYPE EXPANSION TANK

Diaphragm type expansion tank takes place of conventional 

expansion tank. Carefully read instructions packed with 

your tank assembly. 
Tank comes with 10-12 pounds per square inch air charge. 

This is the same as pressure produced in system by 

automatic 

fi

 ll valve. When system is 

fi

 rst 

fi

 lled, tank will 

contain little or no water. 
As water is heated its pressure increases. It expands into 

tank, compressing air in tank. Compressed air cushion 

permits water in system to expand as temperature 

changes. Diaphragm type tank can be mounted on air 

purger 

fi

 tting or at any convenient place in supply or return 

line.

AIR ELIMINATING FITTING (AIR PURGER)

Air purger is used to remove excess air from system. It 

is installed in supply line. It will eliminate air from water 

before it reaches radiators and bleed off this air.

MAIN AIR VENT FOR DOWN FLOW SYSTEMS OR 

DIAPHRAGM TYPE EXPANSION TANK

Before system is 

fi

 lled with water, there is air in pipes and 

radiation units. Some of it will be trapped as system is 

fi

 lled . It is possible to eliminate most of this air through 

air vent on radiation units. Main air vent will speed and 

simplify this. Install on highest point in supply main when 

all radiation is below top of boiler. 

AUTOMATIC FILL VALVE

For a safe, ef

fi

 cient operation, hot water system must be 

completely 

fi

 lled

 with water. Adding new water, when 

needed can be done manually (by use of hand valve in 

water supply line). Requires regular attention to system’s 

needs. Automatic 

fi

 ll valve accomplishes this without 

attention. Install in supply line on hot water boilers only. 

Valve operates through water pressure differentials. It does 

not require electrical connection.

DRAIN VALVE

Manual valve provides means of draining all water from 

boiler and system. It is often installed in 3/4” tapping at 

bottom of end boiler section. Or it can be installed in tee 

where return line enters boiler.

EQUIPMENT & OPTIONAL ACCESSORIES

WATER TEMPERATURE CONTROL

Water temperature limit control in relay is adjustable
and may be set as necessary. It may be set as low as 

140°F, or as high as 220°F. This depends on type and 

amount of radiation involved and weather conditions.

CIRCULATING PUMP

Every forced hot-water system requires circulating pump. 

Separate pump or zone valve is required for each zone, 

if you have a two or more zone system. Pump must have 

capacity to provide circulation required by your system. 

Pump is connected into main just ahead of boiler. It is also 

wired to electrical system.

BLOWER (Draft Inducer)

Blower provides means for pulling air through boiler and 

exhausting 

fl

 ue gasses into vent system. Blower shuts 

off when burners are not 

fi

 ring. This keeps heat in house 

rather than having it go up chimney.

 WARNING

Burn 

and scald hazard.  Safety relief valve could       

discharge steam or hot water during operation.       

Install discharge piping per these instructions

.

!

     

Содержание PENNCO FSB 3 Series

Страница 1: ... P N 240009022 Rev B 04 2012 An ISO 9001 2008 Certified Company Tested for 50 psi ASME Working Pressure C S A Certified for Natural gas or Propane Manufactured by ECR International Inc 2201 Dwyer Avenue Utica NY 13504 4729 web site www ecrinternational com Models FSB 2 FSB 3 FSB 4 FSB 5 FSB 6 FSB 7 ...

Страница 2: ...his boiler must be performed by a qualified installer TO THE INSTALLER Leave all instructions with boiler for future reference When this product is installed in the Commonwealth of Massachusetts the installation must be performed by a Licensed Plumber or Licensed Gas Fitter WARNING Fire explosion asphyxiation and electrical shock hazard Improper installation could result in death or serious injury...

Страница 3: ... upon Net AHRI Rating being equal to or greater than calculated heat loss of building Manufacturer should be consulted before selecting a boiler for installations having unusual piping and pickup requirements This boiler cannot be used with all types of chimneys Read these instructions carefully before installing These Gas Fired Hot Water Boilers are low pressure sectional cast iron boilers Design...

