ECP240R
RATINGS:
Voltage:
US/CA: 120/240V~, 2W + N + PE,
60Hz, 2.7A
International: 240V~, 50Hz, 2.7A
Configuration:
3-wire plus ground (US)
2-wire plus ground (International)
Capacitance:
30µf (US)
Line Current:
2.7 A
KVA Rating:
.65 at 240V AC
TeST pRoCeduReS:
1. Energize the power panel.
2. Close the circuit breaker leading to the
EcoPower4™ unit.
3. Check if Line 1 and Line 2 indicator lights
are on:
IF NO - De-energize the unit and check if
cables are connected correctly.
NOTE: For international appliances, only
1 indicator light may be on.
Check the ground cable connections.
If problem persists, call EcoTrust Energy
at 1.800.989.2299.
4. Keep these instructions near the unit for
future use.
EcoPower4
ECP240R
LINE
RED
BLACK
GREEN
WHITE
L1
L1
L2
L2
NEU
BUS
GND
BUS
20A
BREAKER
POWER PANEL
LINE
BROWN
GREEN WITH YELLOW STRIPE
BLUE
L
L
NEU
BUS
GND
BUS
20A
BREAKER
POWER PANEL
EcoPower4
ECP240R
US/CANADIAN INSTALLATION
INTERNATIONAL INSTALLATION
3. Run conduit (according to code) between the conduit connector on the box and the
power panel, and feed the connection cables through the conduit into the power
panel.
instaLLation ProcedUres:
1. If possible, de-energize the power panel prior to connection of the EcoPower4™
unit.
2. Install the circuit breaker onto the power panel.
3. US/Canadian Installation - Connect the (red) L1 and (black) L2 wires to the circuit
breaker, the ground cable (green) to the ground bus, and the neutral cable (white) to
the neutral bus, as shown in the diagram below.
4. International Installation (240V, 50Hz) - Connect the brown wire (hot) to the circuit
breaker, the ground wire (green with yellow stripe) to the ground bus, and the blue
wire to the neutral bus as shown in the diagram below.