Страница 4: ...4 DIMENSIONS Model Width A FSB 2 11 FSB 3 14 1 4 FSB 4 17 1 2 FSB 5 20 3 4 FSB 6 24 FSB 7 27 1 4 ...

Страница 5: ...rting installation See rating and capacity table 8 When installed in utility room door should be wide enough to allow largest boiler part to enter or to permit replacement of another appliance such as water heater 9 Boiler installed in building under construction take care to insure clean combustion air supply during construction process Airborne particulates such as from drywall dust and from fib...

Страница 6: ...s communicating directly or by ducts with outdoors о Two Permanent Opening Method Provide opening commencing within 12 inches of top and second opening commencing within 12 inches of bottom enclosure Direct communication with outdoors or communicating through vertical ducts Provide minimum free area of 1 in2 per 4 Mbh of total input rating of all appliances in enclosure Communicating through horiz...

Страница 7: ...hall be installed to relief valve outlet connection to avoid burns scalding or water damage due to discharge of steam and or hot water during operation Discharge line shall connect to relief valve outlet and piped down to safe point of disposal Check local codes for maximum distance from floor or allowable safe point of discharge be of pipe size equal to or greater than that of the relief valve ou...

Страница 8: ...8 INSTALLATION SYSTEM PIPING Figure 3 Forced Hot Water Typical Piping Figure 4 Forced Hot Water Typical Piping With Zone Control Valve ...

Страница 9: ... exposed to refrigerated air circulation piping system shall be equipped with flow control valves or other automatic means to prevent gravity circulation of boiler water during cooling cycle INSTALLATION SYSTEM PIPING Figure 5 Piping Arrangements For Boiler When Used In Connection With Refrigeration System Low Design Water Temperature Systems Below 140 F And Large Water Content Systems Condensatio...

Страница 10: ... as directly as possible with as few elbows as possible 7 Where possible it is recommended to common vent water heater and boiler Consult appropriate Vent Sizing Tables in National Fuel Gas Code for specific requirements of multiple appliance venting 8 Boiler is only appliance connected to vent Type B vent pipe is recommended for vent connector 9 Slope pipe up from boiler to chimney not less than ...

Страница 11: ...on to gas vents or chimneys vent installations shall be in accordance with Venting of Equipment of the National Fuel Gas Code ANSI Z223 1 NFPA 54 or applicable provisions of the local building codes Figure 7 Type B Gas Vent 11 VENT INSTALLATION ...

Страница 12: ...ing system Turn on any exhaust fans such as range hoods and bathroom exhausts so they will operate at maximum speed Do not operate a summer exhaust fan Close fireplace dampers 4 Place in operation the appliance being inspected Follow the lighting instructions Adjust thermostat so appliance will operate continuously VENT INSTALLATION 5 Test for spillage at the draft hood relief opening after 5 minu...

Страница 13: ...ameter 90 elbow or 3 feet of straight pipe for 3 diameter 90 elbow 2 3 4 5 Section Boilers use 3 vent pipe for 6 7 Section Boilers use 4 vent pipe CHOICE OF VENT PIPE MATERIAL U L Listed Z Flex Z Vent Stainless Steel Vent Pipe U L Listed Heat Fab Saf T Vent Stainless Steel Vent Pipe U L Listed Flex L Star 34 Stainless Steel Vent Pipe U L Listed ProTech Systems FasNSeal Stainless Steel Vent Pipe IN...

Страница 14: ...90 elbow pointing down fitted with a minimum 1 4 mesh screen to keep out rodents and birds The elbow shall be of the same material and size as vent pipe The elbow exit should be at least 6 away from exterior wall as shown in Figure 8 or B Tjernlund VH 1 Series side wall vent hood For 2 3 4 5 section boilers use VH 1 3 For 6 7 section boilers use VH 1 4 7 Vent Pipe Termination Location See Figure 9...

Страница 15: ...regulators and relief equipment See Figure 9 United States Terminate vent system at least 4 feet 1 22m horizontally from and in no case above or below unless a 4 feet 1 22m horizontal distance is maintained from electric meters gas meters regulators and relief equipment HORIZONTAL VENTING INSTRUCTIONS Figure 9 Horizontal Venting Clearances A The venting system shall terminate at least 4 feet below...

Страница 16: ...efore operating appliance B For Heat Fab Saf T Vent stainless steel vent pipe use a high temperature silicone sealant rated for 550 F The outside of the male end and inside of the female end of the pipe must be cleaned before applying the silicone bead For 3 vent pipe runs the male end of the vent pipe which goes over the outlet of the boiler s induced draft blower must be crimped The vent pipe sh...

Страница 17: ...e boiler to prevent collection of condensate throughout the assembly 7 Allow the sealant to cure for 24 hours before operating the appliance D For ProTech Systems FasNSeal stainless steel vent pipe no cleaning fluid is required For 3 vent pipe runs on 2 3 4 and 5 section boilers begin by locating the FasNSeal Ametek Adapter over the boiler s induced draft blower Continue the vent pipe run with 3 F...

Страница 18: ...ols Power Venter 2 3 4 5 SWG 4D 6 7 SWG 5D Some possible reasons for using a power venter for sidewall venting 1 May be preferred by local codes 2 Need a vent piping run beyond 30 9 1m but not more than 50 15 2m 3 The boiler installation site experiences gusting or high winds A power venter can help prevent the boiler from short cycling due to gusting or high winds by providing vent exhaust pressu...

Страница 19: ...ng Install manual shut off valve in vertical pipe about 5 feet 1 5m above floor See Figure 10 Tighten all joints securely Propane gas connections should only be made by licensed propane installer Two stage regulation should be used by propane installer Propane gas piping should be check by propane installer Check Gas Supply Gas pipe must be correct size for length of run and for total BTU per hour...

Страница 20: ...apacity BTU Per Hour Input Includes Fittings 1 1 20 92 000 190 000 350 000 625 000 40 63 000 130 000 245 000 445 000 60 50 000 105 000 195 000 365 000 Table 6 PROPANE GAS Length of Pipe Ft Pipe Capacity BTU Per Hour Input Includes Fittings Copper Tubing Iron Pipe 20 131 000 216 000 189 000 393 000 40 90 000 145 000 129 000 267 000 60 72 000 121 000 103 000 217 000 ...

Страница 21: ...not install a thermostat where it will be affected by drafts hot or cold pipes sunlight lighting fixtures televisions a fireplace or a chimney 4 Check thermostat operation by raising and lowering thermostat setting as required to start and stop the burners 5 Instructions for the final adjustment of the thermostat are packaged with the thermostat adjusting heating anticipator calibration etc 6 Set ...

Страница 22: ...ler water temperature reaches high limit set point high limit contacts open cutting power to blower and pilot control Burners extinguish and blower stops Circulator pump continues to run as long as the thermostat continues to call for heat When boiler water temperature drops past the high limit set point and through the differential high limit contacts close repeating steps 3 7 9 If venting system...

Страница 23: ...23 WIRING DIAGRAMS Figure 12 Control Module Damper is not an option ...

Страница 24: ...ss Repeat until you have covered every radiation unit in system End at highest unit in system If units have automatic vents manual venting is unnecessary but it will speed up proper filling of system If system is closed expansion tank system you may have automatic fill valve Leave it open to refill system automatically as needed Check temperature pressure gauge Note position of hand indicating pre...

Страница 25: ...nob WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life This appliance is equipped with an ignition device which automatically lights burner Do NOT try to light this burner by hand Before operating smell all around appliance area for gas Be sure to smell next to floor because some gas is heavier than air and...

Страница 26: ...equire primary air adjustment and are not equipped with primary air shutters Main burner flames form sharp blue inner cones in softer blue outer mantel with no yellow Puffs of air from blow ing on flame or stamping on floor will cause flames to turn orange momentarily This is not unusual Remain still when observing main burner flames See Figure 16 Page 27 If flame appearance is not correct check m...

Страница 27: ... supply to burners 3 Turn your thermostat up to call for heat and let your boiler run until temperature of water reaches limit setting Gas valve shuts off and circulator keeps running until thermostat is satisfied or water cools enough to restart burners through limit control 4 To check operation of contacts in pressure switch disconnect rubber tubing located between blower and pressure switch fro...

Страница 28: ...water left in to freeze will crack pipes and or boiler Cleaning Your Boiler And Burners Flue passages between sections should be examined yearly and cleaned if necessary To clean Remove burners pilot and vent pipe Remove top and front jacket panels Remove two screws attaching intermediate front panel to left and right side jacket panels Remove control panel as a unit Remove draft diverter and inte...

Страница 29: ...ctrical contact Check all control terminals and wire joints Chimney flue is blocked Pressure switch will not close and pilot spark will not operate to start pilot Have your service technician check and correct if necessary Rollout switch blown Have your service technician check heat exchanger for blockage Replace rollout switch with exact replacement IF BURNER IS NOISY POSSIBLE CAUSE WHAT TO DO Ga...

Страница 30: ...to expand as temperature changes Diaphragm type tank can be mounted on air purger fitting or at any convenient place in supply or return line AIR ELIMINATING FITTING AIR PURGER Air purger is used to remove excess air from system It is installed in supply line It will eliminate air from water before it reaches radiators and bleed off this air MAIN AIR VENT FOR DOWN FLOW SYSTEMS OR DIAPHRAGM TYPE EX...

Страница 31: ...ked Factory Pressure Switch Set point 0 4 wc for 2 5 section boilers 0 5 w c for 6 7 section boilers Rollout Switch FLAME ROLLOUT SAFETY SHUTOFF Rollout switch is temperature sensitive fuse link device Located on boiler base just outside fire box In event of heat exchanger flueway blockage causing flame to roll out of fire box fuse does not change in appearance when blown If rollout switch blows i...

Страница 32: ... using wire nuts Ensure remaining Molex plug connectors have not worked loose during transit Check sensing bulb is fully inserted in well and is not loose A 3 Adjusting Settings To discourage unauthorized changing of settings procedure to enter adjustment mode is required To enter adjustment mode press UP DOWN and I buttons see Figure 1 simultaneously for three seconds Press and release I button u...

Страница 33: ...tion was not detected and delay is called before retry Recycle delay Flame signal was lost and delay is called before retry 11 Wait for pressure switch to open failed to close Inducer is still off Pressure switch has not opened at beginning of heat cycle Alarm is sent but no lockout occurs 12 Wait for pressure switch to close failed to open Inducer is on Pressure switch has not closed at beginning...

Страница 34: ...kout models must be reset through key buttons and display On retry models wait for retry or reset at thermostat Check for correct installation and wiring before replacing any component Control module cannot be repaired If it malfunctions it must be replaced Use only qualified service agent to service ignition systems 1 Perform checkout as first step in troubleshooting 2 Check troubleshooting guide...

Страница 35: ...out Soft lockout is reset after one hour if alarm reason disappears 63 Soft lockout maximum number of recycles exceeded Soft lockout 64 Soft Lockout electronics failure On board self diagnostics detected error Soft lockout 65 Over temperature error Sensor measured temperature in excess of maximum allowable limit Soft lockout Note Soft lockout time is 1 hour or manual reset Hard lockout requires ma...

Страница 36: ...aged wire Check for cracked ceramic insulator which can cause short to ground and replace igniter sensor if necessary At gas valve disconnect main valve wire from MV terminal Turn on power and set thermostat to call for heat Pilot should light main burner will remain off because main valve actuator is disconnected Check pilot flame Verify it is blue steady and envelops 3 8 to 1 2 in 10 to 13 mm of...

Страница 37: ...Date Service Performed Company Name Tech Initials Company Address Phone ...

Страница 38: ...NOTES ...

Страница 39: ...Date Service Performed Company Name Tech Initials Company Address Phone ...

Страница 40: ...PENNCO BOILERS 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com ...

Отзывы: